What the video shows
88.5 second factory production and specimen verification video of our 600 V UL Style SOOW shielded 3x10 AWG portable cord (UL 62 and CSA C22.2 No. 49) for mobile VFD dewatering pump skids.
The video illustrates a sample, process, or operating context. Final product construction, suitability, standards, and test acceptance criteria are confirmed against the ordered specification.
TL;DR: EMI-shielded UL Style SOOW portable cord (3x10 AWG, 600 V, 30 A) is an extra-hard-usage thermoset flexible power cable certified to UL 62 and CSA C22.2 No. 49 (UL 62 Ed. 21, 2026). It integrates three 104/30 AWG Class K bare copper cores, 90 °C oil-resistant EPDM insulation, an extruded black elastomer inner bedding, a >= 85% optical coverage tinned copper wire braid shield (IEC TR 61000-5-2, 1997), and a matte-black chlorinated polyethylene (CPE) jacket (OD ~18.8 mm / 0.74 in). In our 1:28 (88.5 s) factory production and specimen verification video, we show how this 5-layer cord feeds a mobile variable-frequency drive (VFD) dewatering pump skid from a NEMA 4X power pedestal via a portable reel cart while blocking pulse-width modulation (PWM) switching noise from corrupting 4-20 mA flow sensors.
| Engineering Parameter | Verified Specimen & Video Specification (3x10 AWG Shielded SOOW) | Governing Standard / Test Method | Field Engineering Role |
|---|---|---|---|
| Cable Style & Dual Listing | UL Style SOOW (600 V) + CSA C22.2 No. 49 (cUL) FT2 | UL 62 & CSA C22.2 No. 49 | Extra-hard-usage portable cord for US and Canadian plants |
| Conductor Geometry (Layer 01) | 3 x 10 AWG (~5.26 mm²), 104/30 AWG Class K bare copper | ASTM B174 / UL 62 Sec. 5 | Supple hand-truck reel coiling; max DC resistance <= 3.54 Ω/km |
| Core Insulation (Layer 02) | 90 °C oil-resistant EPDM (1.14 mm / 45 mils wall; Black, Red, Green/Yellow) | UL 62 Oil-Resistant "O" Inner | Resists pump grease and thermal aging from -40 °C to +90 °C |
| Inner Bedding & Wrap (Layer 03) | Extruded black elastomer valley-filling cushion + clear PET tape | Concentric core roundness control | Prevents copper braid wires from cutting into EPDM under bending |
| EMI/RFI Shield (Layer 04) | 24-carrier woven tinned copper wire braid (>= 85% optical coverage) | High-frequency PWM containment | Traps inverter common-mode noise near 4-20 mA flow and level loops |
| Outer Jacket (Layer 05) | Matte-black thermoset CPE (2.03 mm / 80 mils wall; OD ~18.8 mm / 0.74 in) | UL 62 "OW" + CSA FT2 Flame | Resists basin water, UV sunlight, oil, and concrete floor abrasion |
| Rated Ampacity & Span | 30 A (2 power cores + 1 PE ground) or 25 A (3 loaded cores) | NFPA 70 (NEC) Table 400.5(A)(1) | Powers mobile 600 V VFD pumps across 10.1 m to 45 m deck runs |
Outdoor Wastewater Basin Dewatering: The 3-point Portable VFD Power Path
UL Style SOOW portable cord is a 600 V extra-hard-usage flexible elastomer power cable defined under UL 62 Flexible Cords and Cables Standard in which each letter designates a verified construction property: S for 600 V service cord, O for oil-resistant inner core insulation, O for oil-resistant outer jacket, and W for outdoor weather and water resistance. When municipal water treatment plants, refinery tank farms, or tunnel dewatering crews deploy wheeled centrifugal pump skids, standard unshielded SOOW cords solve mechanical dragging and wet-deck exposure but leave nearby instrumentation unprotected against inverter switching noise.
In the opening field sequence of our engineering video (00:00 to 00:35), the 600 V 3x10 AWG shielded SOOW cord operates along a 3-point outdoor concrete basin power path:
- Point [1] Weatherproof Shore Power Box (NEMA 4X). A stainless pedestal mounted along the clarification basin handrail feeds 600 V / 30 A power through a sealed industrial twist-lock plug into the portable cord.
- Point [2] Wheeled Portable Cord Reel Cart. An operator pays out and retrieves a 10.1 m (33 ft) active flexible cord span across rough concrete walkways. The extruded inner bedding and 104/30 AWG Class K stranding keep the cable round and kink-free over the reel spool.
- Point [3] Mobile VFD Pump and Flow Sensor Skid. The cord terminates at a wheeled centrifugal pump cabinet equipped with an onboard variable-frequency drive (VFD) and an inline 4-20 mA electromagnetic flow transmitter mounted on the discharge header.

Decoding the Verified UL 62 and CSA C22.2 No. 49 Sheath Legend
Every meter of the finished matte-black CPE jacket carries a permanent white dot-matrix identification string verified in our continuous specimen scan (00:50 to 00:56 of the video and macro photo f472208c):
UL STYLE SOOW 600V 10 AWG 3 °C -40 °C 90 °C AWM I/II A/B FT2 CSA TEW UL 62 [Sequential Meter Mark: 0017M ... 104M]
For electrical inspectors and plant safety engineers auditing incoming reels against NFPA 70 (National Electrical Code) Article 400 Flexible Cords and Flexible Cables and the CSA C22.2 No. 49 Flexible Cords and Cables Standard, this dual marking confirms four compliance boundaries:
- UL STYLE SOOW 600V 10 AWG 3 °C UL 62: Approved for 600 V extra-hard usage in damp, wet, and oil-exposed industrial locations under NEC Table 400.4.
- -40 °C 90 °C: Verified cold-bend flexibility down to -40 °C and continuous conductor thermal stability up to +90 °C.
- AWM I/II A/B & CSA TEW: Dual-rated appliance wiring material (Class I internal / Class II external, Group A/B) and Canadian thermoplastic/thermoset equipment wire (600 V, 105 °C dry / 90 °C cord rating), allowing the cord to pass directly from outdoor deck reels into UL 508A control cabinets without a transition junction box.
- FT2: Passes the horizontal flame specimen test under CSA C22.2 No. 0.3 / UL 2556 without dropping flaming particles.
Why Do Mobile VFD Pump Skids Require an >= 85% Tinned Copper Braid Shield?
A tinned copper wire braid shield (>= 85% optical coverage) is a woven metallic electromagnetic compatibility (EMC) screen placed over the inner elastomer bedding of a flexible power cord (IEC TR 61000-5-2, 1997). It provides a low-impedance 360-degree return path for high-frequency common-mode currents (30 kHz to 30 MHz) generated by insulated-gate bipolar transistor (IGBT) inverter switching.
When a mobile dewatering pump or portable mixer is fed by a 480 V or 600 V PWM inverter (using 3x10 AWG Black / Red / Green-Yellow PE for single-phase VFD input feeds, or the matching 4x10 AWG 3P+PE construction for three-phase VFD motor output leads per NEC 250.119), the drive switches DC bus voltage at carrier frequencies between 2 kHz and 16 kHz with rise times (dV/dt) of 500 V/us to 5,000 V/us. On an unshielded SOOW portable cord, the power conductors act as an unscreened radiator. Capacitive coupling between the cord and grounded steel handrails or wet concrete decks injects high-frequency common-mode noise into adjacent 4-20 mA flow meters, pH probes, and RS-485 telemetry cables.

Foil-Only Tape vs. 24-carrier Tinned Copper Braid Under Reel-Cart Flexing
Fixed tray VFD cables (Type TC-ER) often use rigid aluminum-Mylar foil tape. However, when a portable cord is wound and unwound daily on a small-diameter hand-truck reel cart (drum diameter 250 mm to 350 mm), thin aluminum foil work-hardens and cracks transversely after a few hundred coiling cycles.
Our UL 62 and CSA C22.2 No. 49 compliant portable cord engineering range and shielded flexible cable portfolio solve this mechanical-to-electrical trade-off by weaving a 24-carrier fine tinned copper braid at >= 85% optical coverage directly over an extruded black elastomer inner cushion:
- Low Surface Transfer Impedance (Z_T) Across VFD Harmonic Bands. Fine tinned copper strands cross at an optimized braid angle (30 to 40 degrees), maintaining low DC shield resistance (< 6.5 Ω/km) and effective magnetic and capacitive screening across the 10 kHz to 30 MHz VFD switching spectrum.
- Zero Foil Tearing During Tight Bending (6 x OD). Unlike aluminum foil, braided tinned copper wires slide slightly over the PET separator tape during 6 x OD (~113 mm) dynamic bending without opening gaps in the shield.
- Fast 360-degree EMC Gland Clamping. During termination into a NEMA 4X VFD enclosure, electricians flare the tinned copper braid directly over the compression cone of a nickel-plated brass EMC cord grip. You can review the transfer impedance physics in our guide on VFD cable 360-degree EMC gland termination and transfer impedance and compare grounding topologies in our analysis of ground loops in shielded control cables: single-end vs. both-ends termination.
Inside the 5-Layer Shielded 3x10 AWG UL Style SOOW Architecture and Product Selection
Extruded elastomer inner bedding (valley-filling inner jacket) is a concentric rubber layer extruded over the cabled EPDM insulated cores before metallic braiding that fills the three triangular trefoil interstices into a smooth cylinder, preventing copper braid wires from sawing into the primary core insulation during repeated reel-cart payout.
Many low-cost shielded portable cords wrap a copper braid directly over three bare twisted cores with paper fillers. Under reel tension and floor foot traffic, the hard copper braid presses into the soft paper fillers, deforming the cable into a triangle and abrading the 90 °C EPDM insulation wall. In the 3D strip-back (00:35 to 00:50) and macro end-face audit (00:56 to 01:28) of our video, you can inspect all five concentric layers of our 600 V UL Style SOOW and SJOOW heavy-duty portable cord.

Layer-by-Layer Breakdown (05 -> 01 Strip-Back Sequence)
- Layer 01: 3 x 10 AWG (5.26 mm²) Class K Extra-Flexible Bare Copper (104/30 AWG). Each conductor bundles 104 strands of 30 AWG (0.254 mm) annealed bare copper wire per ASTM B174 and UL 62. Compared with 19-strand THHN building wire, 104/30 rope-bunch stranding reduces bending stiffness by more than 70% while keeping 20 °C DC resistance at or below 3.54 Ω/km (1.08 Ω/1000 ft).
- Layer 02: 90 °C Oil-Resistant EPDM Rubber Insulation ("O", 1.14 mm / 45 mils). Cross-linked ethylene propylene diene monomer (EPDM) rubber provides high dielectric strength (2,000 V AC factory hipot), ozone resistance, and zero thermal softening up to +90 °C. Our specimen uses high-contrast Black and Red power cores paired with an extruded bi-color Green/Yellow equipment grounding core (PE) for global and North American safety compliance.
- Layer 03: Extruded Black Elastomer Bedding + Clear PET Separator Tape. An integral black elastomer inner sheath fills the core valleys to form a concentric circular cushion, while a helical polyester (PET) tape allows the insulated cores to slip smoothly during torsion and tight coiling.
- Layer 04: >= 85% Tinned Copper Wire Braid Shield. A 24-carrier high-speed rotary braider weaves corrosion-resistant tinned copper strands uniformly around the inner bedding, providing both EMI/RFI containment and radial cut-through protection.
- Layer 05: Heavy-Duty Matte-Black Thermoset CPE Outer Jacket ("OW", 2.03 mm / 80 mils, OD ~18.8 mm). Vulcanized chlorinated polyethylene (CPE) resists mineral and hydraulic oils (ASTM D471 / IRM 902), municipal wastewater chemicals, UV sunlight, and sub-zero -40 °C winter flexing.

Comparing Portable Cord Families Across Voltage, Jacket Chemistry, and EMI Shielding
When specifying portable cords for pumps, generators, stage lighting, or mobile automation skids, buyers can cross-reference five related constructions across our CSA C22.2 No. 49 certified portable cord lineup and industrial VFD cable range:
| Portable Cord Model & Link | Rated Voltage & Standard | Core Insulation / Outer Jacket | EMI Shielding Architecture | Operating Temp Range | Nominal OD (3x10 AWG Reference) | Primary Industrial Application |
|---|---|---|---|---|---|---|
| UL Style SOOW Shielded 3x10 AWG (Featured Video Specimen) | 600 V (UL 62 / CSA C22.2 No. 49 / FT2) | 90 °C Oil-Resistant EPDM + Extruded Bedding + Thermoset CPE | >= 85% Tinned Copper Braid | -40 °C to +90 °C | ~18.8 mm (0.74 in) | Mobile VFD dewatering pumps, flow sensor skids, noisy inverter feeds |
| Standard Unshielded UL Style SOOW | 600 V (UL 62 / CSA C22.2 No. 49 / FT2) | 90 °C Oil-Resistant EPDM + Thermoset CPE | Unshielded | -40 °C to +90 °C | ~17.3 mm (0.68 in) | Across-the-line mobile motors, portable generators, construction tools |
| UL Style SEOOW TPE Portable Cord | 600 V (UL 62 / CSA C22.2 No. 49) | Thermoplastic Elastomer (TPE) core + TPE jacket | Unshielded (or custom shielded) | -50 °C to +105 °C | ~16.9 mm (0.665 in) | Arctic cold-storage facilities, food/beverage washdown, lightweight reels |
| UL Style SJEOOW Junior Cord | 300 V (UL 62 / CSA C22.2 No. 49) | Thermoplastic Elastomer (TPE) core + TPE jacket | Unshielded | -50 °C to +105 °C | ~11.0 mm (12 AWG max) | Light portable instrumentation, hand tools, 120/240 V control pendants |
| 2kV Type W Heavy Portable Power Cable | 2,000 V (ANSI/NEMA WC 23058 / UL 1650) | 90 °C EPR + Two-layer reinforced CPE / PCP | Unshielded (use SHD-GC for shielded) | -40 °C to +90 °C | ~24.1 mm (3x8 AWG start) | Heavy mining skids, dockside shore power, crane magnet reels |
For international projects operating under European harmonised standards (450/750 V instead of 600 V), see our technical comparison of H07RN-F heavy-duty polychloroprene rubber cables and our engineering walkthrough on what H07RN-F cable is and how it compares to North American SOOW. You can also watch our 5-core SOOW mobile power distribution demonstration video for three-phase 3P+N+PE generator hookups.
How Do You Calculate Ampacity Derating, Voltage Drop, and Cord Grip Sizing for 3x10 AWG Shielded SOOW?
Sizing a 3x10 AWG shielded SOOW portable cord requires checking three engineering boundaries: current-carrying conductor count under NEC Table 400.5(A)(1), coiled reel-cart thermal derating, and the larger ~18.8 mm (0.74 in) outer diameter created by the inner elastomer bedding and tinned copper braid.
NEC Table 400.5(A)(1) Ampacity and Reel-Cart Coiling Derating
Under NFPA 70 (NEC) Table 400.5(A)(1), a 10 AWG flexible cord is rated at:
- 30 A (Column B) when 2 conductors carry current (such as a 240 V or 480 V single-phase VFD input or DC bus feed, where the third Green/Yellow wire serves strictly as the equipment grounding conductor).
- 25 A (Column A) when all 3 conductors carry balanced three-phase current (where the metallic enclosure or separate ground path is used, or in a 3-wire delta circuit).
