VFD XLPE 2KV TR (869) Large-AWG VFD CableLarge-AWG 2,000 V RHW-2 symmetrical Type TC-ER VFD cable

Heavy-gauge 2,000 V UL 1277 Type TC-ER / RHW-2 symmetrical VFD feeder cable (869 series) with annealed bare copper conductors, heavy-wall 90 °C XLPE insulation, three bare copper grounds, 5-mil bare copper tape shield, and oil/UV-resistant PVC jacket.

Low-EMC design
EMC screen
Oil-resistant
Flame-retardant
Order designation
VFD XLPE 2KV TR (869) 3×2/0 AWG + 3×6 AWG
Outer Ø
37.7 mm
Max. R20
0.261 Ω/km
Weight
3,979 kg/km
Min. bend R
452 mm
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
2,000 V (2 kV)
UL 1277 Type TC-ER / UL 44 RHW-2
EMC screening
5-mil Cu tape
100% helically overlapped bare Cu tape
Conductor temp.
+90 °C wet/dry
Heavy-wall 2 kV RHW-2 XLPE
Grounding
3 × Bare Cu
Symmetrical grounds in interstices
Min. bend radius
12 × OD
Large-AWG fixed tray & burial routing
Size range
8 AWG–500 MCM
High-power large-AWG drive feeders

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHW-2 · IEEE 1202 / FT4 · NFPA 79 — confirmed in the datasheet and quotation for your order.

Application fit

Is VFD XLPE 2KV TR (869) right for your machine?

Heavy-gauge 2,000 V UL 1277 Type TC-ER / RHW-2 symmetrical VFD feeder cable (869 series) with annealed bare copper conductors, heavy-wall 90 °C XLPE insulation, three bare copper grounds, 5-mil bare copper tape shield, and oil/UV-resistant PVC jacket.

VFD inverter to AC motor screened feeder

Suitable

Large-AWG (8 AWG–500 kcmil) symmetrical 3+3 design and 5-mil Cu tape eliminate bearing currents on > 100 HP drives.

High-HP machinery & NFPA 79 MCC

Suitable

NFPA 79 and UL Type TC-ER compliance targets heavy extruders, compressors, and high-horsepower MCC feeders.

Motor stator, traction & converter leads

Suitable

Heavy-wall 2 kV RHW-2 XLPE resists corona discharge and standing-wave peaks on long feeder runs.

Fixed installation

Suitable

Oil-, UV-, and direct-burial black RAL 9005 PVC jacket passes IEEE 1202 / FT4 tray flame testing.

Energy chain / drag chain

Not suitable

Large-AWG copper-tape tray cable is for stationary installation, not continuous drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not engineered for motorised cable drums; choose a rubber reeling cable for mobile spooling.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableHigh-horsepower industrial AC drivesHeavy manufacturing & extrudersCompressors, pumps & HVAC chillersSteel, cement & mining plantsNFPA 79 machinery & NEC trays

Construction

Layer by layer

Shown: VFD XLPE 2KV TR (869) 3×2/0 AWG + 3×6 AWG — annealed bare copper 2 kV RHW-2 XLPE phases and three symmetrical bare copper grounds inside an uncoated 5-mil helical copper tape shield and black PVC jacket.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorUncoated annealed stranded bare copper (ASTM B8 Class B)ASTM B3 / B8 large-AWG bare copper
2Phase insulation2 kV heavy-wall RHW-2 XLPE (Black consecutively numbered)UL 44 RHW-2 + 3 × bare Cu interstitial grounds
3Fillers & separatorExtruded/cabled interstitial fillers & separator tapeBalanced circular large-AWG assembly
45-mil copper tape shieldUncoated 5-mil helically overlapped bare copper tape (100%)Low-impedance VFD EMI shield
5Outer jacketBlack oil-, UV- & direct-burial thermoplastic PVC jacket (RAL 9005)UL 1277 Type TC-ER / NFPA 79

VFD XLPE 2KV TR (869 Series)

