Fixed installation
Ideal for hot refinery pipe racks, steam-traced process lines and outdoor trays where +70 °C PE cores would soften.
Product
High-thermal-stability 300/500 V process instrumentation cable built to BS EN 50288-7 with Class 2 copper conductors, +90 °C XLPE (2X) insulation, collective or PiMF Al/PET screen and oil-resistant flame-retardant PVC (Y) outer sheath.
Typical values for this cable type, based on BS EN 50288-7 (300/500 V) — confirmed in the datasheet and quotation for your order.
Application fit
Combines the +90 °C thermal stability and low capacitance of thermoset XLPE (2X) core insulation with the chemical, acid, alkali and hydrocarbon splash resistance of an industrial PVC (Y) outer sheath.
Ideal for hot refinery pipe racks, steam-traced process lines and outdoor trays where +70 °C PE cores would soften.
UV-stabilised, oil- and chemical-resistant Black RAL 9005 PVC outer sheath.
Unarmoured PVC sheath requires ducting underground; specify SWA armoured execution for direct burial.
Use RE-2Y(st)Y SWAYClass 2 stranded conductors and thermoset XLPE insulation are for static process installations.
PUR Drag-Chain Control CableConstruction
Shown: RE-2X(st)Y PiMF 4×2×1.0 mm² with Class 2 copper conductors, +90 °C XLPE Black/White numbered cores, individual pair foil screens (PiMF), collective Al/PET screen and Black or Ex-i Blue PVC outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Stranded copper conductors | Annealed bare or tinned copper, 7-wire stranded (IEC 60228 Class 2)Low DC loop resistance for 4–20 mA and HART digital transmitters |
| 2 | Cross-linked polyethylene (XLPE / 2X) | Thermoset XLPE per EN 50290-2-29 (+90 °C continuous, +250 °C short-circuit)Does not melt or deform under high ambient heat or soldering/overload |
| 3 | Individual pair screen (PiMF option) | Al/PET laminated tape + 0.5 mm² tinned copper drain wire on each pairEliminates pair-to-pair capacitive crosstalk |
| 4 | Polyester binder tape | Helical PET separating wrap over laid-up pairs or triadsMaintains circular pair bundle geometry |
| 5 | Collective Al/PET electrostatic screen (st) | Aluminium/PET tape (≥ 20 % overlap) + 0.5 mm² tinned copper drain wire100 % electrostatic shielding |
| 6 | Oil- & flame-retardant PVC outer sheath (Y) | Extruded PVC (TM1 / YM1 per EN 50290-2-22) with ripcord, Black RAL 9005 or Blue RAL 5015 (Ex-i)IEC 60332-1-2 & IEC 60332-3-24 Cat C flame retardant |
+90 °C XLPE pairs/triads with collective Al/PET screen and oil-resistant PVC jacket
Individual Al/PET pair screens plus overall Al/PET screen and PVC jacket
Sky-blue PVC outer sheath for Zone 0/1/2 intrinsically safe circuits
Technical data
Sizes
+90 °C XLPE core insulation with flame- and oil-resistant PVC outer sheath.
| Order designation | Format | Screening | Outer Ø ≈ mm | Copper kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|
| 0.5 mm² XLPE/PVC — L/R ≤ 25 µH/Ω · +90 °C | |||||||
| RE-2X(st)Y 1×2×0.5 | 1×2×0.5 mm² | OS | 5.8 | 15 | 46 | 44 | |
| RE-2X(st)Y 2×2×0.5 | 2×2×0.5 mm² | OS | 8.3 | 25 | 77 | 62 | |
| RE-2X(st)Y 4×2×0.5 PiMF | 4×2×0.5 mm² | PiMF+OS | 10.7 | 52 | 134 | 80 | |
| RE-2X(st)Y 8×2×0.5 PiMF | 8×2×0.5 mm² | PiMF+OS | 13.9 | 98 | 228 | 104 | |
| RE-2X(st)Y 12×2×0.5 PiMF | 12×2×0.5 mm² | PiMF+OS | 16.6 | 144 | 322 | 125 | |
| 0.75 mm² XLPE/PVC — L/R ≤ 25 µH/Ω · +90 °C | |||||||
| RE-2X(st)Y 1×2×0.75 | 1×2×0.75 mm² | OS | 6.2 | 20 | 55 | 46 | |
| RE-2X(st)Y 2×2×0.75 | 2×2×0.75 mm² | OS | 9.1 | 34 | 94 | 68 | |
| RE-2X(st)Y 4×2×0.75 PiMF | 4×2×0.75 mm² | PiMF+OS | 11.7 | 71 | 165 | 88 | |
| RE-2X(st)Y 8×2×0.75 PiMF | 8×2×0.75 mm² | PiMF+OS | 15.3 | 136 | 282 | 115 | |
| 1.0 mm² XLPE/PVC — L/R ≤ 25 µH/Ω · +90 °C | |||||||
| RE-2X(st)Y 1×2×1.0 | 1×2×1.0 mm² | OS | 6.6 | 25 | 65 | 50 | |
| RE-2X(st)Y 4×2×1.0 PiMF | 4×2×1.0 mm² | PiMF+OS | 12.6 | 90 | 198 | 94 | |
| RE-2X(st)Y 8×2×1.0 PiMF | 8×2×1.0 mm² | PiMF+OS | 16.6 | 174 | 344 | 125 | |
| 1.5 mm² XLPE/PVC — L/R ≤ 40 µH/Ω · +90 °C | |||||||
| RE-2X(st)Y 1×2×1.5 | 1×2×1.5 mm² | OS | 7.5 | 35 | 84 | 56 | |
| RE-2X(st)Y 2×2×1.5 | 2×2×1.5 mm² | OS | 10.9 | 63 | 148 | 82 | |
| RE-2X(st)Y 4×2×1.5 PiMF | 4×2×1.5 mm² | PiMF+OS | 14.2 | 129 | 262 | 106 | |
| RE-2X(st)Y 8×2×1.5 PiMF | 8×2×1.5 mm² | PiMF+OS | 18.8 | 252 | 456 | 141 | |
| RE-2X(st)Y 12×2×1.5 PiMF | 12×2×1.5 mm² | PiMF+OS | 22.5 | 374 | 652 | 169 | |
| RE-2X(st)Y 24×2×1.5 PiMF | 24×2×1.5 mm² | PiMF+OS | 31.0 | 742 | 1,235 | 232 | |
| Conductor size | Max. DC R @ 20 °C Ω/km | Max. L/R ratio µH/Ω | Max. C (OS) nF/km | Max. C (PiMF) nF/km |
|---|---|---|---|---|
| 0.50 mm² | 36.7 | 25 | 100 | 115 |
| 0.75 mm² | 25.0 | 25 | 100 | 115 |
| 1.00 mm² | 18.5 | 25 | 100 | 115 |
| 1.50 mm² | 12.3 | 40 | 100 | 115 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 2000 V AC dielectric test & mutual capacitance test | 2.0 kV AC for 1 min; C ≤ 100 / 115 nF/km | Every manufactured drum |
| Sample tests | ||
| XLPE hot-set cross-linking test (EN 60811-507) | Elongation under load ≤ 175 % at +200 °C | Per XLPE batch |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.