EN 50525-2-21 H07RN8-F 4G10 + 2x1.5 mm2 Potable-Water Submersible Pump Cable: Hybrid Sensor Cores, AD8 Hygiene and 4K QC Video

Inside our EN 50525-2-21 AD8 H07RN8-F 4G10+2x1.5 mm2 potable-water submersible pump cable: Class 5 copper, EPR cores, PTC sensor leads, and 4K factory QC.

TEBAOFLEX JyenOperations & Technical EngineerDuration 0:48
Featured product
H07RN8-F Submersible Rubber Cable
Category
Product video
Duration
0:48
Published
In this article19 sections
  1. 01What the video shows
  2. 02Municipal Clearwell and Reservoir Riser Duty: Why Standard Black H07RN8-F Fails in Drinking Water
  3. Decoding the Verified Sheath Legend and Blue Potable Identification
  4. 03How Do Valley-Seated 2x1.5 mm2 Sensor Cores Prevent Pump Hood Gland Leaks and Voltage Drop?
  5. Worked Calculation: 400 V Riser Voltage Drop, PTC Loop Impedance, and 15 N/mm2 Tensile Clamping
  6. 04Inside the Three-Layer H07RN8-F 4G10 + 2x1.5 mm2 Architecture and Potable-Water Cable Selection
  7. Dimensional and Electrical Comparison: Plain 4G10 vs Hybrid 4G10 + 2x1.5 mm2
  8. Submersible Pump Cable Selection Matrix Across Potable, VFD, Deep-Well and Sewage Duty
  9. 054K Extrusion Traction, Macro Cross-Section Inspection and Six-Point Submersible FAT Protocol
  10. Scene-by-Scene Walkthrough of the 48-Second Field & 4K Factory Video
  11. Six-Point Factory Acceptance Testing (FAT) Protocol Before Drum Dispatch
  12. 06Potable-Water Submersible Pump Cable Procurement Checklist
  13. 07Frequently Asked Questions
  14. Can standard black H07RN8-F cable be used in drinking-water wells or potable reservoirs?
  15. Why integrate 2x1.5 mm2 control cores into 4G10 instead of running a separate sensor cable?
  16. What cable gland or pump grommet size fits H07RN8-F 4G10 + 2x1.5 mm2?
  17. How deep can H07RN8-F 4G10 + 2x1.5 mm2 be submerged without clamping or armour?
  18. When must a VFD-driven submersible pump switch from unscreened 4G10 + 2x1.5 to a screened hybrid cable?
  19. 08Request a Potable-Water H07RN8-F Cut Specimen or Project Quote

What the video shows

48.0 second municipal clearwell operation, dual-belt caterpillar haul-off extrusion, and 4K 1:1 cross-section verification video of our EN 50525-2-21 AD8 H07RN8-F 4G10 + 2x1.5 mm2 potable-water submersible pump cable.

The video illustrates a sample, process, or operating context. Final product construction, suitability, standards, and test acceptance criteria are confirmed against the ordered specification.

TL;DR: H07RN8-F 4G10 + 2x1.5 mm2 (450/750 V, AD8) is a potable-water-grade hybrid submersible pump power and monitoring cable built to EN 50525-2-21 (DIN VDE 0285-525-2-21) and IEC 60364-5-51 Class AD8 (CENELEC, 2011; IEC, 2005). It combines four 10 mm2 Class 5 flexible copper power cores (L1, L2, L3, PE in cross-linked EPR) with two 1.5 mm2 valley-seated control cores inside a non-toxic sky-blue potable-water elastomer sheath. Integrating thermal (PTC) and seal-leakage (FLS) leads into one circular outer profile eliminates a second pump-hood gland and prevents organoleptic or chemical leaching in municipal drinking-water reservoirs. Our 48.0 s (PT48S) field and 4K factory video documents reservoir booster operation, caterpillar haul-off extrusion, and 1:1 cross-section verification.
Engineering ParameterVerified Specimen & Video Specification (H07RN8-F 4G10 + 2x1.5 mm2)Governing Standard / ReferenceMunicipal Drinking-Water Function
Base Designation & VoltageH07RN8-F hybrid 4G10 + 2x1.5 mm2, U0/U = 450/750 V (0.6/1 kV fixed protected)EN 50525-2-21 / HD 22.4Powers 15 kW to 22 kW (400 V) submersible reservoir and clearwell pumps
Power Conductors (Layer 01)4 x 10 mm2 (~8 AWG) fine-stranded bare copper (Class 5, <= 1.91 Ohm/km at 20 °C)IEC 60228:2023 & HD 308 S2Brown, Black, Grey phases + Green/Yellow protective earth (52 A to 61 A)
Sensor Conductors (Layer 02)2 x 1.5 mm2 (~16 AWG) Class 5 bare copper (<= 13.3 Ohm/km at 20 °C) in outer valleysIEC 60228:2023 & DIN 44081Carries stator PTC thermistor or mechanical oil-chamber moisture probe signals
Core InsulationCross-linked water-resistant ethylene-propylene elastomer (EPR, EI4 / 3GI3)EN 50363-1 (2.5 kV AC test)Maintains wet dielectric resistance under continuous AD8 hydrostatic pressure
Outer Sheath (Layer 03)High-density sky-blue non-toxic potable-water elastomer (OD 21.7 mm to 23.6 mm)IEC 60364-5-51 AD8 + BS 6920 / KTWZero taste, odor, chloramine swelling, or microbial biofilm promotion in clean water
Mechanical & Thermal LimitsWater temp up to +40 °C (EN 50525-2-21); 4 x OD fixed / 6 x OD flexing bend; 600 N max Cu pullDIN VDE 0298-3 (15 N/mm2 Cu)Suspends cleanly along AISI 316 column risers with clamps every 2 m to 3 m

Municipal Clearwell and Reservoir Riser Duty: Why Standard Black H07RN8-F Fails in Drinking Water

Potable-water H07RN8-F hybrid submersible cable is a continuous-immersion (AD8) flexible rubber feeder built on CENELEC EN 50525-2-21 mechanics while replacing black chloroprene (EM2) with a non-toxic blue compound. Under European harmonized coding, H marks a harmonized type, 07 denotes a 450/750 V rating, and R specifies ethylene-propylene rubber (EPR) insulation. Meanwhile, N8 designates a heavy submersible elastomer sheath, and -F identifies IEC 60228 Class 5 flexible copper.

In the opening field sequence of our 48.0 s video (00:00 to 00:16), vertical booster pumps feed treated municipal water from lakeside storage tanks into an indoor clearwell hall. Welded AISI 316 gauges confirm steady sanitary discharge at 24 psi (1.65 bar). Specifying a standard black wastewater H07RN8-F Submersible Rubber Cable in these potable basins causes three immediate failures.

  1. Organoleptic and Chemical Migration into Treated Water. Conventional black EM2 polychloroprene compounds contain sulfur-modified accelerators, aromatic processing oils, polycyclic aromatic hydrocarbons (PAHs), and carbon-black fillers. In raw sewage or quarry dewatering pits, trace extractables do not matter. Inside municipal clearwells, desalination permeate tanks, or food-grade boreholes, those curing residues leach phenolic odors, bitter taste, and total organic carbon (TOC). Such extractables fail WRAS / BS 6920 Material Audits, German UBA KTW-BWGL Guidelines, and NSF/ANSI/CAN 61 Health Effects Testing.
  2. Microbial Biofilm Growth (DVGW W270 / BS 6920 Part 2.4). Plasticizers and low-molecular-weight waxes migrating out of general-purpose rubber sheaths act as a carbon nutrient source for Pseudomonas aeruginosa and Legionella colonies. Potable-water sky-blue cross-linked elastomers (EPDM / EPR drinking-water formulations) eliminate assimilable organic carbon so residual free chlorine (0.2 mg/L to 2.0 mg/L) stays effective.
  3. Harmonized 10 m Depth Ceiling vs Deep Clearwell Submergence. Baseline EN 50525-2-21 Annex B qualifies standard H07RN8-F for AD8 immersion to 10 m depth at water temperatures up to +40 °C. Municipal intake shafts, aquifer wells, and high-head clearwells frequently submerge pump hoods 30 m to 150 m (3 bar to 15 bar hydrostatic head). Deep potable risers therefore require high-density low-uptake compounds such as our Round Drinking Water Pump Cable and AD8 Submersible Rubber Pump Cable.
Municipal drinking-water clarification and filtration basins where submerged transfer and clearwell booster pumps require non-toxic AD8 potable-water cables

Decoding the Verified Sheath Legend and Blue Potable Identification

Across municipal water utilities in Europe, Latin America, and the Middle East, a sky-blue (RAL 5012 / RAL 5015) outer sheath serves as an instant visual quarantine marker. Maintenance crews never accidentally lower a sewage-contaminated black pump lead into a sanitary clearwell. Along the extruded blue outer jacket shown in our video (00:00 to 00:06 and 00:26 to 00:36), the identification legend reads as follows.

TEBAOFLEX H07RN8-F 4x10+2x1.5 450/750V AD8 EN 50525-2-21 [Potable-Water Grade]

In procurement specs, engineers write either 4G10 + 2x1.5 mm2 or 4x10 + 2x1.5 mm2. Under EN 50525-1, the letter G confirms that one 10 mm2 core is Green/Yellow protective earth (Brown, Black, Grey, Green/Yellow), matching 3P + PE motor terminals directly.

How Do Valley-Seated 2x1.5 mm2 Sensor Cores Prevent Pump Hood Gland Leaks and Voltage Drop?

A hybrid submersible pump power and monitoring cable is a single-sheath composite feeder that seats auxiliary control conductors (1.0 mm2 to 2.5 mm2) inside the outer valleys of three-phase power cores. Combining 4 x 10 mm2 motor leads and 2 x 1.5 mm2 sensor leads under one circular AD8 jacket eliminates the second parallel control cable. As a result, submerged gland penetrations drop by half and tie-wrap snag hazards disappear inside narrow riser columns.

On 15 kW to 22 kW municipal submersible pumps, warranty clauses normally require active monitoring of two internal protection devices.

  • Stator Winding Thermal Switches (PTC Thermistors per DIN 44081 or Bi-Metal Klixon Cutouts). Embedded in the stator end-windings, these sensors trip the surface contactor if impeller clogging raises winding temperature past 130 °C to 150 °C.
  • Mechanical Seal Oil-Chamber Moisture Probes (FLS / CLS Conductive Electrodes). Mounted between the silicon-carbide lower seal and motor housing, these electrodes trigger an early alarm if water breaches the outer shaft seal.

Running two separate cables (4G10 power plus 2x1.5 control) down a vertical riser introduces severe mechanical risk. Differential elongation under pump starting torque twists the thin 2x1.5 mm2 cord around the main cable, abrading its jacket against flange bolts and doubling hood leak paths. Seating both 1.5 mm2 EPR cores symmetrically inside opposite valleys of our Submersible Pump Power and Monitoring Hybrid Cable shields the thin copper strands within the 10 mm2 lay-up pitch. At the pump hood, one smooth circular OD (21.7 mm to 23.6 mm) seals cleanly inside a single vulcanized grommet.

Indoor municipal drinking-water treatment plant vertical riser gallery with flanged discharge headers and sanitary pressure gauges fed by submersible pump risers

Worked Calculation: 400 V Riser Voltage Drop, PTC Loop Impedance, and 15 N/mm2 Tensile Clamping

Submersible pump risers cross two thermal zones: a water-cooled lower zone (<= 40 °C water) and an air-filled upper riser (30 °C to 45 °C ambient). Under IEC 60228:2023, 10 mm2 Class 5 plain copper has a maximum 20 °C DC resistance of R20 = 1.91 Ohm/km. Applying the copper temperature coefficient (alpha = 0.00393 /K) gives the operating resistances at 60 °C submerged and 80 °C dry-gallery temperatures.

R60 (submerged zone) = 1.91 x [1 + 0.00393 x (60 - 20)] = 2.210 Ohm/km | R80 (dry header zone) = 1.91 x [1 + 0.00393 x (80 - 20)] = 2.360 Ohm/km

Consider a 22 kW (30 HP), 400 V, 50 Hz submersible clearwell pump drawing I = 41.5 A at cos phi = 0.85 (sin phi = 0.527, reactance X = 0.085 Ohm/km). Across an L = 65 m (0.065 km) feeder (50 m submerged plus 15 m dry gallery, weighted R_eff = 2.245 Ohm/km), three-phase line drop is calculated below.

Delta U = sqrt(3) x 41.5 A x 0.065 km x (2.245 x 0.85 + 0.085 x 0.527) | = 4.672 x (1.908 + 0.045) = 9.12 V (2.28% of 400 V)

A 2.28% steady-state drop stays well inside the 3.0% (12.0 V) motor feeder limit of IEC 60364-5-52 Low-Voltage Installation Standards. Even under a 6 x In (249 A) direct-on-line starting surge, transient dip remains 13.7%, safely below the 15% contactor dropout threshold (IEC, 2009). Meanwhile, the 2 x 1.5 mm2 Class 5 sensor pair (R20 <= 13.3 Ohm/km, or 14.35 Ohm/km at 40 °C) adds only 1.87 Ohm across the 130 m round-trip loop. That low loop resistance introduces zero offset error into a DIN 44081 PTC string (150 Ohm to 750 Ohm normal, > 4,000 Ohm trip).

For vertical suspension, DIN VDE 0298-3 limits permanent static tensile stress on flexible copper power cores to 15 N/mm2 (excluding the 2 x 1.5 mm2 sensor leads).

Maximum allowable static pull F_max = 4 x 10 mm2 x 15 N/mm2 = 600 N (~61.2 kgf)

Finished H07RN8-F 4G10 + 2x1.5 mm2 weighs approximately 910 kg/km (0.91 kg/m in air, or ~0.49 kg/m net submerged weight in freshwater). Consequently, an unclamped vertical drop exceeding 65 m in air approaches the 600 N copper yield boundary even before pump-discharge vibration is added. Always suspend the pump from an AISI 316 stainless lifting chain and clamp the cable to the riser pipe every 2.0 m to 3.0 m with EPDM-lined stainless clamps.

Inside the Three-Layer H07RN8-F 4G10 + 2x1.5 mm2 Architecture and Potable-Water Cable Selection

In the 4K macro cross-section and 3D structural breakdown of our video (00:22 to 00:42), every radial component of H07RN8-F 4G10 + 2x1.5 mm2 preserves circularity under AD8 gland compression.

  • Component 01: 4 x 10 mm2 Class 5 Flexible Bare Copper Power Cores (EPR Insulated). Fine-stranded annealed bare copper (IEC 60228 Class 5, strand diameter <= 0.41 mm) carries cross-linked water-resistant EPR insulation (EI4 / 3GI3, wall 1.0 mm to 1.2 mm). Cores follow HD 308 S2 colors in Green/Yellow (PE), Brown (L1), Black (L2), and Grey (L3). A central non-hygroscopic rubber filler blocks axial capillary water wicking if a termination is nicked.
  • Component 02: 2 x 1.5 mm2 Valley-Seated Control & Thermal Sensor Cores. Two IEC 60228 Class 5 flexible bare copper conductors (strand <= 0.26 mm) use heavy-wall black cross-linked EPR insulation (~0.8 mm wall). Nesting both 1.5 mm2 cores inside opposite outer valleys between the 10 mm2 power cores adds near-zero extra diameter compared with plain 4G10.
  • Component 03: High-Density Sky-Blue Potable-Water AD8 Elastomer Outer Sheath. Pressure-extruded, peroxide-cured non-toxic cross-linked elastomer (wall ~3.6 mm, finished OD 21.7 mm to 23.6 mm) prevents taste or odor migration in clean water. Its high-durometer circular profile resists free chlorine and seals tightly inside M32 x 1.5 or OEM pump grommets.
4K macro razor-cut cross-section of TEBAOFLEX H07RN8-F 4G10 + 2x1.5 mm2 potable-water submersible pump cable showing four 10 mm2 Class 5 copper EPR cores, two valley-seated 1.5 mm2 sensor cores, and sky-blue AD8 sheath

Dimensional and Electrical Comparison: Plain 4G10 vs Hybrid 4G10 + 2x1.5 mm2

Valley-seating the 2 x 1.5 mm2 control cores keeps the finished outer diameter inside the exact same M32 compression-gland envelope as plain 4G10 H07RN8-F.

Construction SizeConductor Layout (IEC 60228 Class 5)Nominal Overall OD (mm)Copper Mass (kg/km)Approx. Net Cable Weight (kg/km)Max 20 °C DC Resistance (Ohm/km)Current Rating in 30 °C Air (60 °C EN / 90 °C VDE)Recommended Metric Gland (AD8 / IP68)
4G6 + 2x1.54 x 6 mm2 + 2 x 1.5 mm218.5 - 20.2~259~6403.30 / 13.339 A / 46 AM25 x 1.5 (13-20 mm seal) or M32
4G10 (Plain)4 x 10 mm2 (no sensor leads)20.9 - 23.4~384~8531.91 (power)52 A / 61 AM32 x 1.5 (18-25 mm seal)
4G10 + 2x1.5 (Video)4 x 10 mm2 + 2 x 1.5 mm221.7 - 23.6~413~9101.91 / 13.352 A / 61 AM32 x 1.5 (18-25 mm IP68 10 bar)
4G16 + 2x1.54 x 16 mm2 + 2 x 1.5 mm224.6 - 26.8~643~1,2101.21 / 13.369 A / 82 AM32 x 1.5 (wide) or M40 x 1.5 (22-32 mm)
4G25 + 2x1.54 x 25 mm2 + 2 x 1.5 mm229.2 - 31.8~989~1,7400.780 / 13.392 A / 108 AM40 x 1.5 (22-32 mm IP68 10 bar)
In-plant 4K dual-belt caterpillar haul-off traction of sky-blue potable-water H07RN8-F outer sheath paired with 1:1 cut specimen on TEBAOFLEX inspection mat

Submersible Pump Cable Selection Matrix Across Potable, VFD, Deep-Well and Sewage Duty

Not every submerged pump installation belongs on unscreened 450/750 V round H07RN8-F. When variable-frequency drives (VFDs), narrow 100 mm (4 in) boreholes, or abrasive mine sumps enter the spec, cross-check our TEBAOFLEX Rubber Cable Portfolio against the selection matrix below.

TEBAOFLEX Submersible SeriesVoltage & StandardSheath & Hygiene / ScreenMax Depth / Duty BoundaryPrimary Target Application
Potable-Water Hybrid H07RN8-F (Featured)450/750 V (0.6/1 kV fixed), EN 50525-2-21 AD8Sky-blue non-toxic potable elastomer (BS 6920 / KTW / W270 compound)10 m harmonized (up to 150 m with high-density potable AD8 compound)Municipal clearwells, drinking-water reservoirs, and PTC-monitored clean-water boosters
Round Drinking Water Pump Cable (0.6/1 kV)0.6/1 kV, KTW / W270 / WRAS / ACSBlue low-migration XLPO / EPDM potable sheath (3-core, 4-core, 5-core)Deep aquifer wells up to 250 m to 500 m continuous potable immersionDeep potable boreholes and municipal wellfield submersible turbines without hybrid pilot pairs
**450/750V Flat Drinking Water Pump Cable**450/750 V / 0.6/1 kV flat profileParallel flat blue potable elastomer (low radial thickness)Tight annular clearance (< 8 mm gap) between pump shell and well casingSlim 100 mm (4 in) and 150 mm (6 in) cased deep drinking-water wells
**Submersible Pump VFD Power & Screened Monitoring Cable**0.6/1 kV, EN 50525 / VDE 0250 EMCIndividual screened control pairs + overall tinned copper braid (>= 85%)PWM inverter drives (dV/dt bearing-current & PTC noise immunity)VFD-driven booster stations and municipal variable-speed intake pumps
Standard Black H07RN8-F Submersible Cable450/750 V, EN 50525-2-21 AD8Black heavy polychloroprene (EM2) oil/sewage-resistant rubberNon-potable water up to 10 m (EN 50525-2-21) or 100 m factory AD8Municipal sewage lift stations, stormwater sumps, and construction dewatering
**NTSCGEWÖU / Armoured Submersible Pump Cable**0.6/1 kV to 6/10 kV, DIN VDE 0250-813Anti-torsion braid or SS wire armour + heavy 5GM5 rubberHigh-head mine dewatering, slurry agitation, and > 600 N tensile loadsOpen-pit mine sumps, tunneling slurry pumps, and offshore ballast caissons

For a deeper breakdown of AD7 vs AD8 hydrostatic qualification rules, see our engineering guide on Submersible Pump Cable AD7 vs AD8 Water Immersion Testing and PO Specifications.

4K Extrusion Traction, Macro Cross-Section Inspection and Six-Point Submersible FAT Protocol

Why does our factory video (00:16 to 00:22) highlight dual-belt caterpillar haul-off traction (1.0x real-time 4K plant footage) right after continuous vulcanization (CV)? On dry-land tray cables, an ovality (f = D_max - D_min) of 1.5 mm rarely causes trouble. On an AD8 submersible pump cable, one vulcanized nitrile or EPDM grommet inside the pump hood must seal against 2 bar to 15 bar water pressure for 10 to 20 years. Uneven haul-off tension can flatten the hot elastomer jacket or leave valley sink-marks above the 2 x 1.5 mm2 control cores. High-pressure reservoir water then bypasses the grommet and floods the stator cavity.

Scene-by-Scene Walkthrough of the 48-Second Field & 4K Factory Video

Video TimestampScene & Camera ViewEngineering Verification Focus
00:00 - 00:06Aerial view of municipal drinking-water tanks & reservoir booster header + 1:1 insetEstablishes continuous sanitary water-supply duty for H07RN8-F 4x10+2x1.5 (450/750 V AD8)
00:06 - 00:12Indoor municipal clean-water booster pump hall with centrifugal headersShows transitions from wet clearwell risers into dry indoor flanged pump manifolds
00:12 - 00:16Close-up of blue potable pump head & welded AISI 316 gauge (~24 psi steady)Confirms pressurized sanitary operation requiring zero-migration, zero-leakage cable entries
00:16 - 00:22Real 4K (1.0x) plant dual-belt caterpillar haul-off of sky-blue potable sheathVerifies uniform linear traction, zero surface scoring, and tight circular concentricity (<= 5% ovality)
00:22 - 00:26Real 4K macro cross-section scan on TEBAOFLEX CABLE inspection clothConfirms compact Class 5 copper fill, zero core-valley voids, and uniform EPR / blue sheath walls
00:26 - 00:363D stepped structural callout (01 4x10 EPR -> 02 2x1.5 sensors -> 03 blue AD8)Maps how valley-laid 1.5 mm2 thermal leads preserve circular OD inside a single outer jacket
00:36 - 00:48three-panel factory specimen plates (vertical cut, 1:1 section, sheath) & summaryDocuments finished batch aesthetics and EN 50525-2-21 AD8 factory direct traceability

Six-Point Factory Acceptance Testing (FAT) Protocol Before Drum Dispatch

Every production batch of potable-water hybrid H07RN8-F undergoes six routine and sample checks prior to reel sealing.

