Project case · Pavlodar, Kazakhstan

Kazakhstan 6/10 kV (N)TSCGEWCUEUS Submersible Pump Case

Engineering case study: 180 m 6/10 kV (N)TSCGEWCUEUS S3×50+2×25/2+S(4×0.5) submersible pump cable for Kazakhstan river port (≤ 54 mm OD, 17 kV FAT).

JyenOperations & Technical Engineer4 images
Industrial river port floating dock and crane infrastructure for 6/10 kV submersible pump duty
Location
Pavlodar, Kazakhstan
Application
River port and industrial 6 kV VFD submersible pump replacement (-40 °C to +90 °C)
Evidence
4 images
In this case21 sections
  1. 011. Kazakhstan River Port 6/10 kV Submersible Pump Scope and 54 mm Gland Limit
  2. Reconciling OEM Replacement Naming and the 54 mm Gland Ceiling
  3. Worked Bend Radius, Cable Mass, and Drum Shipping Check
  4. 022. How Does a 180 m 6 kV VFD Pump Cable Handle du/dt Surges and 8.37 kA Faults?
  5. Controlling VFD Common-Mode Noise and Protecting Internal Control Pairs
  6. Worked 6 kV VFD Wave Impedance, Charging Current, and Voltage Drop Check
  7. 033. 9-Layer Construction of TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV Pump Cable
  8. Layer-by-Layer Engineering Specification (Rev3 Baseline)
  9. 044. Pre-Shipment 17 kV FAT Protocol, Drum Logistics, and MV Pump Cable Selection
  10. Worked MV Dielectric, Partial Discharge, and Fault-Energy Verification
  11. Realistic Workshop Water-Immersion Testing vs. Paper Promises
  12. Comparing TEBAOFLEX Medium-Voltage Submersible Pump and Reeling Series
  13. 055. Submersible Pump Commissioning Rules and Six-Point MV Replacement RFQ Checklist
  14. Six-Point Pre-Order RFQ Checklist for 6/10 kV Submersible Pump Replacement Cables
  15. 06Frequently Asked Questions
  16. Can a 6/10 kV (N)TSCGEWCUEUS 3×50+2×25/2+S(4×0.5) cable fit inside a 54 mm pump entry grommet?
  17. Is TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV suitable for a 180 m 6,000 V VFD pump feeder with a du/dt filter?
  18. How is the S(4×0.5) control group shielded against 6 kV VFD noise inside the same cable?
  19. What is the earth-fault current rating of the 2×12.5 mm² split earth cores plus overall copper braid?
  20. Which pre-shipment FAT tests should buyers lock before balance payment on a 6/10 kV submersible pump drum?
  21. Why must a 180 m submerged 6/10 kV pump replacement cable be delivered on one drum with zero joints?

Case at a glance

Location
Pavlodar, Kazakhstan
Application
River port and industrial 6 kV VFD submersible pump replacement (-40 °C to +90 °C)
Cable type
(N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm² MV Submersible Pump Cable →
Evidence
4 images
TL;DR: Medium-voltage submersible pump cable powers heavy pumps underwater while blocking water, VFD switching noise, and earth faults. For a river port project in Pavlodar, Kazakhstan, TEBAOFLEX built a 180 m joint-free spec for TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm² (Um 12 kV, -40 °C to +90 °C). The cable caps outer diameter at ≤ 54 mm for the original pump gland. It delivers 0.345 μF/km and 0.371 mH/km for 6,000 V VFD duty, rates 8.37 kA / 1 s earth fault, and sets 17 kV AC / 5 min plus ≤ 10 pC PD FAT gates.
  • Project Location & Duty: Pavlodar River Port & industrial water-handling sites, Kazakhstan · 6 kV submersible pump replacement
  • Cable Designation: TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm² (single-drum, 0 joints)
  • Single-Drum Length: 180 m continuous uncut length on one steel-wood drum (1.2×1.1×1.2 m, ~1,026 kg gross)
  • Power & Earth Cores: 3×50 mm² Class 5 tinned Cu (EPR + dual semicon screens) + 2×12.5 mm² (25 mm² total PE)
  • Control & EMC Screen: S(4×0.5 mm²) two twisted pairs (≥ 80% CuSn screen) + overall CuSn braid (≥ 80%, 84% typical)
  • Inner & Outer Sheath: Water-blocking GM1b inner sheath + red oil- and UV-resistant 5GM5 PCP outer sheath
  • Outer Diameter & Bend: Nominal 54 to 58 mm (Rev3 table); tight-tolerance ≤ 54 mm build committed (6×OD = 324 mm)
  • Electrical & Thermal Data: U0/U = 6/10 kV (Um 12 kV); 0.393 Ω/km; 200 A air ref; C = 0.345 μF/km; L = 0.371 mH/km; -40 to +90 °C
  • Pre-Shipment FAT Gates: 17 kV AC / 5 min; PD ≤ 10 pC at 1.73 U0; 8.37 kA / 1 s fault rating; 1.5 to 2.0 kV control test; CE

1. Kazakhstan River Port 6/10 kV Submersible Pump Scope and 54 mm Gland Limit

River port pump stations across northern Kazakhstan run high-head 6,000 V submersible pumps inside deep concrete wells. Winter air drops to -40 °C, while river silt, vibration, and wet-dry cycles age old European pump cables.

Submersible pump entry grommet tolerance is the hard outer diameter cap a replacement cable must meet. It lets the cable seal watertight inside an existing cast-iron pump housing without new gland machining.

Single-drum joint-free delivery is a strict quality rule requiring the full cable run (180 m) in one uncut length. No factory splices or vulcanized repair patches are allowed.

River water intake pumping station tower standing in open river water with steel pedestrian bridge access

Reconciling OEM Replacement Naming and the 54 mm Gland Ceiling

Replacing an aging 6/10 kV submersible pump cable demands clear naming and tight size control before production starts. First, both teams locked transparent brand wording. The paperwork states clearly that this is a TEBAOFLEX replacement cable built for heavy European 6 kV submersible pumps, not an original pump-brand part.

Second, standard Rev3 tables for 3×50 + 2×25/2 + S(4×0.5) mm² list a 54 to 58 mm outer diameter range. Because the existing pump gland capped bore clearance at 54 mm, any oversize sheath from 55 to 58 mm would force costly site rework. TEBAOFLEX engineers committed to a tight ≤ 54 mm build. Full 6/10 kV EPR wall thickness, GM1b inner sheath, and 5GM5 PCP outer sheath strength remain intact.

Worked Bend Radius, Cable Mass, and Drum Shipping Check

Checking pit clearance and drum mass early stops crane and gland surprises on site. Evaluate the 180 m uncut TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV build. Its Rev3 specs are 5,094.0 kg/km mass, 2,073.2 kg/km copper, and 6×OD bend:

1. Flexible minimum bend radius inside concrete pump wet well (6 x OD rule):
   Standard 58 mm max OD build  -> R_min = 6 * 58 mm = 348 mm (Rev3 baseline)
   Tight <= 54 mm grommet build -> R_min = 6 * 54 mm = 324 mm (saves 24 mm bend clearance)

2. Uncut 180 m net cable weight and copper mass:
   Net cable mass  = 180 m * 5.094 kg/m  = 916.9 kg (0.917 t)
   Net copper mass = 180 m * 2.0732 kg/m = 373.2 kg (includes overall CuSn braid)

3. Export drum packing check (1.2 m x 1.1 m x 1.2 m steel-reinforced wooden drum):
   Gross shipping mass ~ 1,026 kg (drum tare ~ 109 kg), volume ~ 1.58 m3 (~1.6 m3 LCL).

Compare deep-submersion sizing rules in our deep-well submersible pump cable hydrostatic depth derating guide and our submersible pump cable AD7 and AD8 immersion testing guide.

2. How Does a 180 m 6 kV VFD Pump Cable Handle du/dt Surges and 8.37 kA Faults?

Feeding a 6,000 V wet pump motor from a medium-voltage VFD over 180 m adds fast pulse stress. Even with a du/dt filter at the drive, engineers must verify exact capacitance, inductance, surge impedance, and screen fault limits first.

