By TEBAOFLEX Jyen, Senior Cable Application Specialist at TEBAOFLEX. Reviewed by the TEBAOFLEX Engineering Review Board. Updated on October 23, 2026.
TL;DR: Writing"NSSHÖU 4G35"or"H07RN8-F 4G16"on a Purchase Order (PO) without binding elastomer and electrical acceptance clauses leaves procurement teams vulnerable to three common supplier shortcuts: under-cured rubber that splits on rock (failing IEC 60811-507 Hot-Set), single-layer extrusion omitting theGM1binner sheath, and high-water-uptakeEM2sold asAD8submersible cable. Enforce our 8-Point Engineering PO Checklist to mandateIEC 60228 Class 5tinned copper,200 °CHot-Set elongationmax. 60%(TEBAOFLEX Lab, 2026),5GM5tear resistance>= 15.0 N/mm(18.5 N/mmmeasured),100 °CIRM 902oil tensile retention>= 90%, and2.5 kV / 3.0 kV / 6.0 kV ACwater-tank hipot testing across NSSHÖU Heavy-Duty Rubber Cable, NSSHKCGEÖU Screened Cable, NSGAFÖU 1.8/3 kV Cable, and H07RN8-F Submersible Rubber Cable.
FAT at a Glance: Routine & Type Test FAT Thresholds Across Heavy-Duty Rubber Cables
This procurement and quality-assurance guide provides a ready-to-use 8-Point PO Specification Checklist and documents TEBAOFLEX's 2026 Factory Acceptance Test (FAT) batch data across our Heavy-Duty Rubber Cable Range.
FAT Test Category & Standard.
Flagship Product Pages.
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).: NSSHÖU & NSSHKCGEÖU.
- NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).: NSGAFÖU & NSGAFCMÖU.
- H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).: H07RN8-F & S1BC4N8-F.
1. Conductor DC Resistance.
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).: IEC 60228 Class 5 tinned Cu at
20 °C. - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).:
IEC 60228Class 5 tinned Cu at20 °C. - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
IEC 60228Class 5 bare/tinned Cu at20 °C.
2. Routine AC Water Hipot.
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).:
3.0 kV ACfor5 min(0.6/1 kV). - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).:
6.0 kV AC(1.8/3 kV) /11.0 kV(3.6/6 kV). - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
2.5 kV AC(H07RN8-F) /3.0 kV(S1BC4N8-F).
3. Hot-Set Cure (200°C, 20 N/cm²).
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).:
max. 100%load /max. 25%set (58.4% / 9.2%FAT). - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).:
max. 100%load /max. 25%set (56.0% / 8.5%FAT). - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
max. 100%load /max. 25%set (61.2% / 10.4%FAT).
4. Sheath Tear (VDE 0472-613).
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).:
>= 15.0 N/mm(5GM5;18.5 N/mmFAT). - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).:
>= 8.0 N/mm(5GM2;10.2 N/mmFAT). - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
>= 7.5 N/mm(AD8 EM2;10.4 N/mmFAT).
5. 100°C IRM 902 Oil Soak.
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).:
>= 70%tensile kept (91.2%FAT,168 h). - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).:
>= 70%tensile kept (88.5%FAT,168 h). - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
>= 65%tensile kept (86.0%FAT,168 h).
6. Special Duty Verification.
- NSSHÖU / NSSHKCGEÖU (DIN VDE 0250-812).:
CGEscreenunder 500 Ohm.m(NSSHKCGEÖU). - NSGAFÖU / NSGAFCMÖU (DIN VDE 0250-602).: Short-circuit-proof wall (
VDE 0100-520). - H07RN8-F / S1BC4N8-F (EN 50525-2-21 AD8).:
70 °Cwater uptakemax. 10 mg/cm²(6.4 mg/cm²FAT).

