Motor stator, traction & converter leads
Ideal for compact 6 kV, 10 kV, 15 kV and 20 kV switchgear cell interconnections, transformer secondary jumpers and mobile skid-mounted.
Product
(N)TMCGC11Y Single-Core Medium-Voltage PUR-Sheathed Cable (3.6/6 kV, 6/10 kV, 12/20 kV & 18/30 kV; 25 mm² to 630 mm²) engineered per DIN VDE 0250-813 with Class 5 fine-stranded tinned copper conductor, triple-extruded inner/outer.
Typical values for this cable type, based on DIN VDE 0250-813 / IEC 60502-2 — confirmed in the datasheet and quotation for your order.
Application fit
Combines the tight 5 × OD bend radius and field-controlled safety of a VDE 0250-813 flexible screened medium-voltage rubber cable with the extreme mechanical cut, tear and oil resistance of an 11YM1 polyurethane (PUR) outer sheath.
Ideal for compact 6 kV, 10 kV, 15 kV and 20 kV switchgear cell interconnections, transformer secondary jumpers and mobile skid-mounted.
11YM1 polyurethane ('11Y') outer sheath provides 3× higher abrasion and notch-tear resistance than standard polychloroprene (5GM3) rubber.
Widely deployed for tunnel boring machine (TBM) MV transformer connections, mobile crusher substations and containerised shore-power.
Designed for fixed, mobile and festoon/trailing jumper service; for multi-core motorized crane reels under high axial tension use.
Use Unscreened NTMCWÖUConstruction
(N)TMCGC11Y Single-Core MV Cable showing Class 5 flexible tinned copper conductor, inner semiconducting elastomer layer, 90 °C 3GI3 EPR insulation, outer semiconducting elastomer layer ('G'), concentric helical/braided tinned copper earth screen ('C'), and red/yellow/black 11YM1 polyurethane ('11Y') outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Class 5 fine-stranded tinned copper conductor | Electrolytic tin-coated annealed flexible copper wires per IEC 60228 / DIN VDE 0295 Class 5 (25 mm² to 630 mm²)Allows 5 × OD static bend radius inside cramped MV switchgear and transformer boxes |
| 2 | Inner semiconducting elastomer stress-control layer ('G') | Vulcanized semiconducting rubber co-extruded over the conductorSmooths strand contour and prevents corona discharge at the conductor interface |
| 3 | 3GI3 Ethylene Propylene Rubber (EPR) MV dielectric | Ozone- and corona-resistant 90 °C thermoset EPR compound Type 3GI3 per DIN VDE 0207-20Flexible across -40 °C to +90 °C with high partial-discharge inception voltage |
| 4 | Outer semiconducting rubber ('G') + Tinned Cu screen ('C') | Easy-strip outer semiconducting elastomer + concentric helical tinned copper wire / counter-helix or braid screen ('C', 10–35 mm²)Confines radial electric field and safely conducts earth-fault currents |
| 5 | 11YM1 Polyurethane ('11Y') heavy-duty outer sheath | Ether-based thermoplastic polyurethane compound Type 11YM1 per DIN VDE 0207-21 (Red RAL 3000, Yellow or Black)Extreme cut, tear, microbe, hydraulic oil and UV weather resistance |
6/10 kV (Umax 12 kV) screened flexible single-core EPR/PUR cable for industrial 10/11 kV switchgear and motors
12/20 kV (Umax 24 kV) screened flexible single-core EPR/PUR cable for 20/22 kV substation transformers and mobile skids
18/30 kV (Umax 36 kV) screened flexible single-core EPR/PUR cable for 30/33/35 kV wind, mining and grid jumpers
Technical data
Sizes
Conductor & screen cross-section, outer diameter, weight, DC resistance and free-air ampacity (30 °C).
| VDE designation | Conductor / Cu screen | Outer Ø ≈ mm | Weight ≈ kg/km | Max. DC R Ω/km | Air 30°C A | Enquiry |
|---|---|---|---|---|---|---|
| 6/10 kV (N)TMCGC11Y | ||||||
| (N)TMCGC11Y 1×50/16 6/10kV | 50 mm² Cl.5 + 16 mm² Cu screen | 24.2 | 920 | 0.3930 | 238 | |
| (N)TMCGC11Y 1×95/16 6/10kV | 95 mm² Cl.5 + 16 mm² Cu screen | 28.0 | 1,410 | 0.2060 | 358 | |
| (N)TMCGC11Y 1×185/25 6/10kV | 185 mm² Cl.5 + 25 mm² Cu screen | 33.8 | 2,410 | 0.1080 | 540 | |
| 12/20 kV (N)TMCGC11Y | ||||||
| (N)TMCGC11Y 1×50/16 12/20kV | 50 mm² Cl.5 + 16 mm² Cu screen | 28.6 | 1,150 | 0.3930 | 242 | |
| (N)TMCGC11Y 1×120/16 12/20kV | 120 mm² Cl.5 + 16 mm² Cu screen | 33.8 | 1,910 | 0.1640 | 418 | |
| (N)TMCGC11Y 1×240/25 12/20kV | 240 mm² Cl.5 + 25 mm² Cu screen | 40.5 | 3,280 | 0.0817 | 645 | |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 100 % High-voltage AC dielectric (11–43 kV) & partial discharge (< 5 pC) test | Zero breakdown for 5 min and PD ≤ 5 pC at 1.73 × Uo | Every manufactured drum length |
| Sample tests | ||
| 11YM1 polyurethane tear strength, abrasion & hot-oil immersion | Meets DIN VDE 0207-21 mechanical and oil retention limits | Per production batch |
| 3GI3 EPR ozone, hot-set & bending-plus-thermal-cycle test | PD remains ≤ 5 pC after 3 bending cycles and +95 °C heating cycles | Type qualification |
Marking & supply
Sheath marking