A 6.6 kV equipment nameplate does not, by itself, determine the correct trailing cable grade. A request that says 3.6/6 kV in one document and 6/10 kV in another needs a technical review before ordering. Check the highest system voltage, earth-fault behaviour, applicable cable standard, equipment interface and mechanical duty with the project engineer and cable manufacturer.
What U0/U(Um) tells you
U0 is the rated power-frequency voltage between a conductor and earth or metallic screen; U is the rated voltage between conductors. Um identifies the highest system voltage for which the cable is designed. These are cable designations, so do not assume that U and the system nameplate voltage must be identical.
For example, a mining cable catalogue lists 3.6/6 (7.2) kV and 6/10 (12) kV constructions. The value in parentheses is important when comparing the cable with the highest system voltage, but it does not by itself approve the cable for a particular fault duty or machine. Other standards may use different designations.
In a balanced 6.6 kV three-phase system with the neutral at earth potential, the phase-to-earth voltage is approximately 6.6 / √3 ≈ 3.81 kV. This calculation does not describe every unearthed system or earth-fault condition.
A hypothetical +10% applied to 6.6 kV gives 7.26 kV, not 7.2 kV. This is arithmetic, not an assumed system tolerance or equipment approval. Obtain the specified highest system voltage and compare it with the actual cable and accessory ratings.
Earth faults and insulation selection
During an earth fault, the voltage from a healthy phase to earth can increase; the magnitude and duration depend on the network and protection. Establish the earthing arrangement, protection settings, fault-clearing time per event, cumulative fault exposure and whether continued operation during a fault is permitted.
Do not assign a fault category or require a single cable grade solely because the neutral is earthed, isolated or resonant-earthed. The project engineer must assess the actual system and specify the required insulation and accessories under the standards that apply to that installation.
Use the right standard for the application
IEC 60502-2 addresses extruded power cables for fixed installations and excludes special applications such as mining cables. Its voltage terminology can be useful for comparison, but it does not establish that a mobile mining cable complies. DIN VDE 0250-813 addresses trailing cable; confirm the specified edition, product documentation and local requirements for the project.
Check cable construction and machine fit

The illustration is representative, not an approved construction drawing. Confirm the actual power, protective-earth and any pilot conductors, screens and terminations for the cable being ordered. A cable for trailing duty and one for powered reeling can have different mechanical requirements even when their voltage ratings match.
A higher insulation grade can change cable diameter, weight and reel capacity, but the change is not a fixed amount. Compare the manufacturer’s drawings for the exact core sizes and designs. IEC 60228 Class 5 describes flexible conductors; it does not by itself set the working tension for the whole cable.
For a quotation, provide the following information:
- The system nominal and highest voltage, earthing arrangement and earth-fault protection requirements.
- The applicable cable standard, required voltage designation and equipment manufacturer’s approved specification.
- Power and protective-earth conductor sizes, screening and any pilot or monitoring circuits.
- Cable length, duty cycle, route, minimum bend radius, permitted tensile load and drum or guide dimensions.
- Connector and gland part numbers, acceptable cable diameter range, environmental exposure and acceptance-test requirements.
Request the right test evidence
Ask for the applicable product test report and certificate, including the test method, voltage, duration and acceptance criteria. Where partial-discharge testing is specified, agree the test conditions and sensitivity for the actual cable. A passing test reports performance under its stated conditions; it does not prove that the insulation has no voids or will never age.
Frequently asked questions
Can 3.6/6 (7.2) kV cable be used on a 6.6 kV system?
It may be appropriate for some installations, but the designation alone is not approval. Verify the highest system voltage, fault exposure, applicable standard, accessories and manufacturer’s limits for the actual project.
Is 6/10 kV always required for an unearthed system?
No single grade applies to every system. The required insulation depends on the fault conditions and the governing cable and installation requirements; have the project engineer confirm the specified grade.
Does a higher voltage grade always add 4–7 mm to the diameter?
No. Diameter depends on the complete construction, conductor sizes and manufacturing tolerances. Compare drawings for the specific cables and check the connector and reel before ordering.
Does a passing withstand or partial-discharge test prove the cable is suitable?
No. Test results are evidence for the stated test conditions. Suitability also depends on the system, mechanical duty, accessories, approvals and installation requirements.
References and related products
DIN VDE 0250-813: trailing cable standard
IEC 60502-2: scope for fixed power cables
IEC 60885-3: partial-discharge measurement methods
IEC 60228: conductors of insulated cables
BS 6708: flexible trailing cables and rated voltage classes for mines and quarries