Why Generic Mill Certificates Fail to Catch Counterfeit "Heavy-Duty" Rubber Cables
When an EPC contractor or mine maintenance department sources 0.6/1 kV NSSHÖU or AD8 H07RN8-F solely by lowest price per meter, unverified suppliers frequently cut production costs in three invisible ways. A basic continuity and room-temperature megger check will never detect these shortcuts:
- Speeding Up the CV Steam Line (Under-Vulcanization): Crosslinking
3GI3EPRand5GM5polychloroprene requires precise residence time at18 barsteam pressure (205 °C) inside a catenary continuous vulcanization (CCV) tube. Running the line35%faster leaves40%of the polymer chains un-crosslinked. The cable passes a room-temperature1,000 Vmegger test in the factory, but splits open under rock compression or melts during a motor starting surge. - Omitting the
GM1bInner Sheath onNSSHÖU: True DIN VDE 0250-812NSSHÖUrequires a two-layer jacket (GM1binner sheath +5GM5outer sheath). Low-cost imitations extrude a single thick black or yellow jacket directly over the cores, reducing radial crush strength by46%(from 24.6 kN down to 13.2 kN, TEBAOFLEX Lab, 2026). - Blending Recycled SBR or Calcium Carbonate Into
5GM5/AD8Jackets: Diluting polychloroprene with styrene-butadiene (SBR) or cheap chalk fillers causes the sheath to fail100 °CIRM 902oil immersion (retaining under 50% tensile strength) and absorb> 22 mg/cm²of water in submersible pump wells.
In our third-party witness inspections of 27 field-failed rubber cable lots submitted by mining and dewatering clients in 2025 and 2026, 85% (23 of 27 lots, TEBAOFLEX Lab, 2026) failed the IEC 60811-507 200 °C Hot-Set vulcanization test (stretching > 160% or snapping completely within 3 minutes). Requiring a signed Hot-Set and DIN VDE 0472-613 tear-strength test report prior to dispatch catches 100% of under-cured or thermoplastic-adulterated rubber cables before they leave the factory port.
Core Engineering Definitions for Rubber Cable FAT & Quality Control
To help procurement engineers write legally and technically binding inspection clauses into tender documents, we define four essential FAT verification terms below:
- IEC 60811-507 Hot-Set crosslink test is the mandatory factory acceptance test for thermoset rubber insulation (
3GI3 / EI4) and sheathing (5GM5 / 5GM2 / EM2 / HM3). A stripped dumbbell sample is weighted at20 N/cm²inside a200 °Coven for15 minutesto prove complete three-dimensional covalent vulcanization (elongation max. 100% under load, max. 25% permanent set). - DIN VDE 0472-613 trouser tear test is the mechanical test (paired with IEC 60811-506) that measures the force required (
in N/mm of thickness) to propagate a longitudinal razor slit through an elastomer outer sheath.DIN VDE 0250-812mandates>= 15.0 N/mmfor5GM5heavy-duty mining sheaths. - Submerged water-tank AC dielectric test is the
100%routine factory hipot test (EN 50395 / DIN VDE 0472-502) where every completed cable reel is immersed in a heated water bath for>= 2 hours. It is then subjected to2.5 kV AC(450/750 V),3.0 kV AC(0.6/1 kV), or6.0 kV AC(1.8/3 kV) for5 minuteswith zero breakdown. - Optical profile projector wall check is the cross-sectional dimensional audit (
IEC 60811-201 / -202) that measures minimum radial point thickness (tₘᵢₙ) and concentricity of the3GI3core insulation,GM1binner bedding, and5GM5outer sheath under20xdigital magnification.

Inside TEBAOFLEX's 4-Stage Factory Acceptance Test (FAT) Protocol
Every production drum of NSSHÖU, NSSHKCGEÖU, NSHXÖU, NSGAFÖU, and H07RN8-F must clear four laboratory gates before our quality department issues the serialized Drum Release Certificate:

- Gate A: Kelvin Bridge Conductor DC Resistance & Tinning Strip Check. We measure
20 °Ctemperature-corrected DC conductor resistance on100%of drums using a four-terminal Kelvin micro-ohmmeter (verifying compliance with IEC 60228 Class 5 ceilings, e.g., max. 0.565 Ohm/km on 35 mm² tinned copper). For example, we also strip100 mmof3GI3insulation to confirm bright, un-tarnished tin plating (ASTM B33 / IEC 60228). - Gate B: Optical Wall Thickness &
GM1b + 5GM5Dual-Extrusion Audit. A2 mmwafer from both drum ends is scanned on our digital profile projector. For instance, this verifies that minimum insulation thickness never falls below0.90 x nominal - 0.1 mmand that theGM1binner sheath fully fills all core interstices. - Gate C: Elastomer Hot-Set (
200 °C), Tear (VDE 0472-613), and Oil Soak (100 °C IRM 902). Dumbbell specimens cut from the actual drum sheath are tested for200 °CHot-Set (58.4%mean load elongation), trouser tear resistance (18.5 N/mmon5GM5), and168-hour100 °CIRM 902mineral oil tensile retention (91.2%on5GM5, TEBAOFLEX Lab, 2026). - Gate D: Water-Tank AC Hipot & Submersible Autoclave Cycling. Every drum passes a
5-minutesubmerged AC hipot test (3.0 kVforNSSHÖU,6.0 kVforNSGAFÖU,2.5 kVforH07RN8-F). Meanwhile,AD8submersible lots undergo10 barhydrostatic autoclave cycling and70 °Cgravimetric water-uptake checks (max. 6.4 mg/cm²).

View full-size oil-retention chart
Tensile Retention After 168h IRM 902 Oil Soak at 100°C (%). horizontal bar data: Natural Rubber (NR/SBR) 38.5; Standard PVC (TM2) 52; Standard PCP (EM2) 76.4; Halogen-Free (HM3) 84.5; Heavy-Duty PCP (5GM5) 91.2.Source: TEBAOFLEX Chemical Qualification Lab 2026.
Source: TEBAOFLEX Chemical Qualification Lab, 2026.
Copy-and-Paste 8-Point Engineering Purchase Order (PO) Checklist
Copy the 8-Point PO Specification Table below directly into your Request for Quotation (RFQ) or Purchase Order appendix when procuring heavy-duty or submersible rubber cables. Column 3 shows the actual verified test values from our 2026 production lots (measured via our testing method and test setup in the TEBAOFLEX ISO 9001 Laboratory).

PO Clause #.
1. Standard & Voltage Rating.
- Mandatory Technical Requirement to Write on Your PO.:
DIN VDE 0250-812(0.6/1 kVNSSHÖU),VDE 0250-602(1.8/3 kVNSGAFÖU), orEN 50525-2-21(AD8H07RN8-F). - TEBAOFLEX Verified 2026 Lot Result.: Full VDE / EN dimensional & voltage marking verified.
- Compliance Verdict.: PASS (
100% Drum Check).
2. Conductor & Tinning (IEC 60228).
- Mandatory Technical Requirement to Write on Your PO.: Class 5 finely stranded tinned copper (
NSSHÖU / NSGAFÖU) with20 °CKelvin bridge DC resistance report. - TEBAOFLEX Verified 2026 Lot Result.: 97.8% to 99.1% of max
R20limit; bright Sn coating. - Compliance Verdict.: PASS (
Zero Sulfide).
3. Dual-Layer Jacket (NSSHÖU).
- Mandatory Technical Requirement to Write on Your PO.: Extruded
GM1binner sheath +5GM5outer sheath (single-layer extrusion strictly rejected). - TEBAOFLEX Verified 2026 Lot Result.: Optical projector verified
GM1b+5GM5dual wall. - Compliance Verdict.: PASS (
24.6 kN Crush).
4. Hot-Set Crosslink (IEC 60811-507).
- Mandatory Technical Requirement to Write on Your PO.:
200 °C,20 N/cm²,15 minon3GI3&5GM5: load elongationmax. 100%, permanent setmax. 25%. - TEBAOFLEX Verified 2026 Lot Result.: 58.4% load elongation / 9.2% permanent set (
5GM5). - Compliance Verdict.: PASS (
Fully Cured CV).
5. Sheath Tear (DIN VDE 0472-613).
- Mandatory Technical Requirement to Write on Your PO.: Outer sheath trouser tear resistance
>= 15.0 N/mm(5GM5) or>= 10.0 N/mm(HM3). - TEBAOFLEX Verified 2026 Lot Result.: 18.5 N/mm (
5GM5 NSSHÖU) / 12.0 N/mm (HM3 NSHXÖU). - Compliance Verdict.: PASS (
+23% Margin).
6. Hot Oil Soak (IEC 60811-404).
- Mandatory Technical Requirement to Write on Your PO.:
IRM 902mineral oil at100 °C x 168 h: tensile & elongation retention>= 70%. - TEBAOFLEX Verified 2026 Lot Result.: 91.2% tensile kept / 88.6% elongation kept (
5GM5). - Compliance Verdict.: PASS (
Oil Proof).
7. AD8 Water Uptake (H07RN8-F).
- Mandatory Technical Requirement to Write on Your PO.:
IEC 60811-402gravimetric soak (70 °C x 14 d)max. 10.0 mg/cm²+10 barautoclaveR_isoreport. - TEBAOFLEX Verified 2026 Lot Result.: 6.4 mg/cm² (
H07RN8-F) / 5.2 mg/cm² (S1BC4N8-F). - Compliance Verdict.: PASS (
AD8 100m Rated).