FAT CheckpointTest StandardTest Condition on 4G10 + 2x1.5 mm2Pass / Acceptance Criterion
1. Conductor DC ResistanceIEC 60228:2023 & EN 5039520 °C Kelvin bridge check on all 4 power + 2 sensor cores10 mm2 <= 1.91 Ohm/km; 1.5 mm2 <= 13.3 Ohm/km
2. Submerged AC Spark & Dielectric VoltageEN 50525-2-21 & EN 503952,500 V AC (50 Hz, 5 min) after 24 h water immersion (20 +/- 5 °C)Zero dielectric breakdown or flashover on power or 1.5 mm2 cores
3. Wet Insulation Resistance (Ki)EN 50395 Clause 8500 V DC at +60 °C (or +90 °C 3GI3) in water bathVolume resistivity constant Ki >= 3.67 MOhm.km (EPR EI4)
4. Gravimetric Water AbsorptionIEC 60811-40214 days immersion in +70 °C deionized water (insulation & blue sheath)Mass uptake within AD8 low-swelling elastomer limits (<= 10 mg/cm2)
5. Outer Diameter & Ovality AuditEN 50396 dual-axis laser + optical comparatorContinuous inline X-Y laser gauge + razor-cut end-sampleFinished OD 21.7 mm - 23.6 mm; ovality (D_max - D_min)/D_nom <= 5%
6. Potable-Water Compound Batch TraceabilityBS 6920 / KTW-BWGL / DVGW W270 formulation auditRaw elastomer batch lot + peroxide cure log verificationZero chloroprene/aromatic-oil cross-contamination; clean non-toxic cure

Potable-Water Submersible Pump Cable Procurement Checklist

Before issuing a purchase order for municipal clearwell, borehole, or reservoir booster cables, lock down six technical fields on the datasheet.

  1. Specify the Exact Drinking-Water Regulatory Regime. Name the local water authority acceptance standard explicitly (WRAS / BS 6920, UBA KTW-BWGL + DVGW W270, ACS, or NSF/ANSI/CAN 61). Avoid vague commercial phrases such as "food-grade rubber".
  2. State Maximum Submergence Depth (m or bar) and Water Temperature (°C). Harmonized EN 50525-2-21 H07RN8-F covers 10 m depth and +40 °C water. For 80 m (8 bar) boreholes or warm geothermal wells (+50 °C to +70 °C), state the exact hydrostatic pressure so compound density and 0.6/1 kV walls match.
  3. Confirm Pump Hood Entry Grommet Bore Range (mm). Submersible pump OEMs (Grundfos, Flygt / Xylem, KSB, Wilo) machine tight rubber compression sleeves (20.0 mm to 24.0 mm). Verify that finished cable OD (21.7 mm to 23.6 mm on 4G10 + 2x1.5) lands inside the middle 60% compression window (EN 62444, 2013).
  4. Declare VFD vs Direct-On-Line / Soft-Starter Supply. Unscreened 4G10 + 2x1.5 runs cleanly on 50/60 Hz grid, star-delta, or soft-starter panels. When a PWM variable-frequency drive feeds a riser over 25 m, specify our screened VFD hybrid pump cable or S07RC4N8-F so dV/dt coupling cannot trip PTC relays.
  5. Define Sensor Core Identification (Numbered 1-2 vs Color-Coded). State whether your panel diagram expects white-numbered black 1.5 mm2 EPR cores (1, 2) or paired colors. Confirm whether two (4G10 + 2x1.5) or four (4G10 + 4x1.5 for independent PTC and FLS loops) auxiliary cores are required.
  6. Order Cut-to-Length Riser Assemblies + AISI 316 Clamping Allowance. Add a 3 m to 5 m service loop at the surface junction box so crews can retrieve the pump without underwater resin splices.

Frequently Asked Questions

Can standard black H07RN8-F cable be used in drinking-water wells or potable reservoirs?

No. Standard black H07RN8-F uses a polychloroprene (EM2) rubber sheath cured with industrial accelerators, plasticizers, and carbon-black fillers. In clean water, those additives leach phenolic odor and total organic carbon (TOC) while promoting microbial biofilm growth. Potable-water wells require a non-toxic sky-blue cross-linked elastomer formulated for drinking-water contact (BS 6920 / WRAS, KTW-BWGL / DVGW W270, ACS, or NSF/ANSI 61).