Characteristic cable surge impedance (Z_0) is the wave ratio sqrt(L / C) set by cable inductance and capacitance. It governs how strongly VFD pulses reflect at motor windings.

Split-earth EMC screening is a balanced fault layout pairing two 12.5 mm² tinned-copper earth cores (25 mm² total) with a dense overall copper braid (≥ 80%, 84% typical).

Medium-voltage distribution substation showing step-down transformer, overhead switchgear busbars, and insulated MV feeder cables

Controlling VFD Common-Mode Noise and Protecting Internal Control Pairs

Inside one 54 mm sheath, three 6,000 V VFD phases run millimeters from four 0.5 mm² thermal and leak sensor wires. Without dual shielding aligned to IEC 61800-3:2022 drive EMC rules, steep drive pulses couple noise into the control loop and trip the pump.

TEBAOFLEX isolates both circuits in two stages. First, the four 0.5 mm² wires form two twisted pairs under a dedicated ≥ 80% tinned-copper screen (1.5 to 2.0 kV AC test). Second, the full core bundle sits under a GM1b rubber inner sheath and a ≥ 80% (84% typical) overall copper braid. Paired with the two 12.5 mm² earth cores, that screen path handles 8.37 kA for one second across a 60 °C to 250 °C rise.

Worked 6 kV VFD Wave Impedance, Charging Current, and Voltage Drop Check

Drive engineers size output du/dt filters directly from per-kilometer R, L, and C data. Compute the 180 m (0.180 km) Kazakhstan feeder response from TEBAOFLEX Rev3 constants. The rated values are C = 0.345 μF/km, L = 0.371 mH/km, and R_20 = 0.393 Ω/km:

1. Total 180 m lumped capacitance and inductance per phase:
   C_180 = 0.180 km * 0.345 uF/km = 0.0621 uF (62.1 nF)
   L_180 = 0.180 km * 0.371 mH/km = 0.0668 mH (66.8 uH)

2. Surge impedance and one-way wave travel time (for du/dt filter check):
   Z_0 = sqrt(0.371e-3 H/km / 0.345e-6 F/km) = 32.8 Ohm
   tau = 0.180 km * sqrt(0.371e-3 * 0.345e-6) = 2.04 us (round-trip 2*tau = 4.07 us)
   -> A du/dt filter slowing pulse rise time well beyond 4.07 us prevents full 2x wave doubling.

3. 50 Hz capacitive charging current at 6,000 V line-to-line (phase voltage U_ph = 3,464 V):
   I_c = 2 * pi * 50 Hz * 62.1e-9 F * 3,464 V = 0.068 A/phase (minimal filter reactive load)

4. Full-load voltage drop check at 100 A (90 C hot resistance R_90 = 0.393 * 1.275 = 0.501 Ohm/km):
   R_180,90C = 0.180 km * 0.501 Ohm/km = 0.0902 Ohm
   dV_LL = 1.732 * 100 A * 0.0902 Ohm = 15.6 V (0.26% of 6,000 V; ampacity ref 200 A at 30 C air)

For thermal grouping and submerged ampacity correction, apply DIN VDE 0298-4:2023-06. Review related MV VFD pump specs in our MV submersible pump VFD grommet and PD test guide and our 6.6 kV trailing cable insulation grade guide.

3. 9-Layer Construction of TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV Pump Cable

The official Rev3 cross-section below maps all nine engineered layers of TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm². Every layer works together to control radial electric stress, block water ingress, and resist pit abrasion down to -40 °C.

TEBAOFLEX Rev3 nine-layer cross-section diagram of (N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm² medium-voltage submersible pump cable showing three EPR-insulated phase cores, dual semicon screens, two split earth cores, screened four-core control group, GM1b inner sheath, overall tinned copper braid, and red 5GM5 PCP outer sheath

Triple-extruded semiconductive field control is the void-free bonding of an inner conductor screen, clean EPR insulation, and an outer screen. It stops partial-discharge treeing under 6/10 kV AC stress.