When part of the portable cord remains wound on a hand-truck reel cart during continuous pumping, inner turns trap I2R heat. Apply a drum layer derating factor (K_reel = 0.85 for 1 coiled layer; 0.65 for 2 layers; 0.45 for 3 layers) alongside the UL 62 ambient temperature factor (K_temp = 1.00 at 30 °C; 0.91 at 40 °C; 0.82 at 50 °C for 90 °C EPDM):
I_allowable = I_NEC_base * K_temp * K_reel | Delta_V_1phase = 2 * I_load * (L_m / 1000) * (R_ac_90 °C * cos(phi) + X_L * sin(phi))
Worked Calculation (10.1 m Active Span vs. 30 m Total Reel Length at 24 A Load):
- At 90 °C operating temperature, the AC resistance of 10 AWG Class K bare copper (R_20 °C = 3.54 Ω/km) rises to R_ac_90 °C = 3.54 [1 + 0.00393 (90 - 20)] = 4.51 Ω/km, with inductive reactance X_L = 0.11 Ω/km.
- Over the 10.1 m deployed span shown in our video (30 m total cord on a 1-layer ventilated reel cart at 30 °C ambient), allowable current is 30 A 1.00 0.85 = 25.5 A (> 24 A pump load).
- Single-phase voltage drop over the full 30 m (0.030 km) cord at 24 A and 0.85 power factor is 2 24 0.030 (4.51 0.85 + 0.11 0.527) = 5.60 V (1.17% on a 480 V circuit or 0.93% on a 600 V circuit, well below the 3.0% NEC branch-circuit limit) (NFPA 70, 2026). On a balanced three-phase 600 V circuit (sqrt(3) factor), voltage drop over the same 30 m run at 24 A is 4.85 V (0.81%).
Why Unshielded Cord Grip Charts Fail on Shielded 3x10 AWG SOOW (~18.8 mm OD)
A common field installation error occurs when procurement orders 1/2" NPT cord grips sized for standard unshielded 3x10 AWG SOOW (OD ~17.0-17.5 mm / 0.67-0.69 in). Because our shielded construction adds an extruded elastomer inner bedding (~0.8 mm radial wall) and a 24-carrier tinned copper braid (~0.6 mm radial build), the verified nominal outer diameter increases to ~18.8 mm (0.74 in) (tolerance 18.2 mm to 19.3 mm).
| Trade Size & Thread Standard | Typical Clamping Range (mm / in) | Fits Unshielded 3x10 AWG SOOW (~17.3 mm)? | Fits Shielded 3x10 AWG SOOW (~18.8 mm)? | Recommended EMC Termination Hardware |
|---|---|---|---|---|
| 1/2" NPT or M20 x 1.5 Standard Gland | 10.0 - 16.0 mm (0.39 - 0.63 in) | No (Undersized) | No (Jacket will not enter nut) | Do not specify for 10 AWG SOOW |
| 3/4" NPT Standard Narrow-Range Cord Grip | 12.7 - 18.0 mm (0.50 - 0.71 in) | Yes | Borderline / Too Tight (18.8 mm binds) | Avoid narrow-insert 3/4" bushings |
| 3/4" NPT Wide-Range or 1" NPT EMC Gland | 16.0 - 21.0 mm (0.63 - 0.83 in) | Yes | Yes (Optimal Fit for ~18.8 mm) | Nickel-plated brass 3/4" NPT or 1" NPT (M25 x 1.5 / PG21) 360-degree EMC gland with stainless mesh strain-relief grip |
Factory Production Line, Specimen Macro Audit and Pre-Shipment FAT Timeline
To give North American electrical distributors, OEM pump skid builders, and plant engineers full pre-shipment transparency, our 1:28 (88.5 s) video documents the exact manufacturing line and finished wooden drum quality control checks for the 600 V UL Style SOOW Shielded 3x10 AWG batch:
| Video Timestamp (MM:SS) | Production / QC Stage | Verified Engineering Detail Shown in Uncropped Footage | Quality Control Acceptance Criterion |
|---|---|---|---|
