0.6/1 kV 2PNCT-B 3×60 mm²: Shipyard Dry-Dock Portal Crane Reeling Cable Guide

Engineer JIS C 3327 0.6/1 kV 2PNCT-B 3×60 shipyard crane reeling cable: 8×OD level-wind drum, 90 °C EPR derating, 38.5 mm OD, and 6-point FAT. Watch 1:32.

JyenOperations & Technical EngineerDuration 1:32
Featured product
2PNCT / 3PNCT Rubber Cabtyre Cable
Category
Product video
Duration
1:32
Published
In this article23 sections
  1. 01What the video shows
  2. 021. Why Do Shipyard Dry-Dock Portal Cranes Fatigue Shielded Reeling Cables?
  3. Metallic Shield Fatigue vs. Unshielded Gusset-Filled Core Stability
  4. Salt-Mist, Dry-Dock Abrasion, and 90 °C EPR / 2nd-Kind CR Endurance
  5. 032. Cylindrical Level-Wind Drum Derating and 120 m Shipyard Crane Calculation
  6. Worked 120 m Shipyard Dry-Dock Portal Crane Feeder (440 V AC, 145 A, 60 Hz)
  7. Step 1: Compare 1-Layer vs. Multi-Layer Drum and 80 °C 600V 2PNCT at 40 °C
  8. Step 2: Check 120 m Voltage Drop, Resistive Heat, and 60 mm² Fault Survival
  9. Step 3: Check Active Quay Payout Mass and Tensile Margin
  10. 043. Inside the 5-Layer 2PNCT-B Unshielded Architecture and Shipyard Reeling Selection
  11. Adjacent 3-Core JIS C 3327 2PNCT & 2PNCT-B Reeling Reference Sizes
  12. Shipyard Portal Crane & Heavy Industrial Reeling Selection Matrix
  13. 054. How Should Shipyards Specify 8×OD Level-Wind Drums, Fairleads, and 6-Point FAT?
  14. Level-Wind Drum Barrel Sizing, 4-Roller Fairlead Alignment, and Strain Relief
  15. 6-Point Electrical and Mechanical Factory Acceptance Test (FAT) Protocol
  16. 06Frequently Asked Questions
  17. 1. What does the "-B" suffix mean on 0.6/1 kV 2PNCT-B 3×60 mm² reeling cable?
  18. 2. How much continuous current can 0.6/1 kV 2PNCT-B 3×60 mm² carry on a shipyard cable drum at 40 °C?
  19. 3. What minimum drum barrel diameter and bending radius are required for 2PNCT-B 3×60 mm²?
  20. 4. Why does 0.6/1 kV 2PNCT-B 3×60 mm² use Black, White, and Red cores without an integrated earth?
  21. 5. Which 6 factory acceptance tests should shipyard buyers audit on 2PNCT-B 3×60 mm² before shipment?
  22. 07References and Visual Credits
  23. Visual & Media Credits

What the video shows

92 s 1080p60 factory showcase of TEBAOFLEX 0.6/1 kV 2PNCT-B 3×60 mm² JIS C 3327:2000-based unshielded heavy-duty chloroprene reeling cable for shipyard dry-dock portal cranes, featuring water-spray vulcanization cooling, twin-belt haul-off, 36.2 m level-wind drum payout, 5-layer 3D strip-back, signed QC tag (2026.4.15), and 4K macro specimen QC.

The video illustrates a sample, process, or operating context. Final product construction, suitability, standards, and test acceptance criteria are confirmed against the ordered specification.

TL;DR: 0.6/1 kV 2PNCT-B 3×60 mm² Reeling Cable is a JIS C 3327:2000-based 0.6/1 kV unshielded heavy-duty chloroprene reeling cable built for shipyard dry-dock portal cranes. It pairs three Class 5 60 mm² bare copper cores (90 °C cross-linked EPR in Black/White/Red) with a central non-hygroscopic tensile filler, integral gusset-filled bedding, and a ~38.5 mm 2nd-Kind CR jacket rated for ≥ 8×OD (~308 mm) dynamic drum bending. At 40 °C dockside ambient, a single-layer level-wind drum delivers 157 A versus only 132 A on standard 80 °C 600 V 2PNCT 3×60 (18.8% higher capacity per JIS C 3327:2000 / JCS 0168-1:2016). Always audit all 6 electrical and jacket FAT records before drum dispatch.

Watch the complete 1:32 factory showcase video embedded on this 0.6/1 kV 2PNCT-B 3×60 mm² engineering page. It opens with a shipyard dry-dock portal luffing jib crane and 3-core trefoil 3D reveal (00:00), followed by water-spray vulcanization cooling and synchronized twin-belt caterpillar haul-off (00:10). Next, it animates a 36.2 m active level-wind drum payout cycle (00:20), strips back all 5 unshielded layers (00:32), verifies the 0.6/1kV 2PNCT-B Cable 3X60mm² Apr 2026 print and signed QC tag dated 2026.4.15 (00:52), and presents macro trefoil specimens (01:19). Our engineering audit applies JIS C 3327:2000, JIS C 3102, IEC 60228:2023, IEC 60502-1:2021, DIN VDE 0298-4:2023-06, IEC 60364-5-52:2009+AMD1:2024, and IEC 60949:1988+AMD1:2008 directly to this production lot.

Engineering Parameter0.6/1 kV 2PNCT-B 3×60 mm² Reeling Cable ValueGoverning Standard / Reference
Conductor System3×60 mm² Class 5 rope-lay annealed bare Cu (180 mm² Cu, 11.2 mm Ø)JIS C 3102 / IEC 60228:2023 Class 5
Core Insulation & Colors90 °C cross-linked EPR (-35 °C to +90 °C, 250 °C SC); Black (T), White (S), Red (R)JIS C 3327:2000 / TEBAOFLEX 0.6/1 kV Spec
Center & Bedding LockNon-hygroscopic center tensile filler + integral gusset-filled CR bedding (unshielded)Heavy-Duty Unshielded Reeling Spec
Outer Sheath & Nominal ODHeavy-duty matte black 2nd-Kind polychloroprene (CR); Ø ~38.5 mmJIS C 3327:2000 / JIS C 3005
Rated & Test Voltage0.6/1 kV AC nominal (1.2 kV max system); 3,500 V AC 5-min routine (3,000 V JIS min.)IEC 60502-1:2021 / JIS C 3327:2000
Dynamic Bend & Pull Limit≥ 8×OD (~308 mm radius, 616 mm min. barrel); 2,700 N Cu to 3,564 N tensile ratingDIN VDE 0298-3:2006-06 / TEBAOFLEX QC
Ampacity (3×60, 30 °C)~215 A free air; 204 A quay; 172 A (1L drum), 131 A (2L), 105 A (3L)JCS 0168-1:2016 / DIN VDE 0298-4:2023-06
Showcase Video Runtime1 minute 32 seconds (91.5 s, 1920x1080 60 fps, 7 technical chapters)TEBAOFLEX 2026 Factory Archive

1. Why Do Shipyard Dry-Dock Portal Cranes Fatigue Shielded Reeling Cables?

0.6/1 kV 2PNCT-B Reeling Cable is a JIS C 3327:2000-based 0.6/1 kV unshielded heavy-duty chloroprene power reeling cable engineered specifically for motorized cylindrical cable drums on rail-mounted coastal cranes. Along shipbuilding graving docks, rail-mounted portal luffing jib cranes travel continuously between concrete coping power boxes and dry-dock gates. Every long-travel pass subjects the trailing drum cable to simultaneous tensile pull, 4-roller fairlead deflection, seawater spray, and steel-shot blasting grit.

Coastal Japanese shipbuilding dockyard with rail-mounted portal luffing jib cranes and heavy dry-dock gantry structures operating along the seawall

Metallic Shield Fatigue vs. Unshielded Gusset-Filled Core Stability

Many shipyards mistakenly order braided copper-shielded control cables for main 0.6/1 kV crane travel drums when VFD emission rules do not require metallic screening. Under continuous drum payout and level-wind spooling across 4-roller fairleads (00:23 in our video), thin braided copper shield wires work-harden and snap first. Broken shield strands then poke inward through the bedding into the EPR insulation, causing intermittent ground-fault trips during rainy coastal shifts.

Integral Gusset-Filled Elastomeric Bedding is a pressure-molded black rubber inner bedding extruded deep into all three trefoil valleys so the insulated phases lock into a solid circular profile (TEBAOFLEX JIS-based heavy reeling architecture). Paired with a non-hygroscopic high-tenacity center tensile filler cord, this unshielded 2PNCT-B design eliminates metallic shield fracture completely while resisting oval crushing on cylindrical drums. Because the center filler absorbs reeling acceleration forces without wicking rainwater, the ~38.5 mm outer profile tracks cleanly across traversing level-wind guides.

Salt-Mist, Dry-Dock Abrasion, and 90 °C EPR / 2nd-Kind CR Endurance

Dry-dock coping walls combine abrasive concrete dust, welding sparks, marine hydraulic oil drips, and 40 °C summer deck heat. 90 °C Cross-Linked EPR Insulation is a thermoset ethylene-propylene rubber dielectric rated from -35 °C to +90 °C continuous conductor temperature and 250 °C short-circuit peaks without softening (JIS C 3327:2000 base extended to 90 °C EPR 0.6/1 kV reeling duty). Surrounding that core, 2nd-Kind Polychloroprene (CR) Sheath is a heavy-duty vulcanized chloroprene elastomer compounded and tested to JIS C 3005 for mineral oil immersion resistance, coastal UV ozone endurance, and flame retardancy. For chemical and environmental elastomer failure diagnostics, review our rubber cable sheath oil, ozone, and hydrolysis guide or browse our heavy-duty reeling cable catalog and material handling and port crane industry hub.

2. Cylindrical Level-Wind Drum Derating and 120 m Shipyard Crane Calculation

Selecting the right drum layer count matters more than nominal free-air ampacity on shipyard portal cranes. Stacking 0.6/1 kV 2PNCT-B 3×60 mm² onto three cylindrical drum layers drops continuous ampacity by 51% relative to free air under drum thermal derating rules (DIN VDE 0298-4:2023-06). Meanwhile, upgrading from standard 80 °C 600 V 2PNCT 3×60 (185 A base) to 90 °C 0.6/1 kV 2PNCT-B 3×60 (~215 A base) delivers 18.8% higher single-layer drum current at 40 °C quay ambient (JCS 0168-1:2016).

Drum Winding & Installation GeometryDerating Factor30 °C Ambient35 °C Ambient (0.96)40 °C Quay (0.91)50 °C Hot Deck (0.82)Shipyard Portal Crane Assessment
Free Air (Single Suspended Span)1.00215 A206 A196 A176 AReference rating only; never valid for wound drums
Uncoiled Flat Along Quay Rail0.95204 A196 A186 A167 AApplies only to fully payed-out quay segment
1-Layer Level-Wind Cylindrical Drum0.80172 A165 A157 A141 ATarget geometry for 145 A shipyard travel drives
2-Layer Cylindrical Drum (Wound)0.61131 A126 A119 A107 AFails 145 A continuous crane load at 40 °C
3-Layer Cylindrical Drum (Wound)0.49105 A101 A96 A86 ASevere inner-turn heating; forces wider barrel

Base 30 °C free-air ampacity (~215 A) reflects 90 °C EPR 0.6/1 kV 2PNCT-B 3×60 mm² documented in our showcase video (01:15); cylindrical drum layer and ambient factors sqrt[(90 - T_amb) / 60] follow DIN VDE 0298-4:2023-06 and JCS 0168-1:2016.

Worked 120 m Shipyard Dry-Dock Portal Crane Feeder (440 V AC, 145 A, 60 Hz)

For example, evaluate a rail-mounted shipyard dry-dock portal luffing crane operating at 440 V 3-phase 60 Hz and 145 A RMS continuous (93.9 kW active power at cos phi = 0.85, sin phi = 0.527). The crane draws main travel and slewing power through 120 m of TEBAOFLEX 0.6/1 kV 2PNCT-B 3×60 mm² routed from a stainless dockside power box onto a wide 1-layer level-wind cylindrical drum at 40 °C summer quay ambient. Calculations use conservative JIS C 3327 multicore 60 mm² resistance (R_20 = 0.339 Ω/km; bare copper target 0.324 Ω/km) and trefoil X_60 = 0.095 Ω/km.

Step 1: Compare 1-Layer vs. Multi-Layer Drum and 80 °C 600V 2PNCT at 40 °C

Verify thermal drum margin at 40 °C (f_t90 = 0.91 for 90 °C EPR vs. f_t80 = 0.89 for 80 °C standard 600 V 2PNCT 3×60 at 185 A free air per DIN VDE 0298-4:2023-06).

90 C 2PNCT-B 3x60 (1-layer drum, 40 C): I_z,1L   = 172 A * 0.91 = 156.5 A (>= 145 A PASS)
90 C 2PNCT-B 3x60 (2-layer drum, 40 C): I_z,2L   = 131 A * 0.91 = 119.2 A (< 145 A FAIL)
90 C 2PNCT-B 3x60 (3-layer drum, 40 C): I_z,3L   = 105 A * 0.91 =  95.6 A (< 145 A SEVERE OVERHEAT)
80 C 600V 2PNCT 3x60 (1-layer, 40 C):   I_z,80C  = 148 A * 0.89 = 131.7 A (< 145 A FAIL)

Only the 90 °C 0.6/1 kV 2PNCT-B 3×60 mm² wound in a single precision level-wind layer passes 145 A at 40 °C (156.5 A ≥ 145 A PASS). Standard 80 °C 600 V 2PNCT (131.7 A) or a compact 2-layer drum (119.2 A) would overheat, forcing a heavier 100 mm² conductor jump.

Step 2: Check 120 m Voltage Drop, Resistive Heat, and 60 mm² Fault Survival

Next, scale the conservative 20 °C multicore resistance (0.339 Ω/km) to 90 °C (alpha_20 = 0.00393 /°C), apply a 1.008 60 Hz AC multiplier, and check both voltage drop and adiabatic short-circuit survival (k = 143 A·s^0.5/mm² per IEC 60949:1988+AMD1:2008).

R_90,dc = 0.339 * [1 + 0.00393 * (90 - 20)] = 0.4323 Ohm/km  (bare Cu 0.324 -> 0.4131 Ohm/km)
R_90,ac = 0.4323 * 1.008 = 0.4357 Ohm/km
dV      = sqrt(3) * 145 A * 0.120 km * (0.4357 * 0.85 + 0.095 * 0.527)
        = 30.138 * (0.3703 + 0.0501) = 12.67 V  (2.88% of 440 V PASS; bare Cu 2.77%)
P_loss  = 3 * (145 A)^2 * 0.4357 Ohm/km * 0.120 km = 3,298 W total (27.5 W/m)
Short-circuit (60 mm2 phase, k=143): I_sc = 143 * 60 / sqrt(1.0) = 8.58 kA (1.0 s) / 12.13 kA (0.5 s)

Line voltage drop stays at 2.88% of 440 V (2.77% for bare copper target), safely inside the 3% to 5% industrial motor feeder band (IEC 60364-5-52:2009+AMD1:2024). Each 60 mm² phase survives 12.13 kA over 0.5 s without EPR thermal damage.

Step 3: Check Active Quay Payout Mass and Tensile Margin

Finally, verify trailing tensile pull across the 36.2 m active quayside span animated at 00:27 in our showcase video (~3.05 kg/m gusseted cable mass vs. 2.96 kg/m catalog baseline).

Active 36.2 m payout mass:           M_span  = 36.2 m * 3.05 kg/m = 110.4 kg (~1,083 N dead weight)
Copper tensile baseline (15 N/mm2):  F_base  = 180 mm2 * 15 N/mm2 = 2,700 N
Catalog pull limit (center filler):  F_max   = 3,564 N  -> > 3x SAFETY MARGIN vs. 1,083 N span load

With over 3x tensile reserve against active span weight and smooth traversing roller alignment, the drum torque motor maintains stable catenary tension without stretching the copper conductors.

3. Inside the 5-Layer 2PNCT-B Unshielded Architecture and Shipyard Reeling Selection

Chapters 04 and 06 of our video (00:32 to 01:18) peel back all five structural layers of TEBAOFLEX 0.6/1 kV 2PNCT-B 3×60 mm² and display the symmetrical 2D trefoil section (T Black, S White, R Red, Ø ~38.5 mm).

Five-layer 0.6/1 kV 2PNCT-B 3×60 mm² unshielded reeling cable 3D cutaway showing Class 5 flexible bare copper conductors, non-hygroscopic center tensile filler cord, 90 °C EPR insulation in JIS Black/White/Red, integral gusset-filled elastomeric bedding matrix, and heavy-duty 2nd-Kind CR outer sheath
  1. Layer 01, Flexible Stranded Bare Copper Conductors (3×60 mm²): Three symmetrical Class 5 rope-lay annealed bare copper conductors (180 mm² total copper per JIS C 3102 / IEC 60228:2023 Class 5) deliver ~215 A open-air current capacity with high cyclic flex endurance.
  2. Layer 02, High-Tenacity Non-Hygroscopic Center Tensile Filler Cord: Positioned precisely inside the central trefoil valley, this moisture-blocking cord stabilizes core lay geometry and absorbs axial reeling acceleration pulls.
  3. Layer 03, 90 °C Cross-Linked EPR Insulation (Black · White · Red): Thermoset ethylene-propylene rubber operates continuously from -35 °C to +90 °C (250 °C short-circuit) using unmistakable JIS C 3327 3-core phase colors: Black (T), White (S), and Red (R).
  4. Layer 04, Integral Gusset-Filled Elastomeric Bedding Matrix: Pressure-molded black rubber penetrates every interstice between the three insulated phases, locking circularity on cylindrical drums without brittle metallic shielding.
  5. Layer 05, Heavy-Duty 2nd-Kind Polychloroprene (CR) Outer Sheath (Ø ~38.5 mm): Matte black marine CR rubber resists salt mist, hydraulic oil, ozone, UV, and quay concrete wear. Crisp white dot-matrix marking (0.6/1kV 2PNCT-B Cable 3X60mm² Apr 2026, verified at 00:58) ensures full drum traceability.
4K production specimen gallery of TEBAOFLEX 0.6/1 kV 2PNCT-B 3×60 mm² reeling cable showing flush-cut macro 3-core trefoil in Black/White/Red, upright circular CR jacket roundness, and full white dot-matrix specification legend

Adjacent 3-Core JIS C 3327 2PNCT & 2PNCT-B Reeling Reference Sizes

When engineering shipyard cranes under our JIS standard cables hub and PNCT / 2PNCT / 3PNCT rubber cabtyre catalog, engineers benchmark 3×38 to 3×100 mm² sizes to verify drum flange capacity and torque motor pull.

Cable ConfigurationStranding & Conductor ØNominal OD (mm)Min. Drum Bend (8×OD)Pull Limit (N)30 °C Air / 1-Layer Drum
2PNCT 3×38 (600 V, 80 °C)7/34/0.45 mm (8.7 mm)30.0240 mm2,257 N140 A / 112 A
2PNCT 3×60 (600 V, 80 °C)19/20/0.45 mm (11.2 mm)38.0304 mm3,564 N185 A / 148 A
2PNCT-B 3×60 (0.6/1 kV, 90 °C)3×60 mm² Class 5 Cu~38.5~308 mm2,700 to 3,564 N~215 A / 172 A
2PNCT 3×100 (600 V, 80 °C)19/34/0.45 mm (14.6 mm)49.0392 mm5,940 N255 A / 204 A

Standard 600 V 80 °C 3×38, 3×60, and 3×100 figures reflect JIS C 3327:2000 reference dimensions (TEBAOFLEX online cabtyre tables list standard sizes through 2PNCT 4×22 and 3PNCT 4×38, with larger shipyard sizes built to order); 0.6/1 kV 2PNCT-B 3×60 reflects the upgraded 90 °C EPR gusset-filled unshielded reeling sample filmed in this showcase.

Shipyard Portal Crane & Heavy Industrial Reeling Selection Matrix

Unshielded 0.6/1 kV 2PNCT-B 3×60 suits shipyard cylindrical drums running clean three-phase power, whereas screened control drums, high-speed monospiral STS reels, extreme vertical lifts, or mining faces require purpose-built TEBAOFLEX families. Match your duty boundary below (see also our 2PNCT vs. 3PNCT JIS C 3327 guide and reeling cable selection guide).

TEBAOFLEX Cable FamilyVoltage & Screen TypeGoverning StandardPrimary Crane BoundaryWhen to Choose Over Unshielded 2PNCT-B
PNCT / 2PNCT / 3PNCT Cabtyre600 V standard (0.6/1 kV custom 2PNCT-B), unshieldedJIS C 3327:2000Shipyard portal cranes & cylindrical drums (see PNCT crane video)Baseline choice for JIS unshielded cylindrical drum reeling
NSHTÖU Reeling Cable & RXG / RXG-D PCP0.6/1 kV, TÖ anti-torsion braidDIN VDE 0250-814:1985-02, 5GM3 PCP (5GM5 on FO)High-speed > 120 m/min monospiral STS reels (see NSHTÖU-FO 12FO video)Required for high-speed monospiral reels needing embedded TÖ mesh
NSHTÖU-V Aramid High-Tensile0.6/1 kV, synthetic aramid braid + marine PURDIN VDE 0250-814:1985-02 (6×OD, -40 to +90 °C)Steep vertical hoist drums and long-span crawler reelsChoose when axial lift pull or severe abrasion demands aramid/PUR reinforcement
Screened 2PNCT-BS Control0.6/1 kV, braided EMC screenJIS C 3327:2000-based screened specDam gantry PLC & telemetry reeling (see 2PNCT-BS 6Px2 video)Choose only for low-current control/signal circuits needing EMI shielding
NSSHÖU-J Trailing Cable0.6/1 kV, heavy 5GM5 yellowDIN VDE 0250-812:1985-05Ground-dragged tunneling & mine faces (see NSSHÖU-J 3×150 video)Choose for abrasive floor-dragged mining service instead of portal drums

4. How Should Shipyards Specify 8×OD Level-Wind Drums, Fairleads, and 6-Point FAT?

Most shipyard reeling failures start at the yellow 4-roller fairlead or the stainless dockside junction box (00:01 and 00:23 in our video), not along the open concrete quay. Tight drum barrels crush the gusset bedding while misaligned guide rollers abrade one side of the 2nd-Kind CR jacket flat.

Concrete graving dry dock bordered by rail-mounted shipyard portal cranes and coping wall crane tracks exposed to coastal water and abrasion

Level-Wind Drum Barrel Sizing, 4-Roller Fairlead Alignment, and Strain Relief

4-Roller Level-Wind Fairlead is a traversing rectangular steel roller carriage synchronized to the motorized drum shaft so the reeling cable spools side-by-side in neat parallel turns without overlapping (DIN VDE 0298-3:2006-06). Enforce these four mechanical rules on every ~38.5 mm OD 0.6/1 kV 2PNCT-B 3×60 mm² installation:

  • Minimum Dynamic Bending Radius (≥ 8×OD = ~308 mm): Size every motorized drum inner barrel and guide roller arc to at least a 308 mm bending radius (616 mm minimum drum barrel diameter). For example, a 1,000 mm shipyard cylindrical drum barrel yields a 500 mm core radius (13.0×OD), giving generous copper flex life, whereas retrofitting onto a 500 mm barrel (250 mm radius = 6.5×OD) violates the 8×OD limit and fatigues 60 mm² strands rapidly.
  • Fixed Entry Sweep (≥ 6×OD = 231 mm): Inside the stationary 0.6/1 kV stainless dockside power box and crane slewing slip-ring cabinet, keep clamped stationary bends at ≥ 231 mm radius.
  • Level-Wind Fleet Angle (≤ 2°) and Torque Limiter: Keep the traversing 4-roller carriage centered directly over the cable quay slot and cap torque-motor pull below 2,700 N (15 N/mm² copper baseline) during crane start-stop ramps.
  • Bell-Mouth Relief & Separate Quay Earth Discipline: Anchor the cable cleanly through a marine bell-mouth strain grip at the dockside box (00:01). Because 2PNCT-B 3×60 mm² is a pure 3-phase power cable (Bk/W/R), verify that the crane portal chassis bonds to the shipyard rail ground grid or dedicated earth conductor per local marine electrical code.

