Contact

Project case · Singapore

Case Study: 0.6/1 kV 2YSLCYK-J 4x120 mm² Double-Screened VFD Motor Cable for a Singapore Data Centre

How TEBAOFLEX built and verified 0.6/1 kV 2YSLCYK-J 4x120 mm² low-capacitance double-screened VFD motor cable with strict OD control for Singapore.

JyenOperations & Technical Engineer4 images
Hyperscale data centre rooftop cooling chillers and VFD fan arrays in Singapore
Location
Singapore
Application
Hyperscale data centre chilled-water pump and cooling VFD power circuits
Evidence
4 images
In this case15 sections
  1. 011. Project Context: Data Centre VFD Power Circuits in Singapore
  2. 022. Why Does 2YSLCYK-J Outperform Standard PVC Power Cables on Long Inverter Runs?
  3. Technical Data Table: 2YSLCYK-J 4 x 120 mm² vs. 4 x 35 mm²
  4. 033. 2YSLCYK-J 4x120 mm² Architecture, Pre-Shipment FAT, and TEBAOFLEX VFD Range
  5. Six-Layer Construction Breakdown
  6. Visual FAT Evidence: 49.12 mm Tube-Fit OD and Foil Check
  7. Selecting TEBAOFLEX 0.6/1 kV VFD Motor Cables
  8. 044. Export Drums, Tube-Pulling Limits, and Singapore Delivery
  9. 055. Pre-Order Checklist for Data Centre VFD Cable Buyers
  10. 06Frequently Asked Questions
  11. What does the designation 2YSLCYK-J 0.6/1 kV mean on a VFD motor cable?
  12. Why is PE insulation (2Y) preferred over standard PVC on long VFD motor runs?
  13. How should installers terminate the double screen on a 2YSLCYK-J 4x120 mm² cable?
  14. Is Class 5 flexible 2YSLCYK-J cable suitable for continuous drag-chain movement?
  15. How did TEBAOFLEX verify conduit compatibility before shipping the 4x120 mm² cable to Singapore?

Case at a glance

Location
Singapore
Application
Hyperscale data centre chilled-water pump and cooling VFD power circuits
Cable type
0.6/1 kV 2YSLCYK-J 4x120 mm² double-screened low-capacitance VFD motor cable →
Evidence
4 images
TL;DR: A Singapore cable distributor needed 0.6/1 kV 2YSLCYK-J 4x120 mm² VFD cable for a data centre. Because site crews pull the heavy 4x120 mm² cable through pre-installed tubes, outer-diameter accuracy and 100% foil-plus-braid EMC screening were critical. TEBAOFLEX built the DIN VDE 0250 polyethylene (2Y) construction and verified a 49.12 mm outer diameter (51.9 mm ceiling). We also shared dissected foil photos and shipped the lot to Singapore on steel-spoked ISPM 15 export drums.
  • Project Location: Project Specification & Verified Delivery Detail: Singapore (Hyperscale computing & digital data centre power and cooling infrastructure)
  • Buyer Profile: Project Specification & Verified Delivery Detail: Singapore specialist cable trading firm transitioning from long-lead European mill schedules
  • Cable Designation: Project Specification & Verified Delivery Detail: TEBAOFLEX 2YSLCYK-J 0.6/1 kV (4 x 120 mm² primary order; 4 x 35 mm² companion size)
  • Voltage & Thermal Rating: Project Specification & Verified Delivery Detail: U0/U 0.6/1 kV (700/1,200 V max AC; 900/1,800 V DC); -40 °C to +70 °C fixed (160 °C 5 s short-circuit)
  • Core & Dielectric Build: Project Specification & Verified Delivery Detail: IEC 60228 Class 5 bare copper (<= 0.161 Ω/km at 20 °C) + low-capacitance polyethylene (2Y PE) cores (HD 308 S2)
  • Dual EMC Screen: Project Specification & Verified Delivery Detail: Metal-out aluminium-laminated polyester foil (100% coverage) + tinned copper wire braid + black RAL 9005 UV/oil-resistant PVC sheath
  • Dimensional & Electrical FAT: Project Specification & Verified Delivery Detail: 49.12 mm digital-caliper verified OD (51.9 mm nominal ceiling for tube pull); 4 kV / 5 min AC dielectric withstand
  • Export Packaging: Project Specification & Verified Delivery Detail: Steel-spoked ISPM 15 heat-treated wooden drums with end-cap sealing and container-securing inspection

1. Project Context: Data Centre VFD Power Circuits in Singapore

Double-screened 2YSLCYK-J VFD motor cable is a 0.6/1 kV low-capacitance inverter power cable with PE insulation, dual foil-and-braid screening, and a black PVC sheath. It links pulse-width-modulated (PWM) frequency converters to three-phase AC motors while blocking electromagnetic interference (EMI).

AI and cloud data centres in Singapore run large chilled-water pumps, condenser loops, and cooling-tower fan banks round the clock. High-power VFD cabinets (160 kW to 250 kW drives requiring 4x120 mm² feeders) regulate pump speed to match server rack heat loads.

Closed-loop industrial cooling water centrifugal pump and motor bay typical of high-capacity data centre chilled-water plants fed by VFD cables

Inside a computing facility, unshielded PVC motor feeders create severe interference risks. Fast IGBT drive stages switch at 2 kHz to 16 kHz and emit harmonics up to 30 MHz. Under IEC 61800-3:2022 Adjustable Speed Power Drive Systems EMC Standard, converter cabling must contain radiated and conducted noise so nearby sensors and fibre links never trip.

Previously, this Singapore distributor bought 2YSLCYK-J feeders from Europe with 14 to 20 week lead times. Local factories could build standard power cables under IEC 60502-1:2021 Extruded Power Cable Standard, yet lacked low-capacitance PE VFD tooling. Sharing past production videos and cross-section photos from our VFD and EMC motor supply cable line secured technical approval.

2. Why Does 2YSLCYK-J Outperform Standard PVC Power Cables on Long Inverter Runs?

Decoding the German DIN VDE 0250 / 0207 code shows why data centre engineers specify 2YSLCYK-J instead of standard NYY-J wire.

  1. 2Y (Low-Permittivity Polyethylene Insulation). Standard PVC (Y) has a relative permittivity near 4.0 to 5.0, whereas solid polyethylene (2Y) sits near 2.3. Lower permittivity cuts core-to-screen capacitance nearly in half and trims PWM charging spikes.
  2. SL + C (Foil + Tinned Copper Braid Screen). A metal-side-out aluminium-polyester foil (100% coverage) blocks electric fields above 1 MHz. Meanwhile, the direct-contact tinned copper braid (C) keeps surface transfer impedance (Z_T) low below 1 MHz.
  3. YK (Black RAL 9005 PVC Outer Sheath). Unlike indoor transparent 2YSLCY-J jackets, the black K sheath adds EN 4892-2 Method A UV resistance, oil resistance, and wet-duct durability. It also passes IEC 60332-1-2 Vertical Flame Propagation Testing.
  4. -J (Green-Yellow Protective Earth Core). Four equal concentric cores (Brown, Black, Grey, and Green-Yellow per HD 308 S2) carry three-phase power plus full-size protective earth.

Cable mutual capacitance and surge impedance are the dielectric properties that govern ground-leakage spikes (I_cap = C_cable dV/dt) and reflected-wave voltage peaks at motor terminals. High-capacitance PVC feeders push extra switching current back into the inverter bridge, overheating IGBT modules and pitting motor bearings.

C_per_m proportional to epsilon_r / ln( D_ins / d_cond ) | I_peak = C_total * ( dV / dt ) | F_pull = 20 N/mm² * ( 4 * 120 mm² ) = 9,600 N max copper pulling tension

Dropping epsilon_r from ~4.5 (PVC) to 2.3 (2Y polyethylene) cuts cable capacitance by roughly 45% (DIN VDE 0207, 2021). That reduction keeps drive leakage currents low on long chiller-room runs. You can check critical length math in our guide to VFD cable reflected-wave critical length and dV/dt calculations.

Technical Data Table: 2YSLCYK-J 4 x 120 mm² vs. 4 x 35 mm²

The project datasheet covered two sizes for main chiller drives (4 x 120 mm²) and auxiliary pumps (4 x 35 mm²).