Why integrate 2x1.5 mm2 control cores into 4G10 instead of running a separate sensor cable?

Seating 2 x 1.5 mm2 EPR control cores inside the outer valleys of the 4 x 10 mm2 power cores eliminates a second submerged gland on the pump hood. Cutting entry penetrations from two to one halves hydrostatic leak paths. The main 10 mm2 lay-up also shields thin PTC thermistor and seal-leakage (FLS) leads from twisting or abrading against riser flanges.

What cable gland or pump grommet size fits H07RN8-F 4G10 + 2x1.5 mm2?

Because both 1.5 mm2 sensor cores sit inside natural interstices between the 10 mm2 power cores, overall diameter stays 21.7 mm to 23.6 mm (close to plain 4G10 at 20.9 mm to 23.4 mm). Select a metric M32 x 1.5 IP68 (10 bar) AISI 316 stainless submersible gland with an 18 mm to 25 mm EPDM insert, or an OEM 21 mm to 24 mm pump sleeve.

How deep can H07RN8-F 4G10 + 2x1.5 mm2 be submerged without clamping or armour?

Hydrostatically, harmonized EN 50525-2-21 rates baseline H07RN8-F (AD8) to 10 m depth at +40 °C, whereas TEBAOFLEX high-density potable AD8 compounds operate to 100 m to 150 m when specified. Mechanically, DIN VDE 0298-3 caps permanent copper tensile stress at 15 N/mm2 (600 N max pull across 4 x 10 mm2). Never hang pump weight on the cable; clamp it to an AISI 316 riser column or lifting rope every 2 m to 3 m.

When must a VFD-driven submersible pump switch from unscreened 4G10 + 2x1.5 to a screened hybrid cable?

Whenever a PWM variable-frequency drive (VFD) feeds a submersible motor over risers longer than 20 m to 25 m, fast IGBT switching edges (dV/dt) couple common-mode noise into unscreened 1.5 mm2 sensor cores. That capacitive noise causes nuisance PTC or moisture-relay trips. Specify a screened hybrid submersible cable combining an overall >= 85% tinned copper braid with individually foil-and-braid-screened 1.5 mm2 control pairs.

Request a Potable-Water H07RN8-F Cut Specimen or Project Quote

Designing a municipal clearwell booster station, upgrading borehole risers to potable-water AD8 elastomers, or matching OEM submersible pump entry grommets (4G6+2x1.5 up to 4G95+4x1.5)? TEBAOFLEX manufactures custom hybrid EN 50525-2-21 submersible rubber cables with 1:1 cut cross-section samples, OD tolerance sheets, and complete six-point FAT reports. Contact TEBAOFLEX engineering for a 24-hour technical quotation and factory specimen dispatch.

WhatsApp: +86 185 9591 3361.

Fact-checked and reviewed by TEBAOFLEX Jyen (Submersible & Municipal Water Cable Engineering Desk) on November 9, 2026. Conductor DC resistances (IEC 60228:2023 Class 5), EN 50525-2-21 ampacities, DIN VDE 0298-3 15 N/mm2 tensile limits, and 4G10 + 2x1.5 mm2 dimensions are verified against CENELEC/IEC standards and our 4K QC archive.

Image credits: Hero aerial treatment plant photo from "MaraduWaterTreatmentPlant-September2026-Rehman" by Rehman Abubakr via Wikimedia Commons (CC BY-SA 4.0). Municipal filtration basin and indoor riser gallery photos by USEPA via Wikimedia Commons (Public domain). 4K macro cross-section and caterpillar haul-off specimen photography by TEBAOFLEX.

Specify it

Sizes, technical data and documents for each cable.

H07RN8-F — horizontal cutaway

Rubber Cable

H07RN8-F

H07RN8-F is a 450/750 V flexible rubber cable to EN 50525-2-21 with Class 5 copper, EI4 rubber insulation and an EM2 water-resistant sheath, rated for continuous fresh-water immersion to 10 m as a submersible-pump supply.

Rated voltage
450/750 V
Standard
IEC
Sizes and data →