power connection cable seriesDIN VDE 0276-604 N2XH0.6/1 kV XLPE + HM4 LSZHEN 50575 CPR Cca / B2ca

N2XH LSZH Power CableDIN VDE 0276-604 0.6/1 kV XLPE-insulated LSZH halogen-free fixed power cable

N2XH Low-Smoke Zero-Halogen Power Cable (0.6/1 kV) manufactured per DIN VDE 0276-604, HD 604 S1 and IEC 60502-1 with Class 1/2 bare copper conductors (1×16 to 1×500 mm² & 3×1.5 to 5×240 mm²), 90 °C 2XI1 XLPE insulation, halogen-free.

IEC 60332-3-24 Cat C LSZH
DIN VDE 0276-604
UV-Stable Black HM4 Sheath
Zero Halogen Acid Gas
Order designation
N2XH-J 5×16 RM
Outer Ø ≈
21.4 mm
Weight ≈
985 kg/km
Conductor DC R
1.1500 Ω/km
Ampacity (air 30°C)
94 A
All sizes (6)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Standard
VDE 0276-604
HD 604 S1 / IEC 60502-1
Voltage rating
0.6/1 kV
4,000 V AC test voltage
Configurations
1C to 5C (-J/-O)
1.5 to 500 mm² Cu Cl. 1/2
Insul. / Sheath
2XI1 XLPE / HM4
+90 °C XLPE + LSZH jacket
CPR fire class
Cca-s1,d1,a1
B2ca option for escape routes
Temperature
-30 to +90 °C
+250 °C short-circuit rating

Typical values for this cable type, based on DIN VDE 0276-604 / HD 604 S1 / IEC 60502-1 — confirmed in the datasheet and quotation for your order.

Application fit

Is N2XH right for your machine?

Halogen-free replacement for NYY-J PVC power cables in public buildings, hospitals, data centres, airports, metro stations and industrial plants where toxic hydrochloric smoke must be prevented.

Fixed installation

Suitable

Installed on indoor cable trays, risers, masonry walls, concrete ducts and dry/wet building shafts.

TBM gantry & advancing tunnel reel

Suitable

Passes IEC 60332-3-24 bunched flame, IEC 61034-2 > 60 % light transmittance and IEC 60754-2 low acidity for tunnels and escape routes.

Switchgear & control cabinet wiring

Suitable

+90 °C XLPE insulation delivers ~15–20 % higher continuous current rating than +70 °C NYY PVC cables of equal size.

Immersion & wet locations

With conditions

UV-resistant Black HM4 sheath allows outdoor tray installation in conduit; not for uninhibited direct burial in waterlogged soil.

Typical machinesHyperscale Data Centres & Server HallsHospitals, Airports & High-Rise Commercial BuildingsUnderground Metro Stations & Road TunnelsPharmaceutical, Food & Cleanroom ManufacturingPower Stations & Switchgear Rising Mains

Construction

Layer by layer

N2XH-J / N2XH-O showing bare annealed copper conductors (RE/RM/SM), 90 °C cross-linked polyethylene (2XI1 XLPE) core insulation, halogen-free flame-retardant inner filling compound, and black thermoplastic polyolefin LSZH (HM4) outer sheath.

1234
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Bare annealed copper conductor (RE / RM / SM)Solid Class 1 ('RE', 1.5–16 mm²) or stranded Class 2 ('RM' circular / 'SM' sector, 16–500 mm²) bare copper per IEC 60228Low-loss fixed building & industrial feeder conductor
22XI1 Cross-Linked Polyethylene (XLPE) insulation90 °C thermoset XLPE compound Type 2XI1 per HD 604 S1, colour-coded per HD 308 S2High dielectric strength & +250 °C short-circuit capability
3Halogen-free flame-retardant inner filling compoundUnvulcanized mineral-filled halogen-free elastomeric inner bedding filling core intersticesPrevents chimney effect during vertical tray fires
4HM4 Low-Smoke Zero-Halogen (LSZH) outer sheathThermoplastic halogen-free polyolefin compound Type HM4 (Black, UV-stabilized)Zero halogen (< 0.5 % HCl), conductivity < 2.5 µS/mm, pH > 4.3

N2XH-O (1 × 16 to 1 × 500 mm² Single-Core)

Single-core 0.6/1 kV XLPE/LSZH feeder cable without green/yellow core for parallel trefoil bus feeders

N2XH-J (3G1.5 to 5G240 mm² Multi-Core)

3-, 4- and 5-core 0.6/1 kV XLPE/LSZH distribution cable with green/yellow protective earth core ('-J')

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0276-604 / HD 604 S1 / IEC 60502-1. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage (Uo/U)
0.6 / 1 kV AC (max. 1.2 kV AC / 1.8 kV DC)
AC routine test voltage
4,000 V AC rms for 5 minutes
Max. DC resistance @ 20 °C
1.15 Ω/km (16) · 0.387 Ω/km (50) · 0.193 Ω/km (95) · 0.0754 Ω/km (240)
Volume resistivity @ 90 °C
≥ 10¹² Ω·cm (2XI1 XLPE dielectric)