  • Rated & Max Operating Voltage: TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: 0.6/1 kV (700/1,200 V AC max; 900/1,800 V DC) | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: 0.6/1 kV (700/1,200 V AC max; 900/1,800 V DC) | Reference Standard / Test Condition: DIN VDE 0250 / IEC 60502-1
  • Conductor Stranding & Max R_20: TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: Class 5 bare Cu; <= 0.161 Ω/km at 20 °C | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: Class 5 bare Cu; <= 0.554 Ω/km at 20 °C | Reference Standard / Test Condition: IEC 60228:2023 / DIN VDE 0295
  • Free-Air Ampacity (I_B at 30 °C): TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: Approx. 292 A (apply grouping/tube derating) | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: Approx. 135 A (apply grouping/tube derating) | Reference Standard / Test Condition: DIN VDE 0298-4 (70 °C PE continuous / 160 °C 5 s SC)
  • Nominal Outer Diameter (OD): TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: 51.9 mm nominal ceiling (49.12 mm FAT measured) | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: 32.7 mm nominal | Reference Standard / Test Condition: Factory caliper verified for conduit/tube clearance
  • Copper Index & Total Mass: TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: 4,287.6 kg/km Cu / 5,556.8 kg/km total | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: 1,245.7 kg/km Cu / 1,817.3 kg/km total | Reference Standard / Test Condition: Production design weight schedule
  • Minimum Bending Radius: TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: 10 x OD fixed (~500 mm); 20 x OD occasional flex | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: 10 x OD fixed (~330 mm); 20 x OD occasional flex | Reference Standard / Test Condition: Cables > 20 mm OD (20 N/mm² max Cu pull force)
  • Routine Dielectric & Insulation Test: TEBAOFLEX 2YSLCYK-J 4 x 120 mm²: 4.0 kV AC for 5 min (core-core & core-screen) | TEBAOFLEX 2YSLCYK-J 4 x 35 mm²: 4.0 kV AC for 5 min; >= 20 MOhmkm at 20 °C | Reference Standard / Test Condition: IEC 60502-1 / IEC 60332-1-2 flame retardant

3. 2YSLCYK-J 4x120 mm² Architecture, Pre-Shipment FAT, and TEBAOFLEX VFD Range

Buyers switching from European mills to TEBAOFLEX expect clear physical proof before container loading. During October 2026 inspection, the Singapore buyer checked three items: outer diameter for tube pulling, internal aluminium-foil wrapping, and sheath print accuracy.

TEBAOFLEX 0.6/1 kV 2YSLCYK-J 4x120 mm² double-screened VFD motor cable cross-section showing four Class 5 fine-stranded copper cores, colour-coded PE insulation, non-hygroscopic fillers, Al-PET foil, tinned copper braid, and black RAL 9005 PVC sheath

Six-Layer Construction Breakdown

Each core uses fine-stranded copper built to IEC 60228:2023 Conductors of Insulated Cables Class 5 rules. The table below details all six layers.

  • 1. Phase & Earth Conductors: Material & Structural Execution: 4 x 120 mm² finely stranded bare copper (IEC 60228 Class 5) | Engineering Role in Data Centre VFD Circuits: High fatigue resistance under motor vibration and far easier cabinet termination than rigid Class 2 wire
  • 2. Core Insulation (2Y): Material & Structural Execution: Extruded low-permittivity polyethylene (Brown, Black, Grey, Green-Yellow) | Engineering Role in Data Centre VFD Circuits: Minimizes capacitive inverter switching losses and maintains >= 20 MOhmkm insulation resistance
  • 3. Core Lay-Up & Binder: Material & Structural Execution: Concentric four-core lay-up with shaped fillers + polyester (PET) binder tape | Engineering Role in Data Centre VFD Circuits: Preserves a round, stable core bed so heavy conduit pulling does not deform screen geometry
  • 4. First EMC Screen: Material & Structural Execution: Aluminium-laminated polyester foil wrapped metal-side-out (100% coverage) | Engineering Role in Data Centre VFD Circuits: Maintains continuous circumferential contact with the outer copper braid to block MHz-band radiated noise
  • 5. Second EMC Screen (C): Material & Structural Execution: High-coverage tinned copper wire braid (>= 80-85% optical density) | Engineering Role in Data Centre VFD Circuits: Provides a low-inductance high-current fault and common-mode return path resistant to humid-air oxidation
  • 6. Outer Sheath (YK): Material & Structural Execution: Special black RAL 9005 PVC (UV, oil, and weather resistant; IEC 60332-1-2) | Engineering Role in Data Centre VFD Circuits: Protects the screen during long tube pulls (-40 °C to +70 °C fixed; cadmium- and silicone-free RoHS)

Visual FAT Evidence: 49.12 mm Tube-Fit OD and Foil Check

The buyer stressed that the cable could not run oversized or undersized because crews pull it inside pre-laid tubes. If 4x120 mm² swells past 53 mm, it jams in conduit bends or misses M63 EMC glands (42 mm to 52 mm clamping range). An undersized jacket also fails to seal inside gland rings.

TEBAOFLEX pre-shipment verification showing digital caliper outer diameter check at 49.12 mm on the left and dissected 2YSLCYK-J 4x120 mm² layers with metal-side-out aluminium-laminated foil and PE core rings on the right

Our quality desk sent two clear inspection photos from the finished batch.

  • Digital Caliper Diameter Check (49.12 mm). Actual outer diameter measured 49.12 mm, sitting cleanly within the 51.9 mm design ceiling and M63 EMC gland clamping range.
  • Dissected Foil and Core Check. Stripping a sample exposed the white-backed, metal-side-out aluminium-laminated foil, the four colour-coded PE rings, and the black RAL 9005 sheath (4Cx120MMSQ 600/1000V DIN VDE Standard 2026).

Selecting TEBAOFLEX 0.6/1 kV VFD Motor Cables

For drives above 75 kW, engineers also weigh 4-core (4G) against symmetrical 3+3 split-earth layouts. Compare both in our guides on symmetrical 3+3 ground versus 4-core VFD motor cables and 360 degree EMC cable gland termination and surface transfer impedance.

  • 2YSLCY-J / 2YSLCYK-J PE Double-Screened VFD Cable: Core & Earth Topology: 4G (1.5-240 mm²) or symmetrical 3 + 3G | Insulation & Thermal Limit: Low-capacitance PE (2Y), +70 °C continuous (160 °C SC) | Best-Fit Industrial / Data Centre Duty: Long inverter-to-motor runs needing lowest dielectric capacitance (2YSLCYK-J black UV/duct sheath)
  • 2XSLCYK-J XLPE Double-Screened VFD Cable: Core & Earth Topology: 4G or symmetrical 3 + 3G (1.5-240 mm²) | Insulation & Thermal Limit: Cross-linked XLPE (2X), +90 °C continuous (250 °C SC) | Best-Fit Industrial / Data Centre Duty: High-ambient plant rooms and compact conduits needing higher ampacity per mm²
  • Low-Capacitance Double-Screened JB VFD Cable: Core & Earth Topology: Multi-core colour-coded Class 5 flexible | Insulation & Thermal Limit: Low-capacitance polyolefin/XLPE + dual foil/braid | Best-Fit Industrial / Data Centre Duty: Automated machine tools, conveyors, and compact cabinet drives
  • Type 29513 1,000 V Double-Shielded VFD Cable: Core & Earth Topology: AWG / kcmil heavy-duty industrial VFD build | Insulation & Thermal Limit: 90 °C cross-linked thermoset + foil/braid (1,000 V UL/CSA style) | Best-Fit Industrial / Data Centre Duty: North American / UL-governed industrial chiller, pump, and compressor skids

For 12/20 kV distribution rings in the same city, see our companion 12/20(24) kV (N)TMCGCW11Y 1x120/16 mm² Singapore data centre medium-voltage cable case study.

4. Export Drums, Tube-Pulling Limits, and Singapore Delivery

At a unit weight of 5,556.8 kg/km (5.56 kg/m), 4x120 mm² VFD cable puts heavy load on shipping reels. Thin plywood drums easily split during port crane lifts.

Heavy-duty steel-spoked ISPM 15 heat-treated wooden export cable drum built by TEBAOFLEX to carry 4x120 mm² 2YSLCYK-J VFD power cable to Singapore

From Shanghai port loading to Port of Singapore arrival, our logistics team applied four controls.

  1. Steel-Spoked ISPM 15 Export Drums. We wound the 4x120 mm² cable onto thick hardwood drums reinforced with welded steel hub rings and channel spokes, stamped with ISPM 15 heat-treatment marks for Singapore customs.
  2. Sealed Ends and Full Batten Lagging. Both cable ends were sealed against tropical humidity and strapped inside the flange. Full wooden batten lagging protected the reel inside the 40HC container.
  3. Tube-Pulling Force and Bend Radius. Across 480 mm² total copper (4 x 120 mm²), maximum copper pulling tension is 9.6 kN (20 N/mm²). Fixed conduit bend radius must stay at or above 10 x OD (~500 mm).
  4. 360 degree circumferential EMC gland bonding is a termination method that clamps both the foil and tinned copper braid evenly inside a metal gland cone at the drive and motor ends. It avoids twisted "pigtail" ground leads that leak high-frequency noise.

5. Pre-Order Checklist for Data Centre VFD Cable Buyers

Before ordering 0.6/1 kV 2YSLCYK-J or 2XSLCYK-J cables (35 mm² to 240 mm²), verify five details.

  1. Lock outer-diameter limits against site tubes. Confirm nominal and actual OD (mm) so pre-laid tubes and 360 degree EMC glands fit cleanly.
  2. Check 70 °C PE versus 90 °C XLPE tube derating. Apply conduit and grouping factors (DIN VDE 0298-4) to the 292 A (4x120 mm²) free-air rating.
  3. Review 4G versus 3+3G symmetry above 90 kW. Confirm whether your inverter manual accepts 4x120 mm² (4G) or calls for 3x120 + 3G16 split-earth cores.
  4. Verify metal-side-out foil plus tinned braid. Request stripped sample photos showing the aluminium foil side touching the tinned copper braid (>= 80% cover).
  5. Confirm steel-spoked ISPM 15 drum weights. Match gross drum mass to site forklift and loading-bay limits whenever cable mass exceeds 4,000 kg/km.

Image credits: Rooftop cooling plant photo "Data center roof.jpg" by Rsparks3 via Wikimedia Commons (CC0 1.0); cooling pump bay photo "Closed cooling water system pumps and its pipe connections.jpg" by Harald the Bard via Wikimedia Commons (CC BY-SA 4.0); 2YSLCYK-J 4x120 mm² cross-section, digital caliper OD check, dissected foil proof, and steel-reinforced ISPM 15 drum photos by TEBAOFLEX.

Frequently Asked Questions

What does the designation 2YSLCYK-J 0.6/1 kV mean on a VFD motor cable?

In DIN VDE 0250 / 0207 coding, 2Y means low-permittivity polyethylene (PE) insulation, and SL marks a flexible drive lay-up. C denotes a concentric tinned copper braid screen over 100% aluminium foil, YK indicates a black (RAL 9005) UV-resistant PVC sheath, and -J confirms a green-yellow earth core.

Why is PE insulation (2Y) preferred over standard PVC on long VFD motor runs?

Polyethylene (2Y) has a dielectric constant near 2.3 versus 4.0 to 5.0 for PVC. Lower mutual capacitance cuts PWM charging current spikes (I = C dV/dt) by roughly 45% (DIN VDE 0207, 2021). That lowers inverter heat, stops nuisance overcurrent trips, and limits motor voltage stress.

How should installers terminate the double screen on a 2YSLCYK-J 4x120 mm² cable?

Installers should fit 360 degree conductive EMC compression glands (M63 size for 49.12 mm OD) at both the inverter cabinet and motor box. Twisting the copper braid into a long single-wire pigtail adds inductance that blocks MHz noise from returning to the drive DC bus.

Is Class 5 flexible 2YSLCYK-J cable suitable for continuous drag-chain movement?

No. IEC 60228 Class 5 copper makes 2YSLCYK-J 4x120 mm² easy to bend into cabinet plinths and motor boxes (10 x OD fixed; 20 x OD occasional flex). Continuous drag-chain motion requires a dedicated PUR-sheathed chain-flex VFD cable.

How did TEBAOFLEX verify conduit compatibility before shipping the 4x120 mm² cable to Singapore?

Before drum lagging, our quality team checked outer diameter with a digital caliper (49.12 mm actual within the 51.9 mm ceiling). We also stripped samples to prove metal-side-out aluminium foil and copper braid coverage, ran 4 kV / 5 min AC tests, and sent full photo proof for buyer approval.

Closed-loop industrial cooling water centrifugal pump and motor bay typical of high-capacity data centre chilled-water plants fed by VFD cables
TEBAOFLEX 0.6/1 kV 2YSLCYK-J 4x120 mm² double-screened VFD motor cable cross-section showing four Class 5 fine-stranded copper cores, colour-coded PE insulation, Al-PET foil, tinned copper braid, and black RAL 9005 PVC sheath
TEBAOFLEX pre-shipment verification showing digital caliper outer diameter check at 49.12 mm and dissected 2YSLCYK-J 4x120 mm² layers with metal-side-out aluminium-laminated foil
Heavy-duty steel-spoked ISPM 15 heat-treated wooden export cable drum built by TEBAOFLEX to carry 4x120 mm² 2YSLCYK-J VFD power cable to Singapore

Specify it