3+3 Symmetrical PE vs Four-Core VFD Cables: Bearing-Current Mitigation

3 min read

Technical article

Compare symmetrical split-PE and four-core VFD cables, bearing-current mitigation, protective-earth sizing and shield termination requirements.

By TEBAOFLEX Jyen. Originally published on July 19, 2026.

Symmetrical motor cables can improve the high-frequency return path between a variable-frequency drive and its motor. A 3+3 construction distributes three protective-earth conductors around three phase conductors. A four-core cable places one PE conductor alongside three phases. Neither label alone determines the complete drive system’s EMC performance or bearing life.

Why bearing currents require a system diagnosis

PWM drives produce common-mode voltage. Motor capacitances, grounding paths, cable layout and the driven machine influence the resulting currents. Bearing damage may involve electrical discharge, circulating currents or shaft-grounding currents; lubrication, mechanical alignment and loading must also be investigated. A fluted bearing is not evidence that a particular four-core cable alone caused the failure.

ABB describes several bearing-current mechanisms and mitigation measures. Symmetrical cabling and appropriate grounding are part of the solution; motor insulation, insulated bearings, shaft grounding and filtering may also be needed. Use the recommendations for the actual motor-drive combination, not a universal power threshold.

Compare complete cable constructions

  • Record phase-conductor area, total PE arrangement, shield construction, conductor resistance and voltage rating.
  • Check the drive manufacturer’s permitted cable type and length, output-filter requirements and termination arrangement.
  • Compare measured capacitance and shield properties under stated conditions; optical braid coverage alone is not a complete EMC rating.
  • For moving machinery, require separate qualification for bending or torsional duty. A symmetrical electrical layout does not prove dynamic endurance.

Protective earth and EMC shielding have different jobs

The PE system must satisfy the applicable protective-conductor and fault-clearing requirements. A metallic shield must not be counted as protective-earth capacity merely because it is conductive. Its cross-section, continuity, connections and permitted protective function must be established by the responsible designer.

Illustrative geometry only: three 16 mm² PE conductors have a combined nominal area of 48 mm². This sum does not establish fault withstand or approve the cable for a given phase size. Check the applicable sizing method, conductor material, fault duration and termination capability.

Termination and commissioning

  • Connect every specified PE conductor using an approved terminal arrangement; do not leave split-PE cores floating.
  • Use the drive and motor manufacturers’ prescribed shield bonds, generally aiming for a short, broad high-frequency connection where specified.
  • Do not assume a long shield pigtail has the same high-frequency performance as a circumferential connection.
  • Verify protective bonding and equipment safety before energization. Shaft-voltage measurements require appropriate probes, bandwidth and competent personnel.

What evidence should a purchase order request?

Ask for an exact construction drawing, declared ratings, compatible glands and terminals, and any claimed EMC or endurance reports. If bearing-current mitigation is a project objective, define the motor, drive, switching conditions, cable route and diagnostic method. Do not accept an isolated peak-to-peak voltage as a universal bearing-safety pass/fail criterion.

A 3+3 cable can be a sound choice when recommended for the installation, but it is not a promise of zero bearing current, zero interference or a particular service life.

Sources and scope

ABB: bearing currents and mitigation

These references explain the relevant methods or manufacturer guidance. They do not certify a TEBAOFLEX product or establish results for a supplied batch.