Thermal

Continuous conductor temp.
+90 °C (vs +70 °C for PVC NYY)
Short-circuit temperature
+250 °C (max. 5 s)
Ambient temperature range
-30 °C to +70 °C (fixed) · -5 °C to +50 °C (laying)

Mechanical

Min. bend radius
15 × OD (single-core N2XH-O) · 12 × OD (multi-core N2XH-J)
Max. pulling tension
50 N / mm² of total copper conductor cross-section
Impact & abrasion
High-density HM4 polyolefin sheath resists tray pulling damage

Resistance

Bunched flame propagation
IEC 60332-3-24 Cat C & EN 50575 CPR Cca-s1,d1,a1 (B2ca opt)
Corrosive gas & acidity
IEC 60754-1/2: pH ≥ 4.3, conductivity ≤ 2.5 µS/mm
Smoke density
IEC 61034-2: light transmittance ≥ 60 %

Reference standards

Design standards
DIN VDE 0276-604 · HD 604 S1 · IEC 60502-1
Core colour standard
HD 308 S2 / DIN VDE 0293-308
RoHS, REACH & CE
EU CPR 305/2011 DoP, 2011/65/EU RoHS 2 & REACH

Identification

VDE code breakdown
N=VDE std · 2X=XLPE · H=Halogen-free HM4 · -J=with GNYE · -O=without GNYE
Core colours (5-core -J)
Green/Yellow, Blue, Brown, Black, Grey (HD 308 S2)
Customs tariff (HS)
8544.4993

Sizes

6 representative N2XH-O (1C) & N2XH-J (5C) 0.6/1 kV configurations

Dimensions, weight, DC resistance and free-air ampacity (30 °C ambient per DIN VDE 0298-4).

Dimensions, weight & air ampacity
VDE designationCores & strandingOuter Ø ≈
mm
Weight ≈
kg/km
Max. DC R
Ω/km
Air 30°C
A
Enquiry
Single-Core N2XH-O
N2XH-O 1×95 RM1 × 95 mm² Class 217.59800.1930298
N2XH-O 1×240 RM1 × 240 mm² Class 225.82,3800.0754538
Five-Core N2XH-J (3P+N+PE)
N2XH-J 5×2.5 RE5G2.5 mm² Class 112.22257.410029
N2XH-J 5×16 RM5G16 mm² Class 221.49851.150094
N2XH-J 5×50 RM5G50 mm² Class 233.52,6800.3870183
N2XH-J 5×95 RM5G95 mm² Class 244.24,9500.1930282
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • For installations requiring functional circuit integrity (FE180 / E30–E90) during a fire, specify NHXH E30/E90.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
100 % 4.0 kV AC dielectric, spark & DC resistance testZero breakdown for 5 min and DC R within IEC 60228 limitsEvery manufactured drum length
Sample tests
IEC 60754-2 acid gas pH/conductivity & IEC 61034-2 smoke densitypH ≥ 4.3, conductivity ≤ 2.5 µS/mm, light transmittance ≥ 60 %Per production batch
EN 50399 / IEC 60332-3-24 vertical tray fire & heat release testMeets CPR Euroclass Cca-s1,d1,a1 (or B2ca-s1,d1,a1)Notified Body CPR certification

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0276-604 & HD 604 S1EN 50575 CPR Cca / B2caIEC 60502-1 & RoHS 2

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX N2XH-J / N2XH-O 0.6/1kV VDE 0276-604 Cca-s1,d1,a1 CE
Delivery form
Fumigated wooden drums or steel export reels
Standard lengths
500 m · 1000 m (or custom cut lengths)
MOQ
100 m (standard) · 500 m (custom)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-20
Updated
2026-10-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

Why does N2XH carry ~15–20 % more current than an NYY-J PVC cable of the exact same copper cross-section?
NYY-J uses thermoplastic PVC insulation limited to +70 °C continuous conductor temperature (+160 °C short-circuit), whereas N2XH uses cross-linked polyethylene (2XI1 XLPE) rated to +90 °C continuous (+250 °C short-circuit). For example, 5×16 mm² N2XH-J in air at 30 °C is rated ~94 A vs ~80 A for 5×16 mm² NYY-J.
What is the difference between N2XH and N2XCH?
N2XH is an unscreened power cable (available as 3-, 4- or 5-core with an insulated Green/Yellow PE core). N2XCH adds a concentric helical copper wire + copper tape screen ('C') around the core assembly for EMC-sensitive environments or tamper-proof public installations.
Can N2XH be buried directly in the ground like NYY-J?
According to DIN VDE 0276-604, thermoplastic HM4 polyolefin sheaths are designed for indoor/outdoor installation in air, trays and conduits. Underground runs must be installed inside protective closed cable ducts/pipes Free of standing water; for direct soil burial without conduit, specify armoured or PE-sheathed N2XY / NA2XY.
What do '-J' and '-O' mean in N2XH-J and N2XH-O?
'-J' indicates the cable includes a Green/Yellow protective earth (PE) conductor (e.g. 3G, 4G, 5G). '-O' indicates the cable has no Green/Yellow conductor (used on 1-core parallel phase feeders or 3-wire/4-wire circuits with a separate earth bar).

Request a quote

Get an engineering quote for N2XH

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

N2XH LSZH Power Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote