400 Hz Aircraft GPU Cable: E/F Interlock and Grounding Guide

Understand the E/F interlock, protective bonding and cable selection for 400 Hz aircraft ground power. Confirm every assembly against the equipment documentation.

JyenOperations & Technical Engineer6 min read
Yellow aircraft ground power cables prepared for delivery
Category
Technical article
Updated
Reading time
6 min read
In this article10 sections
  1. 01What do the E/F interlock contacts do?
  2. 02Interlock, protective bonding and static grounding
  3. 03Choosing a 400 Hz cable construction
  4. 04What to provide when ordering an assembly
  5. 05Frequently asked questions
  6. Are E and F protective earth conductors?
  7. Can one pre-terminated assembly fit every GPU?
  8. Does a seven-core design always reduce voltage drop by a fixed percentage?
  9. Does the interlock make energized disconnection safe?
  10. 06References and related products

An aircraft ground power cable carries power and may also contain control conductors. In a 400 Hz system, the E/F contacts are associated with the interlock; they do not replace protective bonding. Identify the cable and connector from the approved drawings for the specific aircraft and ground power unit (GPU), not from conductor colour or position.

What do the E/F interlock contacts do?

For AC ground power facilities, ISO 6858:2017 describes an aircraft interlock signal associated with contacts E and F. A 28 V DC control signal is typical, but the signal source, return path and connector wiring depend on the approved equipment configuration. The Hobart PowerMaster EV manual, for example, shows different civil and certain military arrangements.

ISO 6858:2017 section 7.2.1 requires a minimum 2.5 s of power availability without an F signal after an operator commands the facility on, allowing aircraft controls to energize. Once the interlock signal has been established, its loss requires supply removal within 0.25 s. The standard also says the facility should tolerate momentary signal interruptions up to 50 ms.

Interlock behaviour and contact timing must be verified for the actual equipment; they do not guarantee arc-free disconnection in every situation. Follow the aircraft and GPU manufacturers’ isolation and handling procedures. Do not infer permission to connect or disconnect an energized assembly from the interlock description.

Interlock, protective bonding and static grounding

An interlock control circuit, protective bonding and static discharge grounding serve different purposes. Whether a separate bonding or grounding conductor is needed, and where it connects, depends on the aircraft, GPU and site installation. Confirm those requirements in the relevant approved documentation; do not identify an earth conductor by its proximity to a phase lead.

Choosing a 400 Hz cable construction

Illustrative cross-section of a symmetrical aircraft ground power cable

Cable constructions can use four power cores or a symmetrical seven-power-core arrangement with paired phase conductors and a central neutral. Control conductors, conductor sizes and termination details vary by design. The illustration is schematic; confirm the actual core count and functions on the product drawing.

At 400 Hz, inductive reactance as well as AC resistance affects voltage at the aircraft connector. A symmetrical arrangement can reduce inductive impedance, but a percentage saving cannot be assumed for every cable. Request measured or calculated performance for the specified length, current, power factor, temperature, connector losses and any GPU voltage compensation.

For comparison, discuss the available 400 Hz aircraft ground power cable, F19 four-core cable and F20 symmetrical cable with the supplier. Product descriptions are starting points, not approval for a particular aircraft, connector or operating duty.

What to provide when ordering an assembly

Before ordering a replacement cable or pre-terminated assembly, provide the supplier with:

  • The aircraft and GPU manufacturer, model, serial or production details, and the applicable wiring drawings.
  • Connector part numbers, orientation, ratings and the approved interface for both ends.
  • Required power and control cores, conductor sizes and the specified protective bonding arrangement.
  • Finished length, routing, bend and reel requirements, and the expected temperature, abrasion and fluid exposure.
  • A reviewed termination drawing, lug dimensions, identification, inspection and acceptance-test requirements.

Ask for test data for the exact cable construction and exposure when fluid resistance or mechanical durability is required. An ISO 9001 quality management certificate alone does not establish those product properties.

Frequently asked questions

Are E and F protective earth conductors?

In the interlock arrangement described above, E and F perform control functions. That does not determine how protective bonding or static grounding is provided for a particular installation; verify the approved drawings.

Can one pre-terminated assembly fit every GPU?

No. The connector, terminal dimensions, circuit arrangement and approval can differ by equipment and production version. Confirm the exact assembly drawing before manufacture or replacement.

Does a seven-core design always reduce voltage drop by a fixed percentage?

No. Compare cables using the same load and installation conditions and verified 400 Hz electrical data. Both resistance and reactance contribute to the result.

Does the interlock make energized disconnection safe?

No. The interlock is one part of a system, not a guarantee against arcing or injury. Use the approved equipment procedures and have qualified personnel carry out installation and maintenance.

References and related products

ISO 6858:2017: aircraft ground support electrical supplies

ISO 461-1:2003: connector design, performance and testing

ISO 461-2:1985: connector dimensions

Hobart PowerMaster EV: operation and maintenance manual

US Department of Defense: aircraft point-of-use power systems

400 Hz aircraft ground power cable

F19 400 Hz four-core cable

F20 400 Hz symmetrical cable

Specify it

Sizes, technical data and documents for each cable.

TEBAOFLEX

Power connection cables

F19 400Hz Airport 4-Core + 4 Control Wires

F19 400Hz Airport 4-Core + 4 Control Wires 0.6/1kV manufactured to IEC 60228 Class 5/6, rated 0.6/1 kV (400 Hz Aircraft Ground Power) and -40°C to +90°C with a 8 × OD minimum bending radius for infrastructure & construction installations.