Mine roadway & tunnel wall hangers
Primary duty — HV roadway suspension feeding moving longwall district substations.
Product
BS 6708 Type 621 3,800/6,600 V (15 kV AC test) pliable-armoured power supply cable with four equal Class 5 tinned copper cores (3 phase + 1 pilot/earth), 5.0 mm EPR insulation, pliable steel wire armour and PCP sheath.
Typical values for this cable type, based on BS 6708 · IEC 60228 Class 5 — confirmed in the datasheet and quotation for your order.
Application fit
6.35/11 kV and 3.8/6.6 kV pliable wire-armoured underground mine roadway feeder cable to BS 6708 Type 621 for district transformers and pantechnicons.
Primary duty — HV roadway suspension feeding moving longwall district substations.
Armoured HV distribution in mine drifts, tunnels and underground pump stations.
Pliable wire armour allows periodic handling and extension as the face advances.
Pliable wire armour is not rated for continuous motorised reeling drums.
Use (N)TSCGEWÖU MV ReelHV roadway feeder — cannot be flexed inside coal-face Bretby handlers.
Use BS 6708 Type 307Construction
Four equal-cross-section IEC 60228 Class 5 flexible tinned copper conductors (3 phase cores + 1 pilot/earth core, 35 to 150 mm²) insulated with 5.0 mm nominal EPR are laid up in contact with each other inside a 3.8–5.0 mm rubber inner bedding sheath, armoured with 7/0.90 mm or 7/1.25 mm stranded galvanised steel pliable wire armour and sheathed overall with 6.0–8.3 mm heavy-duty chloroprene (PCP).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Phase & pilot/earth conductors (4) | Electrolytic stranded tinned copper wire, IEC 60228 Class 5 (4×35 to 4×150 mm²)IEC 60228 Class 5 |
| 2 | Medium-voltage EPR insulation | Ethylene propylene rubber (EPR, 5.0 mm nominal radial wall on all sizes, 15 kV AC routine test)BS 6708 (3.8/6.6 kV) |
| 3 | Rubber bedding & inner sheath | Rubber-based inner sheath compound (3.8 mm on 4×35 mm²; 5.0 mm on 4×50–4×150 mm²)BS 6708 |
| 4 | Pliable galvanised steel wire armour | Stranded galvanised steel pliable armour (7/0.90 mm on 4×35 mm²; 7/1.25 mm on 4×50–4×150 mm², 0.35–0.70 Ω/km)BS 6708 |
| 5 | Heavy-duty chloroprene outer sheath | Heavy-duty flame-retardant polychloroprene (chloroprene / PCP, 6.0 to 8.3 mm radial thickness)BS 6708 |
3 unscreened phase cores + 1 unscreened pilot/earth core + pliable galvanised steel wire armour
For 3,800/6,600 V pliable-armoured cables with individually copper/nylon braided-screened phase cores, specify Type 630 or Type 631
Technical data
Sizes
Complete core, dimensional, mechanical and electrical schedule per BS 6708.
| Designation 4 Cores | Core CSA mm² | Stranding n/mm | Cond. Ø mm | EPR wall mm | Inner wall mm | Inner min Ø mm | Inner max Ø mm | Armour n/mm | Outer wall mm | Min. OD mm | Max. OD mm | Min. bend mm | Current 25 °C A | Cond. DC 20 °C Ω/km | Armour DC 20 °C Ω/km | Cu mass kg/km | Mass ≈ kg/km | Enquiry |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Type 621 · 4 × 35 mm² | 35 | 276/0.40 | 8.40 | 5.0 | 3.8 | 53.8 | 56.8 | 7/0.90 | 6.0 | 71.2 | 75.2 | 752 | 135 | 0.565 | 0.70 | 1,350 | 8,900 | |
| Type 621 · 4 × 50 mm² | 50 | 396/0.40 | 10.10 | 5.0 | 5.0 | 60.5 | 63.5 | 7/1.25 | 6.3 | 81.0 | 85.3 | 853 | 170 | 0.393 | 0.50 | 1,950 | 11,100 | |
| Type 621 · 4 × 70 mm² | 70 | 360/0.50 | 11.90 | 5.0 | 5.0 | 65.6 | 69.4 | 7/1.25 | 7.0 | 87.1 | 91.4 | 914 | 205 | 0.277 | 0.43 | 2,700 | 13,000 | |
| Type 621 · 4 × 95 mm² | 95 | 475/0.50 | 13.90 | 5.0 | 5.0 | 70.7 | 74.5 | 7/1.25 | 7.5 | 93.2 | 97.5 | 975 | 250 | 0.210 | 0.39 | 3,700 | 14,050 | |
| Type 621 · 4 × 120 mm² | 120 | 608/0.50 | 15.50 | 5.0 | 5.0 | 74.3 | 78.1 | 7/1.25 | 7.8 | 97.4 | 101.7 | 1,017 | 295 | 0.164 | 0.38 | 4,650 | 20,600 | |
| Type 621 · 4 × 150 mm² | 150 | 756/0.50 | 17.20 | 5.0 | 5.0 | 79.2 | 83.2 | 7/1.25 | 8.3 | 103.3 | 107.6 | 1,076 | 320 | 0.132 | 0.35 | 5,800 | 22,000 |
Reel check
A first screen using datasheet values. Engineering confirms drum geometry, acceleration and tension with your quotation.
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 15 kV AC high-voltage dielectric test | 15 kV AC routine voltage withstand test on 3,800/6,600 V 5.0 mm EPR cores per BS 6708 | Every shipping drum |
| Conductor & pliable armour DC resistance | Max. 0.565 to 0.132 Ω/km on Class 5 tinned copper cores; 0.70 to 0.35 Ω/km on pliable GSW armour at 20 °C | Every shipping drum |
| Sample tests | ||
| Chloroprene sheath flame, oil & mechanical test | Heavy-duty PCP outer sheath tested for deep underground and surface mining service per BS 6708 | Production batch |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.