6-Point Electrical and Mechanical Factory Acceptance Test (FAT) Protocol

Every finished export reel filmed during water-spray vulcanization (00:12) and twin-belt haul-off (00:16) undergoes complete pre-shipment verification at TEBAOFLEX Manufacturing under our documented Quality and Certifications program alongside our marine and offshore cable portfolio. Audit all six verifiable FAT records before shipping:

FAT CheckpointTest Method & Acceptance CriterionGoverning StandardInspection Scope
1. Outer Diameter & ConcentricityVerify nominal ~38.5 mm OD (± 1.5 mm), smooth matte finish, and flush trefoil wall uniformity across cut endsJIS C 3327:2000 / TEBAOFLEX 0.6/1 kV SpecEvery production drum
2. 20 °C Conductor DC ResistanceVerify 60 mm² flexible bare copper resistance ≤ 0.339 Ω/km multicore limit (≤ 0.324 Ω/km bare target)JIS C 3102 / IEC 60228:2023 Class 5Every production drum
3. Routine AC Voltage WithstandCompleted cable withstands 3,500 V AC (50/60 Hz) for 5 minutes (0.6/1 kV class; exceeds 3,000 V 1-min JIS base) + spark testIEC 60502-1:2021 / JIS C 3327:2000100% of finished drums
4. 20 °C Insulation ResistanceConfirm 90 °C EPR core insulation resistance ≥ 200 MΩ·km at 20 °C on Black, White, and Red phasesJIS C 3327:2000 / JIS C 3005Every production drum
5. Gusset Bedding & Filler CheckInspect flush-cut macro end-face confirming deep gusset valley filling, centered non-hygroscopic filler, and zero voidsTEBAOFLEX 4K QC / JIS C 3327:2000Every production lot
6. 2nd-Kind CR Oil, Tear & FlameAudit hot mineral oil immersion retention, tensile/elongation retention, and flame self-extinction test certificatesJIS C 3327:2000 / JIS C 3005Per CR compound batch

Engineering Inquiries: Need custom-length 0.6/1 kV 2PNCT-B 3×60 mm² unshielded reeling cables with stainless pulling socks, drum-matched cut lengths, and a full 6-point FAT dossier? Contact our engineering desk, email info@tebaoflex.com, or message WhatsApp +86 185 9591 3361 with your drum barrel diameter, active travel span, and motor amps.

Editorial Note: Authored by Jyen (Technical Editor for JIS C 3327 and shipyard portal crane reeling cables at Jiangsu Tebaoflex Special Cable Co., Ltd.). Standard editions and FAT thresholds were verified against JIS C 3327:2000, JIS C 3102, JIS C 3005, JCS 0168-1:2016, IEC 60502-1:2021, and DIN VDE 0298-4:2023-06.

Frequently Asked Questions

1. What does the "-B" suffix mean on 0.6/1 kV 2PNCT-B 3×60 mm² reeling cable?

In JIS-based heavy reeling specifications extending JIS C 3327:2000, 2PNCT-B denotes an unshielded heavy-duty reeling upgrade rated to 0.6/1 kV AC with 90 °C cross-linked EPR insulation, a non-hygroscopic central tensile filler, and integral gusset-filled 2nd-Kind chloroprene (CR) bedding. Unlike screened 2PNCT-BS control cables, 2PNCT-B omits brittle copper braid shields so high-current crane drums run without shield-wire fatigue.

2. How much continuous current can 0.6/1 kV 2PNCT-B 3×60 mm² carry on a shipyard cable drum at 40 °C?

Under DIN VDE 0298-4:2023-06 and JCS 0168-1:2016, 90 °C 2PNCT-B 3×60 mm² (~215 A free air at 30 °C) carries 157 A (156.5 A) on a 1-layer level-wind drum at 40 °C (0.80 layer × 0.91 ambient). Winding onto a 2-layer cylindrical drum drops capacity to 119 A, and 3 layers drop it to 96 A. Standard 80 °C 600 V 2PNCT 3×60 carries only 132 A on a 1-layer drum at 40 °C.

3. What minimum drum barrel diameter and bending radius are required for 2PNCT-B 3×60 mm²?

For the ~38.5 mm nominal outer diameter verified in our factory showcase, enforce at least an 8×OD minimum dynamic bending radius (~308 mm radius, corresponding to a 616 mm minimum drum barrel diameter) across motorized reels and 4-roller fairleads (DIN VDE 0298-3:2006-06). Keep stationary clamped sweeps inside the dockside junction box at ≥ 6×OD (231 mm).