Layer-by-Layer Engineering Specification (Rev3 Baseline)

  • Layer 1 — Phase Conductors (3×50 mm²): Finely bunched flexible tinned annealed copper per IEC 60228:2023 Class 5 (≤ 0.393 Ω/km at 20 °C) — Primary Field Function: Resists fresh, brackish, and silt-water corrosion while supporting 90 °C continuous duty
  • Layer 2 — Conductor Screen: Extruded semi-conductive rubber compound tightly bonded over stranded copper — Primary Field Function: Smooths strand-edge electric field stress inside 6/10 kV (Um 12 kV) service
  • Layer 3 — Main MV Insulation: Super-clean Ethylene Propylene Rubber (EPR), ≥ 1,000 MΩ·km IR at 20 °C — Primary Field Function: High wet-dielectric stability (17 kV AC test) and 250 °C short-circuit tolerance
  • Layer 4 — Insulation Screen: Extruded semi-conductive layer plus semi-conductive tape wrap — Primary Field Function: Confines radial electric field and eliminates micro-void partial discharges (≤ 10 pC)
  • Layer 5 — Split Earth Cores (2×12.5 mm²): Two flexible tinned copper cores (25 mm² total PE) in semi-conductive rubber covering — Primary Field Function: Symmetrical low-impedance protective earth nestled in two outer phase interstices
  • Layer 6 — Screened Control Group S(4×0.5): Two twisted pairs (4×0.5 mm² tinned Cu, EPR insulated) under ≥ 80% CuSn screen — Primary Field Function: Carries pump thermal/leakage sensors with 1.5 to 2.0 kV AC isolation from 6 kV power
  • Layer 7 — Water-Blocking Inner Sheath: Extruded black GM1b water-blocking rubber compound — Primary Field Function: Locks circular core geometry and adds an internal radial barrier against water migration
  • Layer 8 — Overall EMC & Fault Braid: High-coverage tinned copper wire braid (≥ 80%, 84% typical; filament spec disclosed) — Primary Field Function: Drains VFD common-mode noise and joins PE cores for 8.37 kA / 1 s earth-fault rating
  • Layer 9 — Heavy-Duty Outer Sheath: High-visibility red 5GM5 polychloroprene (PCP) elastomer (≤ 54 mm tight-OD build) — Primary Field Function: Resists water, oil, ozone, UV, tear, and flame per IEC 60332-1-2:2025

Explore our reeling and trailing cable portfolio, heavy-duty rubber cable range, and material handling and port crane industry hub.

4. Pre-Shipment 17 kV FAT Protocol, Drum Logistics, and MV Pump Cable Selection

Pre-shipment medium-voltage FAT is drum-level lab testing run before balance payment and export release. It verifies AC withstand, partial discharge, screen continuity, water immersion, and finished size.

The plate below pairs the field replacement interface (3×50 mm² MV stress cones, 2×12.5 mm² earth leads, and 4-core control lead) with TEBAOFLEX's steel-wood export drum. That heavy drum holds the full 180 m cable in one joint-free run.

Side-by-side engineering plate showing on the left an existing red 6/10 kV submersible pump cable termination with three phase stress cones, two green-yellow split earth leads, and a four-core control group, and on the right a TEBAOFLEX steel-reinforced wooden export cable drum for 180 m joint-free delivery

Worked MV Dielectric, Partial Discharge, and Fault-Energy Verification

Clear pass/fail lab limits separate real high-voltage rubber factories from paper brokers. Audit the four core 6/10 kV (U0 = 6.0 kV) FAT gates agreed for this 180 m drum:

1. Routine AC dielectric withstand margin (17 kV AC for 5 min):
   Test ratio = 17.0 kV / 6.0 kV (U_0) = 2.83 x U_0 (zero breakdown or flashover permitted)

2. Partial discharge (PD) acceptance voltage (1.73 x U_0):
   V_PD = 1.73 * 6.0 kV = 10.38 kV (~10.4 kV AC) -> Apparent charge must stay <= 10 pC.

3. Control-group dielectric & screen continuity audit:
   S(4 x 0.5 mm2) screen >= 80% CuSn; test at 1.5 kV / 1 min (up to 2.0 kV / 5 min FAT gate).
   Overall CuSn braid >= 80% (84% typical) verified end-to-end with strand count & wire OD log.

4. Combined earth-fault thermal capacity (8.37 kA for 1.0 s, 60 C to 250 C rise):
   Specific fault energy I^2 * t = (8.37 kA)^2 * 1.0 s = 70.1 kA2*s (ample margin on 6 kV feeders).

Realistic Workshop Water-Immersion Testing vs. Paper Promises

TEBAOFLEX engineers also addressed a common buying trap: water-immersion test realism. On standard rubber core lines, extruded cores rest at least 16 hours before ≥ 1 hour water immersion and AC testing. When a contract calls for a 24-hour clean-water soak (17 kV AC / 5 min, zero breakdown) on the full 180 m drum, TEBAOFLEX books dedicated tank time. Before balance payment, the factory supplies test reports, drum photos, video, a joint-free guarantee letter, and a cut end-sample.

Referenced standards (DIN VDE 0250-813, IEC 60502-2, IEC 60228, IEC 60811-202, IEC 60332-1-2) set design and test rules. TEBAOFLEX supplies CE compliance records for this order type. Lock any extra third-party witness tests in the contract before production begins.

Comparing TEBAOFLEX Medium-Voltage Submersible Pump and Reeling Series

  • Custom (N)TSCGEWCUEUS 6/10 kV (This Case) — Rated Voltage & Test Basis: 6/10 kV (Um 12 kV); 17 kV AC / 5 min; ≤ 10 pC PD; Core, Screen & Armor Architecture: 3×50 EPR + 2×12.5 PE + S(4×0.5) + 84% CuSn braid; Jacket & Temp. Limit: GM1b inner + red 5GM5 PCP (-40 to +90 °C); Bend / Depth Duty: ≤ 54 mm OD; 6×OD (324 mm); Primary Field Application: River port & industrial 6 kV VFD submersible pump replacement
  • NTSCGERLWÖU Armoured Submersible Pump Cable — Rated Voltage & Test Basis: 3.6/6 & 6/10 kV (Um 7.2/12 kV); 11/17 kV test; Core, Screen & Armor Architecture: Longitudinal & radial water-blocked (LW) + steel-wire armor; Jacket & Temp. Limit: Heavy-duty wet-shaft rubber (+90 °C cond.; 250 °C SC); Bend / Depth Duty: AD8 deep shaft; 10 to 15×OD; Primary Field Application: Deep mine shafts and rocky sumps needing mechanical steel armor
  • (N)TSCGECEWÖU Individually Screened MV Cable — Rated Voltage & Test Basis: 3.6/6 to 12/20 kV (U0/U); Core, Screen & Armor Architecture: 3×Cu individual phase braids + semicon EPR (3GI3) cores; Jacket & Temp. Limit: Red 5GM3/5GM5 or waterproof CM elastomer (90 °C cond., 250 °C SC); Bend / Depth Duty: 6×OD fixed; 10×OD flex; 12×OD reeling; Primary Field Application: MV distribution, trailing, reeling, and wet-zone flexible feeders
  • NTSCGEWÖU Medium-Voltage Reeling Cable — Rated Voltage & Test Basis: 1.8/3 to 12/20 kV (U0/U); Core, Screen & Armor Architecture: 3-core 3GI3 EPR + split earth + anti-torsion textile braid; Jacket & Temp. Limit: Heavy-duty red 5GM5 PCP (90 °C cond., 250 °C SC); Bend / Depth Duty: 6×OD fixed; 10×OD flex; 12×OD reeling; Primary Field Application: Port cranes, stacker-reclaimers, and dynamic MV reels
  • (N)TSW 3.6/6 kV Clean-Water Pump Cable — Rated Voltage & Test Basis: 3.6/6 kV (U0/U); Core, Screen & Armor Architecture: Three-phase stranded copper + EPR insulation + screen; Jacket & Temp. Limit: Water-service elastomer sheath; Bend / Depth Duty: Order-specific wet immersion; Primary Field Application: Clean-water intakes and municipal 3.6/6 kV submersible pumps
  • 15000BE (OGŁ) 0.6/1 kV Mine Dewatering Cable — Rated Voltage & Test Basis: 0.6/1 kV (AS/NZS 5000.1 / PN-90/E-90100); Core, Screen & Armor Architecture: Class 5 tinned Cu (4×16 to 50) + 4×1.5 monitoring + 85% CuSn braid; Jacket & Temp. Limit: Blue heavy-duty TPV elastomer (-25 to +90 °C; 500 m depth); Bend / Depth Duty: 8×OD fixed/dynamic; Primary Field Application: Low-voltage VFD and DOL mine dewatering sumps

See our 6/10 kV NTSCGEWCWOU submersible mining pump video and mining cable ICEA/VDE FAT guide. You can also browse our mining and tunneling cable hub.

5. Submersible Pump Commissioning Rules and Six-Point MV Replacement RFQ Checklist

Proper pit installation protects the 5GM5 PCP jacket and 6/10 kV stress cones inside wet wells. Apply three rules when re-cabling a pump:

  1. Match gland seal fit to caliper-checked cable OD. Confirm the pump entry grommet matches the ≤ 54 mm build before lowering the pump. Tight seals abrade PCP, while loose seals fail IEC 60529 continuous immersion protection.
  2. Build clean MV stress cones and ground both screens properly. Strip the semicon layer smoothly without nicking EPR. Bond both 12.5 mm² PE cores plus overall CuSn braid to main earth, and ground the S(4×0.5) screen cleanly to block ground loops.
  3. Anchor vertical cable weight on a stainless grip above the pit. Never let 180 m of heavy cable (~5.09 kg/m dry) hang solely from the pump gland. Hold 6×OD (≥ 324 mm) bend clearance over every pit rim.

Six-Point Pre-Order RFQ Checklist for 6/10 kV Submersible Pump Replacement Cables

Lock six project details before approving a replacement datasheet and drawing:

  1. Exact cable entry grommet OD ceiling. Measure the pump bore and set a hard OD cap (such as ≤ 54 mm), backed by wall checks per IEC 60811-202:2023.
  2. Continuous uncut drum length and zero-joint rule. State exact run length (180 m on one drum) with zero factory splices or repair patches.
  3. Power, split-earth, and control core schedule. List phase size (3×50 mm²), total split earth (2×12.5 mm² = 25 mm²), and 1.5 to 2.0 kV screen tests on S(4×0.5 mm²) pairs.
  4. Drive type, cable length, and RLC data. State DOL or 6,000 V VFD with du/dt filter, and request per-km C, L, R_20, and 8.37 kA / 1 s fault data.
  5. Pre-shipment FAT matrix and witness proof. Lock 17 kV AC / 5 min, ≤ 10 pC PD at 1.73 U0, 24 h clean-water soak (if needed), screen continuity, end-cut sample, and drum photos.
  6. Certificates, print legend, and drum limits. Confirm regional docs (CE), jacket marks plus meter marks, and max drum size and mass (1.2×1.1×1.2 m, ~1,026 kg) for LCL handling.

Editorial Note: Jyen (Medium-Voltage Submersible & Port Cable Engineering Desk, TEBAOFLEX) checked all RLC values and FAT gates against the Rev3 datasheet and Kazakhstan project records. Referenced standards (DIN VDE 0250-813, IEC 60502-2, IEC 60228, IEC 60529, IEC 60811-202, IEC 60332-1-2, IEC 61800-3, DIN VDE 0298-4) set test baselines. Put any extra third-party certifications in your purchase order. Visit our About TEBAOFLEX manufacturing page or contact our engineering desk with your pump grommet and VFD specs.

Image Credits: Hero cover photo "Kriushinskii Shipyard facility in Ulyanovsk River Port 2024.jpg" by Apetrov09703 via Wikimedia Commons (CC BY-SA 4.0). River intake tower photo "Louisville, KY - Louisville Water Company Pump Station No. 3 (3).jpg" by Bmzuckerman via Wikimedia Commons (CC BY 4.0). Medium-voltage substation photo "Transformer at substation.jpg" by Wikideas1 via Wikimedia Commons (CC0). Rev3 nine-layer cross-section diagram, field termination reference photo, and export drum photo by TEBAOFLEX.

Frequently Asked Questions

Can a 6/10 kV (N)TSCGEWCUEUS 3×50+2×25/2+S(4×0.5) cable fit inside a 54 mm pump entry grommet?

Yes. Standard Rev3 tables list a 54 to 58 mm nominal outer diameter for 3×50 mm² braided builds with control pairs. TEBAOFLEX can engineer a tight ≤ 54 mm build. Locking that ≤ 54 mm cap in the approved datasheet avoids costly site gland rework.

Is TEBAOFLEX (N)TSCGEWCUEUS 6/10 kV suitable for a 180 m 6,000 V VFD pump feeder with a du/dt filter?

Yes. With 0.345 μF/km capacitance and 0.371 mH/km inductance, 180 m gives 62.1 nF total capacitance and 32.8 Ω surge impedance. One-way travel time is 2.04 μs, with just 0.068 A/phase charging current at 50 Hz. Paired with an output du/dt filter, triple-extruded EPR (Um 12 kV) runs 6,000 V VFD loads cleanly.

How is the S(4×0.5) control group shielded against 6 kV VFD noise inside the same cable?

The four 0.5 mm² tinned-copper monitoring wires form two twisted EPR pairs under their own ≥ 80% tinned-copper woven screen tested at 1.5 to 2.0 kV AC. A GM1b inner sheath and an overall ≥ 80% (84% typical) copper braid then enclose the full bundle.

What is the earth-fault current rating of the 2×12.5 mm² split earth cores plus overall copper braid?

Two 12.5 mm² (25 mm² total) tinned-copper earth cores work in parallel with the dense (84% typical) overall copper braid. Together they carry a verified 8.37 kA one-second earth fault across a 60 °C to 250 °C rise (70.1 kA²·s fault energy capacity).

Which pre-shipment FAT tests should buyers lock before balance payment on a 6/10 kV submersible pump drum?

Lock 17 kV AC / 5 min dielectric withstand and partial discharge ≤ 10 pC at 1.73 U0 (10.4 kV). Add ≤ 0.393 Ω/km DC resistance at 20 °C, ≥ 1,000 MΩ·km IR, and 1.5 to 2.0 kV control-pair tests. Include end-to-end screen continuity with filament specs plus 24-hour water immersion when required.

Why must a 180 m submerged 6/10 kV pump replacement cable be delivered on one drum with zero joints?

Submerged splices or hidden factory repair patches create weak points for radial water ingress, partial discharge, and lifting tears. Ordering one continuous 180 m joint-free drum (~916.9 kg net, ~1,026 kg gross) with sequential meter marks and a written no-joint guarantee removes splice risk.

River water intake pumping station tower standing in open river water with steel pedestrian bridge access
River water intake pumping tower illustrating continuous submerged medium-voltage pump cable service.
Medium-voltage distribution substation showing step-down transformer, overhead switchgear busbars, and insulated MV feeder cables
Medium-voltage power distribution bay feeding 6 kV industrial pump drives and du/dt output filters.
TEBAOFLEX Rev3 nine-layer cross-section diagram of (N)TSCGEWCUEUS 6/10 kV S3×50+2×25/2+S(4×0.5) mm² MV submersible pump cable
Official Rev3 9-layer cross-section mapping three EPR phase cores, dual semicon screens, split PE cores, S(4×0.5) control group, GM1b sheath, CuSn braid, and red 5GM5 PCP jacket.
Side-by-side plate showing red 6/10 kV submersible pump termination with three stress cones, two earth leads, and control group beside a TEBAOFLEX export steel-wood drum
Field replacement termination interface (3×50 MV + 2×12.5 PE + 4×0.5 control) paired with a TEBAOFLEX steel-wood export drum for 180 m joint-free delivery.