Three black numbered heavy-wall RHW-2 XLPE phases + three symmetrical bare Cu grounds under 5-mil bare Cu tape (8 AWG–500 kcmil).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHW-2 · IEEE 1202 / FT4 · NFPA 79. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
2,000 V (2 kV) AC
Conductor class
ASTM B8 Class B annealed bare Cu
EMC shield
100% uncoated 5-mil bare Cu tape
Grounding system
3 × symmetrical bare Cu in interstices

Thermal

Max. conductor temp.
+90 °C wet or dry (RHW-2)
Ambient temp. (fixed)
−40 °C to +90 °C
Min. bending radius
12 × OD (Cu-tape shielded)

Resistance

Flame test
IEEE 1202 / CSA FT4 / UL 1685
Environmental ratings
Oil-, UV- & Direct-Burial RAL 9005
Machinery compliance
NFPA 79 · NEC Class I Div 2

Sizes

Large-AWG 3C+3G (869 Series)
Phase + 3×
Ground (AWG)
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
12×D mm
3×8 AWG + 3×14 AWG20.82.100352759250
3×6 AWG + 3×12 AWG22.91.3205281,048275
3×4 AWG + 3×12 AWG26.60.8327561,469319
3×2 AWG + 3×10 AWG31.00.5231,1642,168372
3×1 AWG + 3×8 AWG33.00.4151,4972,682396
3×1/0 AWG + 3×6 AWG35.20.3291,9443,355422
3×2/0 AWG + 3×6 AWG37.70.2612,3333,979452
3×3/0 AWG + 3×4 AWG41.20.2073,0445,077494
3×4/0 AWG + 3×4 AWG44.40.1643,6646,059533
3×250 kcmil + 3×4 AWG48.50.1394,2127,028582
3×350 kcmil + 3×2 AWG54.20.0995,9599,659650
3×500 kcmil + 3×2 AWG61.40.0708,07112,931737
  • Conductor max. DC resistance R20 follows ASTM B8 Class B annealed bare copper at 20 °C.
  • Designed for high-power industrial VFD feeders requiring NFPA 79 machinery compliance, exposed-run TC-ER approval, and direct burial.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric testPer UL 44 RHW-2 2,000 V ratingEvery manufactured reel
Conductor DC resistance checkPer ASTM B8 Class B at 20 °CEvery reel length
Sample tests
TC-ER crush, impact & tape overlapUL 1277 crush/impact & 100% tape lapPer production lot
Vertical tray flame testIEEE 1202 / FT4 / UL 1685Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ER (2,000 V) · UL 44 RHW-2NFPA 79 Industrial Machinery CompliantIEEE 1202 / FT4 · Sunlight, Oil & Direct Burial

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

VFD XLPE 2KV TR (869) TEBAOFLEX.COM UL 1277 TC-ER RHW-2 2000V NFPA 79 [Size]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is the VFD XLPE 2KV TR (869) series tailored for?
The 869 large-AWG series (8 AWG through 500 kcmil) targets high-horsepower industrial VFD feeders on extruders, heavy compressors, pumps, and NFPA 79 factory equipment where high ampacity and symmetrical 3+3 ground balance are critical.
Does VFD XLPE 2KV TR (869) meet NFPA 79 requirements for industrial machinery?
Yes. Its UL 1277 Type TC-ER construction with 2 kV RHW-2 XLPE insulation, oil/UV-resistant jacket, and symmetrical copper-tape shielding satisfies NFPA 79 exposed-run machine wiring provisions.
How should the three interstitial bare copper grounds be connected?
Twist and crimp all three bare copper grounding conductors together to the drive and motor protective-earth lugs while bonding the 5-mil bare copper tape shield circumferentially with an EMC gland or constant-force spring.
How should the EMC shield and symmetrical grounds of VFD XLPE 2KV TR (869) be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for VFD XLPE 2KV TR (869)

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

VFD XLPE 2KV TR (869) Large-AWG VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote