Contact
Screened power & VFD / motor supply cablesUL 1569 Type MCU0/U 600/1000 V · 4 kV ACArmoured EMC

VFDAP 600/1000 V Type MC Armored VFD CableUL 1569 Type MC aluminum-armored copper-tape VFD motor cable

VFDAP 600/1000 V Type MC integrates stranded bare copper phases, three symmetrical bare grounds, copper tape screening, and interlocked aluminum armor under a black PVC jacket for NEC industrial installations.

Low-EMC design
EMC screen
Flame-retardant
Outdoor & humid
Order designation
VFDAP 600/1000V Type MC 3×4 AWG + 3×12 AWG
Outer Ø
27.2 mm
Max. R20
0.832 Ω/km
Weight
1,602 kg/km
Min. bend R
326 mm
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
600/1000 V
AC test voltage 4 kV AC
EMC screening
100% Cu tape
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -20 °C to +90 °C
Min. bend radius
12 × OD
Fixed routing in trays & ducts
Conductor
Bare Cu · Cl.B
ASTM B172 / B8 copper
Size range
14 AWG–500 kcmil
12 standard configurations

Typical values for this cable type, based on UL 1569 Type MC · UL 44 XHHW-2 · CSA C22.2 No. 131 Teck/ACIC — confirmed in the datasheet and quotation for your order.

Application fit

Is VFDAP 600/1000V Type MC right for your machine?

VFDAP 600/1000 V Type MC integrates stranded bare copper phases, three symmetrical bare grounds, copper tape screening, and interlocked aluminum armor under a black PVC jacket for NEC industrial installations.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 600/1000 V XLPE/PVC construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 600/1000 V XLPE/PVC geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Heavy plant machinery & MCC feeder

Suitable

High-capacity 600/1000 V XLPE/PVC feeder connects motor control centers (MCC) cleanly to heavy plant machinery and main distribution panels.

Direct-burial & wet conduit run

Suitable

Moisture-resistant 600/1000 V XLPE/PVC protection allows direct-burial trenching, underground sand beds, and damp concrete ducts.

Energy chain / drag chain

Not suitable

600/1000 V XLPE/PVC construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

600/1000 V XLPE/PVC build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesOil & Gas CableVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of VFDAP 600/1000V Type MC: bare copper conductors, UL 44 XHHW-2 thermoset XLPE (90 °C wet/dry), Helical bare copper tape shield (100% radial coverage), and Black UV- & oil-resistant PVC overall jacket over armor.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorASTM B8 Class B stranded bare annealed copperASTM B8 Class B / UL 44
2Core insulationUL 44 XHHW-2 thermoset XLPE (90 °C wet/dry)UL 1569 Type MC
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeUL 1569 Type MC
4EMC metallic screenHelical bare copper tape shield (100% radial coverage)EMC ≥ 85% / 100% foil
5Metallic armourInterlocked aluminum strip armor (UL 1569 Type MC)UL 1569 Type MC
6Outer sheathBlack UV- & oil-resistant PVC overall jacket over armorIEEE 1202 / FT4 Flame

VFDAP 600/1000V Type MC 3C + 3G Symmetrical

Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1569 Type MC · UL 44 XHHW-2 · CSA C22.2 No. 131 Teck/ACIC. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
600/1000 V
AC test voltage
4 kV AC / 5 min
Conductor class
ASTM B8 Class B bare Cu
EMC screen
Helical bare copper tape shield (100%
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-20 °C to +90 °C
Short-circuit temp.
+250 °C (5 s)
Min. bending radius
12 × OD (fixed)

Resistance

Flame retardance
IEEE 1202 / FT4 Flame
Oil & chemical perf.
UL Oil Res I/II
Environmental / EMC
Direct Burial & Sun Res
Outer sheath
Black UV- & oil-resistant PVC overall

Sizes

3C + 3G Symmetrical (AWG/kcmil)
Cores ×
AWG/kcmil
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
12×D mm
3×14 AWG + 3×18 AWG15.98.450130381191
3×12 AWG + 3×16 AWG16.95.310181474203
3×10 AWG + 3×14 AWG18.23.340260614218
3×8 AWG + 3×14 AWG21.52.100356849258
3×6 AWG + 3×12 AWG23.61.3205311,153283
3×4 AWG + 3×12 AWG27.20.8327601,602326
3×2 AWG + 3×10 AWG31.60.5231,1682,344379
3×1/0 AWG + 3×6 AWG35.80.3291,9483,583430
3×2/0 AWG + 3×6 AWG38.30.2612,3384,239460
3×4/0 AWG + 3×4 AWG44.90.1643,6686,409539
3×350 kcmil + 3×2 AWG54.10.0995,96210,119649
3×500 kcmil + 3×2 AWG61.30.0708,07413,529736
  • Max. conductor DC resistance R20 at 20 °C per ASTM B172 / B8 (bare copper).
  • Minimum bending radius calculated at 12 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer ASTM B172 / B8 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation check100% Cu tape continuity & wall thicknessPer production lot
Flame & environmental qualificationIEEE 1202 / FT4 Flame · UL Oil Res I/IIType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1569 Type MCUL 44 XHHW-2CSA C22.2 No. 131 Teck/ACICEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

VFDAP 600/1000V Type MC 600/1000 V TEBAOFLEX.COM [UL 1569 Type MC] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes VFDAP 600/1000V Type MC suitable for 600/1000 V industrial installations?
VFDAP 600/1000V Type MC combines bare copper conductors, UL 44 XHHW-2 thermoset XLPE (90 °C wet/dry), and Helical bare copper tape shield (100% radial coverage) inside a Black UV- & oil-resistant PVC overall jacket over armor. UL 1569 Type MC aluminum armor eliminates rigid steel conduit while maintaining 100% EMC containment.
Can VFDAP 600/1000V Type MC operate inside continuous drag chains or moving axes?
No. VFDAP 600/1000V Type MC is engineered for stationary tray, conduit, or machine-frame routing at 12 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of VFDAP 600/1000V Type MC be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany VFDAP 600/1000V Type MC?
VFDAP 600/1000V Type MC conforms to UL 1569 Type MC, UL 44 XHHW-2, CSA C22.2 No. 131 Teck/ACIC (IEEE 1202 / FT4 Flame) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for VFDAP 600/1000V Type MC

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

VFDAP 600/1000 V Type MC Armored VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote