(N)TSW 3.6-6 kV is a weather-resistant (W = wetterfest) 3.6/6 kV (Umax 7.2 kV) medium-voltage rubber trailing power cable based on DIN VDE 0250-813, featuring Class 5 tinned copper conductors, 3GI3 EPR insulation with semi-conductive stress control, split
Typical values for this cable type, based on DIN VDE 0250-813 — confirmed in the datasheet and quotation for your order.
Application fit
Designed for outdoor 3.6/6 kV quarry excavators, floating gravel and sand dredgers, mobile transformer stations, and surface-mine feeder connections.
Weatherproof polychloroprene jacket endures ground dragging across quarry benches and gravel beds.
Widely deployed on floating pontoon conveyors and wet gravel-pit suction dredgers.
Ideal for outdoor MV transformer skids, temporary site substations, and motor feeders.
Suitable for manual or slow festoon/take-up loops; for high-speed reeling use NTSCGEWÖU.
NTSCGEWÖU 3.6/6 kVFor underground coal faces requiring metallic phase screens specify NTSKCGECWÖU.
NTSKCGECWÖU 3.6/6 kVConstruction
Three Class 5 tinned copper phase conductors with inner/outer semi-conductive field grading and 3GI3 EPR insulation, three symmetrical
| # | Layer | Material & reference |
|---|---|---|
| 1 | Phase & split earth conductors | Finely stranded tinned copper, Class 5 per DIN EN 60228DIN EN 60228 Class 5 |
| 2 | Inner & outer field grading | Vulcanised semi-conductive elastomeric stress-control layersDIN VDE 0250-813 |
| 3 | MV EPR insulation (3GI3) | Cross-linked ethylene propylene rubber compound 3GI3 (3.6/6 kV)DIN VDE 0207-20 |
| 4 | Symmetrical 3+3E lay-up | 3 phase cores laid up with 3 split earth conductors in the outer intersticesDIN VDE 0250-813 |
| 5 | Inner sheath | Pressure-extruded elastomer inner bedding compound GM1bDIN VDE 0250-813 |
| 6 | Weatherproof outer sheath (W) | Heavy-duty weather-, UV-, ozone- and oil-resistant polychloroprene 5GM3 / 5GM5DIN VDE 0207-21 |
3 phase cores + 3 symmetrical split protective earth conductors for 3.6/6 kV quarry & dredger service.
3-core 3.6/6 kV feeder configuration for ungrounded IT quarry distribution.
Technical data
Sizes
Nominal dimensions, copper weights and electrical parameters for (N)TSW 3.6-6 kV per DIN VDE 0250-813.
| Order designation | Configuration | Phase size mm² | Outer Ø ≈ mm | Copper kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|
| Standard (N)TSW 3.6-6 kV configurations | |||||||
| (N)TSW 3×16+3×16/3E 3.6/6 kV | 3×16 + 3×16/3E (3.6/6 kV) | 16 | 34.5 | 620 | 1,620 | 207 | |
| (N)TSW 3×25+3×16/3E 3.6/6 kV | 3×25 + 3×16/3E (3.6/6 kV) | 25 | 38.0 | 880 | 2,010 | 228 | |
| (N)TSW 3×35+3×16/3E 3.6/6 kV | 3×35 + 3×16/3E (3.6/6 kV) | 35 | 41.2 | 1,170 | 2,430 | 247 | |
| (N)TSW 3×50+3×25/3E 3.6/6 kV | 3×50 + 3×25/3E (3.6/6 kV) | 50 | 45.5 | 1,680 | 3,090 | 273 | |
| (N)TSW 3×70+3×35/3E 3.6/6 kV | 3×70 + 3×35/3E (3.6/6 kV) | 70 | 50.2 | 2,360 | 3,940 | 301 | |
| (N)TSW 3×95+3×50/3E 3.6/6 kV | 3×95 + 3×50/3E (3.6/6 kV) | 95 | 55.6 | 3,260 | 5,040 | 334 | |
| (N)TSW 3×120+3×70/3E 3.6/6 kV | 3×120 + 3×70/3E (3.6/6 kV) | 120 | 60.2 | 4,180 | 6,120 | 361 | |
| (N)TSW 3×150+3×70/3E 3.6/6 kV | 3×150 + 3×70/3E (3.6/6 kV) | 150 | 64.8 | 5,040 | 7,190 | 389 | |
| Configuration | Max. DC R @ 20 °C Ω/km | Current rating in air (A) | Current rating installed (A) | Mutual C pF/m ≈ | AC test V rms |
|---|---|---|---|---|---|
| 3×16 + 3×16/3E (3.6/6 kV) | 1.240 | 93 | 79 | 136 | 11,000 |
| 3×25 + 3×16/3E (3.6/6 kV) | 0.799 | 122 | 104 | 151 | 11,000 |
| 3×35 + 3×16/3E (3.6/6 kV) | 0.568 | 150 | 128 | 168 | 11,000 |
| 3×50 + 3×25/3E (3.6/6 kV) | 0.396 | 187 | 159 | 192 | 11,000 |
| 3×70 + 3×35/3E (3.6/6 kV) | 0.279 | 229 | 195 | 226 | 11,000 |
| 3×95 + 3×50/3E (3.6/6 kV) | 0.211 | 276 | 235 | 267 | 11,000 |
| 3×120 + 3×70/3E (3.6/6 kV) | 0.165 | 319 | 271 | 308 | 11,000 |
| 3×150 + 3×70/3E (3.6/6 kV) | 0.132 | 365 | 310 | 358 | 11,000 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 11 kV AC voltage withstand | 11 kV rms / 5 min per DIN VDE 0250-813 | 100 % of drums |
| Conductor DC resistance | Complies with DIN EN 60228 Class 5 at 20 °C | 100 % of drums |
| Sample tests | ||
| Ozone & weather ageing test | DIN EN 60811-403 ozone resistance without cracking | Per production batch |
| Flame & oil resistance | DIN EN 60332-1-2 & EN 60811-404 | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.