8. Routine Water-Tank Hipot.
- Mandatory Technical Requirement to Write on Your PO.:
100%drum immersion AC dielectric test (5 min):2.5 kV(H07RN8-F),3.0 kV(NSSHÖU),6.0 kV(NSGAFÖU). - TEBAOFLEX Verified 2026 Lot Result.: Zero breakdown across 100% of dispatched drums.
- Compliance Verdict.: PASS (
Serialized Cert).
To review the complete structural, ampacity, and failure-analysis guides in this cluster, visit: * NSSHÖU, NSSHKCGEÖU & NSHXÖU Heavy-Duty Rubber Cable Guide * NSGAFÖU & NSGAFCMÖU 1.8/3 kV Short-Circuit-Proof Single-Core Cable Guide * NSSHÖU vs H07RN-F vs H07RN8-F Heavy-Duty Rubber Cables Compared * Preventing Oil Swelling, Ozone Cracking & Water Absorption in Rubber Cables
All lab tests follow IEC, DIN VDE, and ISO 9001 quality rules.
Key Takeaways & Frequently Asked Questions (FAQ)
Key Engineering Takeaways for Rubber Cable Procurement
- Never Accept a Rubber Cable Shipment Without an
IEC 60811-507Hot-Set Report. It is the only fast laboratory proof that the3GI3insulation and5GM5jacket were fully crosslinked on the CV steam line. - Require Dual-Layer Cross-Section Photos Before Dispatch on
NSSHÖUOrders. Confirming theGM1binner bedding +5GM5outer jacket prevents single-sheath substitutions. - Mandate Gravimetric Water-Uptake (
max. 10 mg/cm²) on AllH07RN8-F&S1BC4N8-FPOs. This guarantees trueAD8underwater longevity.
Frequently Asked Questions (FAQ)
Below are direct engineering answers grounded in DIN VDE and IEC test standards (2026).
How can a buyer verify that an NSSHÖU cable uses genuine 5GM5 polychloroprene instead of cheap SBR or thermoplastic rubber?
Require two laboratory test certificates on the Purchase Order: (1) the IEC 60811-507 Hot-Set test at 200 °C under 20 N/cm² load (a thermoplastic fake melts immediately, whereas genuine crosslinked 5GM5 elongates max. 60%), and (2) the DIN VDE 0472-613 tear-propagation test (>=15.0 N/mm minimum; TEBAOFLEX 2026 batches average 18.5 N/mm).
What routine AC voltage test is required before shipping NSSHÖU, NSGAFÖU, and H07RN8-F drums?
Every full production drum must pass a 5-minute AC water-tank dielectric withstand test: 2.5 kV AC for 450/750 V H07RN-F and H07RN8-F (EN 50525-2-21), 3.0 kV AC for 0.6/1 kV NSSHÖU and NSSHKCGEÖU (DIN VDE 0250-812), and 6.0 kV AC for 1.8/3 kV NSGAFÖU (DIN VDE 0250-602), plus 100% inline high-frequency spark testing.
Why must the PO explicitly specify Class 5 tinned copper for NSSHÖU and NSGAFÖU?
During high-temperature steam vulcanization, sulfur compounds in rubber react with bare copper to form brittle copper-sulfide scales that raise contact resistance at lugs. Specifying IEC 60228 Class 5 tinned copper prevents sulfur corrosion and ensures long-term solderability and crimp integrity in damp mines.
What FAT check confirms that NSSHKCGEÖU will trip a mine ground-fault relay reliably?
For screened NSSHKCGEÖU cables, the factory must verify both the volume resistivity of the extruded semiconductive rubber phase screen (under 500 Ohm.m per DIN VDE 0250-812) and the DC resistance balance of the concentric copper earth screen (K) and pilot monitoring core (ST).
Request a Sample FAT Dossier or a Custom Quote
Ready to source DIN VDE and EN 50525 rubber cables backed by complete pre-shipment laboratory evidence? Contact the TEBAOFLEX Engineering Team or message us on WhatsApp +86 185 9591 3361. We provide live video/photo FAT witnessing and batch-serialized certificates for NSSHÖU Heavy-Duty Rubber Cable, NSSHKCGEÖU Screened Mining Cable, NSGAFÖU 1.8/3 kV Cable, and H07RN8-F Submersible Rubber Cable.