| 00:00 - 00:10 | Outdoor Dewatering Scene & 3D Cross-Section | NEMA 4X pedestal -> reel cart -> VFD pump skid + 3x10 AWG concentric 5-layer geometry reveal | Confirms Black / Red / Green-Yellow core layout and ~18.8 mm outer profile |
| 00:10 - 00:14 | Clip 01/03: High-Speed 24-carrier Tinned Cu Braiding | Uncropped 9:16 native shop video of fine tinned copper strands woven over black elastomer bedding | Optical braid coverage >= 85%; zero broken carrier wires or loose loops |
| 00:14 - 00:18 | Clip 02/03: Thermoset Black CPE Jacket Extrusion | Precision ceramic guide roller stabilizing concentricity and matte surface finish of 600 V CPE jacket | Minimum wall >= 2.03 mm (80 mils); concentricity >= 85%; smooth matte finish |
| 00:18 - 00:22 | Clip 03/03: Multi-Groove Tension Accumulator Sheave | Multi-sheave cooling and haul-off accumulator maintaining uniform linear tension | Zero residual axial twist so internal copper braid stays flat and kink-free |
| 00:22 - 00:50 | Live Payout Simulation & 5-Layer Strip-Back (05 -> 01) | 10.1 m reel payout + X-ray VFD EMI shield view + sequential layer peel (CPE -> Braid -> Bedding -> EPDM -> 104/30 Cu) | Clean PET tape separation; zero rubber adhesion to tinned copper braid |
| 00:50 - 01:02 | Live Specimen QC: Sheath Print & Gloved Macro Cut | Continuous axial scan of UL STYLE SOOW 600V 10 AWG 3 °C -40 °C 90 °C AWM I/II A/B FT2 CSA TEW UL 62 + gloved end-face | Legible indelible dot-matrix print + meter counter (0017M...104M); concentric core bedding |
| 01:02 - 01:28 | 6-point Spec Summary & 8 Uncropped Drum/Specimen Photos | 3000x4000 oblique/axial sample cuts (Photos 01-06) + layer-wound export wooden reels (Photos 07-08) | 2,000 V AC 5-min dielectric withstand pass; IR verified; neat flanged wooden drum winding |
Pre-Shipment Factory Acceptance Test (FAT) Checklist for Custom Shielded SOOW Orders
Before releasing any shipment of shielded UL Style SOOW portable cord from our factory, our laboratory verifies five mandatory tests under UL 62, CSA C22.2 No. 49, and UL 2556:
- Conductor Stranding & 20 °C DC Resistance (UL 62 / ASTM B174). Verify 104/30 AWG strand count (0.254 mm wire diameter) and confirm DC resistance at 20 °C does not exceed 3.54 Ω/km (1.08 Ω/1000 ft) on Black, Red, and Green/Yellow cores plus < 6.5 Ω/km on the tinned copper braid.
- Full-Reel AC Dielectric Withstand & Spark Test. Every finished drum passes an inline 6.0 kV AC spark test during extrusion followed by a 5-minute 2,000 V AC high-potential soak (core-to-core and cores-to-braid shield) with zero breakdown.
- Optical Shield Coverage & Transfer Impedance Audit. Measure carrier pitch angle, strand count, and optical braid coverage (>= 85%) on cut end-face specimens to guarantee VFD harmonic suppression (IEC 62153-4-3).
- IRM 902 Hot Oil Immersion ("OO" Dual Oil Rating). Immerse both the inner 90 °C EPDM core insulation and the outer black CPE jacket in IRM 902 oil at 100 °C (212 °F) for 18 to 24 hours per UL 62 and UL 2556, verifying tensile strength and elongation retention (>= 60-75%).
- -40 °C Cold Bend & CSA FT2 Horizontal Flame Test. Condition finished cord specimens at -40 °C for 4 hours followed by mandrel winding with zero jacket cracking, and verify self-extinguishing performance under FT2 horizontal flame application.
To request a serialized FAT report, custom core count (3 °C, 4 °C, 5 °C, or multi-pair shielded SOOW), or sample cut for your mobile equipment fleet, contact our specialty cable engineering team or submit your project specification for a 24-hour technical quote.
Frequently Asked Questions
What does every letter in UL Style SOOW 600V portable cord stand for?
Under UL 62 and CSA C22.2 No. 49, S designates a 600 V extra-hard-usage service cord, the first O designates oil-resistant inner core insulation (90 °C EPDM rubber), the second O designates an oil-resistant outer jacket (thermoset chlorinated polyethylene, CPE), and W designates weather and water resistance for outdoor sunlight and wet-location duty from -40 °C to +90 °C.
Why add an extruded black elastomer inner bedding under the tinned copper braid in shielded SOOW cord?
An extruded black elastomer inner bedding fills the triangular valleys between the three 10 AWG EPDM cores to create a solid concentric cylinder before braiding. Without this cushion and its PET separator tape, a >= 85% tinned copper braid presses into soft paper fillers during portable reel-cart coiling, causing core corkscrewing and braid wire abrasion against the primary insulation.
What is the continuous ampacity of 3x10 AWG UL Style SOOW portable cord?
Per NFPA 70 (NEC) Table 400.5(A)(1), 3x10 AWG (5.26 mm²) SOOW portable cord is rated for 30 Amps when two conductors carry current and the third bi-color Green/Yellow core serves as the equipment grounding conductor (Column B), or 25 Amps when all three conductors carry balanced three-phase current (Column A) at 30 °C ambient in free air.
Should the >= 85% tinned copper braid shield on a mobile VFD pump cord be grounded at one end or both ends?
For variable-frequency drive (VFD) power cords (3x10 AWG for single-phase VFD input feeds or 4x10 AWG 3P+PE for three-phase VFD motor leads per NEC 250.119), terminate the >= 85% tinned copper braid shield (IEC TR 61000-5-2, 1997) through 360-degree EMC metallic cable glands at both ends (paired with the internal Green/Yellow 10 AWG PE conductor). Bonding both ends creates a low-inductance high-frequency return path that keeps PWM switching currents out of plant ground grids and nearby 4-20 mA flow sensor loops.
What size EMC cable gland fits TEBAOFLEX 600V 3x10 AWG shielded SOOW cord?
Because the extruded inner elastomer bedding and >= 85% tinned copper braid increase the nominal outer diameter of 3x10 AWG shielded SOOW to ~18.8 mm (0.74 in) (compared with ~17.3 mm for unshielded 3x10 AWG), specify a wide-range 3/4" NPT, 1" NPT, or metric M25 x 1.5 (clamping range 16.0 mm to 21.0 mm) nickel-plated brass EMC gland with a strain-relief mesh grip.
Request a Custom Shielded SOOW Sample or FAT Quote
Whether you are building wheeled VFD dewatering pump skids, upgrading noisy industrial inverter feeds, or sourcing custom 3 °C, 4 °C, 5 °C, or hybrid shielded UL Style SOOW portable cords, TEBAOFLEX supplies cut specimen samples, datasheets, and serialized factory acceptance test (FAT) reports. Explore our 600 V SOOW and SJOOW Portable Cord Series or contact TEBAOFLEX engineering for a fast technical quote.
WhatsApp: +86 185 9591 3361.
Image credits: Hero wastewater pump bay photo derived from "Biological filter discharge pumps Viikinmäki Wastewater Treatment Plant" by Antti Leppänen via Wikimedia Commons (CC BY 4.0, modified to remove background cabinet logo); outdoor wastewater treatment basin photo derived from "Siloam Springs WWTP 002" by Brandonrush via Wikimedia Commons (CC BY-SA 3.0); sludge pump and piping photo by YellowstoneNPS via Wikimedia Commons (Public Domain); 5-layer 3D construction and factory specimen QC boards by TEBAOFLEX.