Fixed installation
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Product
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Typical values for this cable type, based on Reference specification per UL 1277 TC-ER 2000V / UL 44 RHW-2 (29541 Series 2000V UL 1277 TC-ER) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Low-impedance shielding contains high-frequency common-mode currents and dV/dt voltage spikes.
Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.
Outer sheath compound resists industrial cutting fluids, mineral oils and outdoor sunlight.
Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.
Use TRA 0.6/1 kV PUR Reeling CableChemical- and mud-resistant 000 V XLPE/PVC build suits offshore topside process modules, hazardous decks, and utility skids.
Construction
Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

| # | Layer | Material & reference |
|---|---|---|
| 1 | 4×4 AWG (7×19×25) Tinned Copper (3P+G) | 7×19×25 AWG (133 Strands) Tinned Copper (3 Phase + 1 Full GND) |
| 2 | 2000V Grade Thick-Wall RHW-2 XLPE Insulation | 2.03mm Corona-Resistant XLPE for High dV/dt Spikes |
| 3 | 100% Foil + 85% Tinned Copper Braid + #4 Drain | 4 AWG Tinned Cu Drain + Al/Mylar Foil + 85% Tinned Cu Braid |
| 4 | Heavy-Duty Black Sunlight-Resistant PVC Jacket | UL 1277 Type TC-ER 2000V Oil & Wet Rated PVC Sheath (30.50 mm OD) |
7×19×25 AWG Tinned Cu + 2.03mm 2kV XLPE + Foil/TCWB · Outer diameter 30.5 mm.
133×27 AWG Tinned Cu + 2kV RHW-2 XLPE + Foil/TCWB · Outer diameter 25.91 mm.
7×19×23 AWG Tinned Cu + 2kV RHW-2 XLPE + Foil/TCWB · Outer diameter 34.8 mm.
Technical data
Sizes
Representative configurations from the series specification; select a row to prefill the quotation tool.
| Configuration | Conductor & shield | Insulation / wall | Outer sheath | Outer diameter mm | Min. bend radius mm | Max. conductor resistance @ 20 °C Ω/km | Copper weight kg/km | Cable weight kg/km | Key electrical / optical rating | Part designation | Enquiry |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 29541 Series 2000V UL 1277 TC-ER | |||||||||||
| 4 × 4 AWG (21.2 mm² · 7×19×25 AWG) | 7×19×25 AWG Tinned Cu + 2.03mm 2kV XLPE + Foil/TCWB | 2.03mm Corona-Resistant XLPE for High dV/dt Spikes | Industrial PVC | 30.5 | 366 | 0.85 | 1,120.0 | 1,580 | 2,000 V UL 1277 TC-ER (95 A · 2 kV RHW-2) | 29541 4G4 AWG (3×4 AWG + 1×4 AWG G/Y) 2000V | |
| 4 × 6 AWG (13.3 mm² · 133×27 AWG) | 133×27 AWG Tinned Cu + 2kV RHW-2 XLPE + Foil/TCWB | 2.03mm Corona-Resistant XLPE for High dV/dt Spikes | Industrial PVC | 25.9 | 311 | 1.35 | 725.0 | 1,085 | 2,000 V UL 1277 TC-ER (75 A · 2 kV RHW-2) | 29540 4G6 AWG (3×6 AWG + 1×6 AWG G/Y) 2000V | |
| 4 × 2 AWG (33.6 mm² · 7×19×23 AWG) | 7×19×23 AWG Tinned Cu + 2kV RHW-2 XLPE + Foil/TCWB | 2.03mm Corona-Resistant XLPE for High dV/dt Spikes | Industrial PVC | 34.8 | 418 | 0.54 | 1,690.0 | 2,240 | 2,000 V UL 1277 TC-ER (130 A · 2 kV RHW-2) | 29542 4G2 AWG (3×2 AWG + 1×2 AWG G/Y) 2000V | |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & continuity | Within maximum Ω/km limit at 20 °C | Every manufactured drum length |
| Dielectric withstand / spark test | No breakdown across insulation or shield | Every manufactured drum length |
| Sample tests | ||
| Vertical flame propagation & jacket qualification | Self-extinguishing within standard char limit | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.