4. Why does 0.6/1 kV 2PNCT-B 3×60 mm² use Black, White, and Red cores without an integrated earth?

Three-core 2PNCT-B 3×60 mm² follows the JIS C 3327 3-phase trefoil color code (Black T, White S, Red R) to deliver compact ~38.5 mm circular symmetry for dedicated three-phase crane power circuits where portal grounding bonds through the steel crane rail system or a separate earth path. When an integrated protective earth is mandatory inside one jacket, specify a 4-core 3C+E or split-earth NSHTÖU build instead.

5. Which 6 factory acceptance tests should shipyard buyers audit on 2PNCT-B 3×60 mm² before shipment?

Buyers should audit all six JIS C 3327:2000 / IEC 60502-1:2021 FAT records before releasing drums. First, verify nominal ~38.5 mm OD and roundness. Second, check 20 °C DC resistance (≤ 0.339 Ω/km multicore ceiling). Third, confirm 3,500 V AC 5-minute withstand (0.6/1 kV routine) and inline spark tests. Fourth, check ≥ 200 MΩ·km insulation resistance at 20 °C. Fifth and sixth, audit flush-cut gusset bedding concentricity plus JIS C 3005 oil-immersion, tensile, and flame test reports (JIS C 3005).

References and Visual Credits

  • JIS C 3327:2000, JIS C 3102 & JIS C 3005: 600 V Rubber Insulated Flexible Cabtyre Cables (2PNCT baseline), Annealed Copper Wires for Electrical Purposes, and Test Methods for Rubber Insulated Cables, Japanese Standards Association (JSA).
  • JCS 0168-1:2016, DIN VDE 0298-3:2006-06 & DIN VDE 0298-4:2023-06: Permissible Current-Carrying Capacities, Dynamic Drum Bending Radii, and Wound-Drum Ampacity Derating Factors, VDE Verlag — DIN VDE 0298-4:2023-06.
  • IEC 60228:2023: Conductors of Insulated Cables (Class 5 Flexible Copper Resistance Baseline), IEC Webstore — IEC 60228:2023.
  • IEC 60502-1:2021 & IEC 60364-5-52:2009+AMD1:2024: 0.6/1 kV Extruded Power Cable Routine 3.5 kV 5-Minute Voltage Test and Low-Voltage Motor Feeder Voltage Drop Limits, IEC Webstore — IEC 60502-1:2021.
  • IEC 60949:1988+AMD1:2008: Calculation of Thermally Permissible Short-Circuit Currents (k = 143 for 90 °C to 250 °C EPR Copper), IEC Webstore — IEC 60949.
  • DIN VDE 0250-814:1985-02 & DIN VDE 0250-812:1985-05: Reference Construction Boundaries for Anti-Torsion NSHTÖU Reeling and NSSHÖU Trailing Cables, VDE.

Visual & Media Credits

  • Cover photo (hero.webp): Netaman Shipyard Crane at Floating Dry Dock Lahesuu sadam Tallinn 21 September 2016.jpg by Pjotr Mahhonin, licensed under CC BY-SA 4.0 via Wikimedia Commons.
  • Section 1 shipyard dry-dock photo (2pnct-b-shipyard-drydock-portal-crane.webp): Koyo Dockyard, -6 Jun. 2012 a.jpg by 中古侍, licensed under CC BY 2.1 jp via Wikimedia Commons.
  • Section 4 graving dry-dock crane tracks photo (2pnct-b-drydock-crane-tracks.webp): Dry Dock 1.JPG by Marcbela (Marc N. Belanger), Public domain (PDM 1.0) via Wikimedia Commons.
  • Section 3 5-layer 3D cutaway and 4K specimen frames (2pnct-b-5-layer-unshielded-architecture.webp, 2pnct-b-specimen-qc-gallery.webp): TEBAOFLEX in-house factory production archive (0.6/1kV 2PNCT-B Cable 3X60mm² Apr 2026).

Specify it

Sizes, technical data and documents for each cable.

PNCT / 2PNCT / 3PNCT — horizontal cutaway

Rubber Cable

PNCT / 2PNCT / 3PNCT

2PNCT and 3PNCT are Japanese rubber cabtyre cable grades for portable machinery and industrial equipment. The family combines flexible copper conductors, EP/EPR insulation and a chloroprene rubber sheath. Common reference constructions are rated 600 V and 80°C maximum conductor temperature.

Rated voltage
600 V
Standard
IEC
Sizes and data →