N2XSEYFGbY 6/10 kV XLPE Flat-Steel-Armoured Feeder CableN2XSEYFGbY 6/10 kV medium-voltage mining and industrial distribution cable per DIN VDE 0276-620, featuring Class 2 copper conductors, triple-extruded 90 °C XLPE cores (2X), copper wire screens (SE), flat steel wire armour (FGb) and FR-PVC sheath.

Engineered for underground mining, open-cast excavation, shaft infrastructure and heavy industrial service per DIN VDE 0276-620 / IEC 60502-2 across -20 to +90 °C.

EMC screen
Oil-resistant
Flame-retardant
Outdoor & humid
Order designation
N2XSEYFGbY 3×95/16 mm² 6/10 kV
Outer Ø ≈
58.2 mm
Net weight ≈
5,480 kg/km
Tensile rating ≈
42.8 kN
Core / stranding
Class 2 compacted Cu
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
6/10 kV
6/10 kV (U_m = 12 kV) MV distribution
Operating temp.
-20 to +90 °C
Continuous mining & industrial duty
Min. bend radius
15 × OD
Fixed installation / dynamic routing
Core / conductor
3×50–240 mm² Cu
Class 2 compacted copper + Cu screen
Outer protection
FGb + FR-PVC
Flat steel wire + counter-tape + PVC
Standard
VDE 0276-620
DIN VDE 0276-620 / IEC 60502-2

Typical values for this cable type, based on DIN VDE 0276-620 / IEC 60502-2 — confirmed in the datasheet and quotation for your order.

Application fit

Is N2XSEYFGbY right for your machine?

Engineered for underground mining, open-cast excavation, shaft infrastructure and heavy industrial service per DIN VDE 0276-620 / IEC 60502-2 across -20 to +90 °C.

Mine roadway & tunnel wall hangers

Suitable

Engineered for underground mining shafts, galleries and tunnel infrastructure per DIN VDE 0276-620 / IEC 60502-2.

Fixed installation

Suitable

Suitable for vertical shaft cleats, gallery messenger hooks and tray routing within 15 × OD.

Free-hanging vertical run

Suitable

Supports inclined roadway and vertical mine shaft suspension within rated kN load across -20 to +90 °C.

Typical machinesMining & TunnellingUnderground Coal & Hard-Rock MiningOpen-Cast Excavators, Draglines & ShovelsVertical Mine Shafts, Hoists & BoreholesTunneling, Mineral Processing & Slurry Plants

Construction

Layer by layer

Shown: N2XSEYFGbY (DIN VDE 0276-620 / IEC 60502-2) featuring phase conductors (3×95 mm²), triple-extruded xlpe core (2x) and outer sheath (fr-pvc) (5-layer construction).

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Phase Conductors (3×95 mm²)IEC 60228 Class 2 compacted circular plain copper conductors
2Triple-Extruded XLPE Core (2X)Inner semicon + 90 °C dry-cured XLPE dielectric + strippable outer semicon
3Individual Copper Wire Screen (SE)Helically applied plain copper wires with counter-helix copper tape
4PVC Bedding & Steel Armour (FGb)PVC inner sheath + galvanized flat steel wires (F) + steel counter tape (Gb)
5Outer Sheath (FR-PVC)Heavy-duty flame-retardant, oil- and UV-resistant PVC outer jacket

N2XSEYFGbY — Standard Mining Execution

Built to DIN VDE 0276-620 / IEC 60502-2 with phase conductors (3×95 mm²) and outer sheath (fr-pvc)

N2XSEYFGbY — Custom Drum Length & Gland Kit

Available in custom shaft/roadway drum lengths or pre-terminated assemblies

N2XSEYFGbY — Routine & Flame Test Certified

Supplied with EN 10204 3.1 routine dielectric, resistance & flame test report

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0276-620 / IEC 60502-2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / transmission duty
6/10 kV (DIN VDE 0276-620 / IEC 60502-2)
Core / conductor construction
Phase Conductors (3×95 mm²) — IEC 60228 Class 2 compacted circular plain copper conductors
Primary dielectric / buffering
Triple-Extruded XLPE Core (2X) — Inner semicon + 90 °C dry-cured XLPE dielectric + strippable outer semicon

Thermal

Continuous operating temperature
-20 to +90 °C (mining & industrial service)
Short-circuit / peak thermal rating
Verified thermal stability per DIN VDE 0276-620 / IEC 60502-2
Storage & transport temperature
−40…+80 °C on export wooden/steel drum

Mechanical

Outer protection / armouring
Outer Sheath (FR-PVC) — Heavy-duty flame-retardant, oil- and UV-resistant PVC outer jacket
Minimum bending radius
15 × OD
Crush, impact & abrasion duty
Heavy-duty mining rock-cut, impact and tensile protection per DIN VDE 0276-620 / IEC 60502-2

Resistance

Flame retardancy & mine fire safety
Self-extinguishing / flame-retardant mining jacket per DIN VDE 0276-620 / IEC 60502-2
Mine water, oil & chemical resistance
Resistant to acidic mine water, hydraulic oils and abrasion per DIN VDE 0276-620 / IEC 60502-2
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing standard
DIN VDE 0276-620 / IEC 60502-2
Flame & environmental test standards
IEC 60332 / MSHA / EN 60794 / IEC 60228
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
N2XSEYFGbY
Sheath colour & metre marking
Continuous metre-marked red mining outer sheath
Customs tariff (HS)
8544.49 / 8544.60 / 8544.70

Sizes

3 standard N2XSEYFGbY mining & industrial configurations

Manufactured to DIN VDE 0276-620 / IEC 60502-2 for underground mining, open-cast excavation, shaft and heavy industrial systems.

Dimensions, tensile load & weights
Order designationConfigurationCore / strandingOuter Ø ≈
mm
Net weight ≈
kg/km
Tensile rating
kN ≈
Min. bend R
mm
Enquiry
N2XSEYFGbY Construction Schedule (-20 to +90 °C)
N2XSEYFGbY 3×70/16 mm² 6/10 kV3 × 70 mm² / 16 mm² SEClass 2 compacted Cu54.04,56031.5810
N2XSEYFGbY 3×95/16 mm² 6/10 kV3 × 95 mm² / 16 mm² SEClass 2 compacted Cu58.25,48042.8875
N2XSEYFGbY 3×150/25 mm² 6/10 kV3 × 150 mm² / 25 mm² SEClass 2 compacted Cu65.57,49067.5985
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Custom core cross-sections, pair/fibre counts, armour grades and factory drum lengths available per DIN VDE 0276-620 / IEC 60502-2.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance, continuity & dimensional verification (DIN VDE 0276-620 / IEC 60502-2)DC resistance at 20 °C / optical attenuation and outer diameter within DIN VDE 0276-620 / IEC 60502-2 tolerancesEvery manufactured drum length
High-voltage dielectric & insulation resistance test (DIN VDE 0276-620 / IEC 60502-2)Zero dielectric breakdown and verified insulation resistance over full production lengthEvery manufactured drum length
Sample tests
Flame propagation, mechanical crush & thermal ageing qualification (DIN VDE 0276-620 / IEC 60502-2)Verified flame retardancy, mechanical integrity and thermal endurance across -20 to +90 °CType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

VDE 0276-620 CompliantEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX N2XSEYFGbY VDE 0276-620 6/10 kV CE
Delivery form
Heavy-duty export fumigated wooden drums or steel mine reels
Standard lengths
500 m, 1,000 m or custom continuous shaft/reeling lengths
MOQ
100 m (standard configurations) · 500 m (custom builds)
Lead time
2–5 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-24
Updated
2026-10-24

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define N2XSEYFGbY (N2XSEYFGbY 6/10 kV XLPE Flat-Steel-Armoured Feeder Cable)?
N2XSEYFGbY (N2XSEYFGbY 6/10 kV XLPE Flat-Steel-Armoured Feeder Cable) is manufactured in accordance with DIN VDE 0276-620 / IEC 60502-2 for 6/10 kV duty over -20 to +90 °C. Its 5-layer construction comprises Phase Conductors (3×95 mm²), Triple-Extruded XLPE Core (2X) and Outer Sheath (FR-PVC).
What is the minimum bending radius and operating temperature range for N2XSEYFGbY?
The minimum bending radius for N2XSEYFGbY is 15 × OD across its continuous operating temperature range of -20 to +90 °C, ensuring mechanical and dielectric reliability in mining and heavy industrial service.
How are the concentric layers of N2XSEYFGbY arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Phase Conductors (3×95 mm²) (IEC 60228 Class 2 compacted circular plain copper conductors); (02) Triple-Extruded XLPE Core (2X) (Inner semicon + 90 °C dry-cured XLPE dielectric + strippable outer semicon); (03) Individual Copper Wire Screen (SE) (Helically applied plain copper wires with counter-helix copper tape); (04) PVC Bedding & Steel Armour (FGb) (PVC inner sheath + galvanized flat steel wires (F) + steel counter tape (Gb)); (05) Outer Sheath (FR-PVC) (Heavy-duty flame-retardant, oil- and UV-resistant PVC outer jacket).
What factory test certificates are supplied with N2XSEYFGbY?
Every production drum of N2XSEYFGbY undergoes routine conductor resistance/continuity, high-voltage dielectric and dimensional testing per DIN VDE 0276-620 / IEC 60502-2, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for N2XSEYFGbY

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

N2XSEYFGbY 6/10 kV XLPE Flat-Steel-Armoured Feeder Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote