VFD-THIN 600/1000 V TC-ER Thin-Wall VFD CableReduced-diameter 600/1000 V TC-ER symmetrical VFD cable for tight glands

VFD-THIN 600/1000 V TC-ER pairs high-dielectric thin-wall XLPE insulation with bare copper conductors, three symmetrical grounds, and dual EMC screening to save tray space and ease conduit pulling.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
VFD-THIN 600/1000V TC-ER 3×4 AWG + 3×12 AWG
Outer Ø
21.3 mm
Max. R20
0.832 Ω/km
Weight
1,232 kg/km
Min. bend R
170 mm
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
600/1000 V
AC test voltage 4 kV AC
EMC screening
Foil + TCWB
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -20 °C to +90 °C
Min. bend radius
8 × OD
Fixed routing in trays & ducts
Conductor
Bare Cu · Cl.B
ASTM B172 / B8 copper
Size range
14 AWG–500 kcmil
12 standard configurations

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 2277 Type WTTC · UL 44 XHHW-2 — confirmed in the datasheet and quotation for your order.

Application fit

Is VFD-THIN 600/1000V TC-ER right for your machine?

VFD-THIN 600/1000 V TC-ER pairs high-dielectric thin-wall XLPE insulation with bare copper conductors, three symmetrical grounds, and dual EMC screening to save tray space and ease conduit pulling.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 600/1000 V XLPE/PVC construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 600/1000 V XLPE/PVC geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Control cabinet & internal panel wiring

Suitable

Compact flame-retardant 600/1000 V XLPE/PVC geometry routes neatly through dense switchgear ducts, control cabinets, and DIN-rail terminals.

Dual-tier power & PLC tray

Suitable

Screened 600/1000 V XLPE/PVC construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Energy chain / drag chain

Not suitable

600/1000 V XLPE/PVC construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

600/1000 V XLPE/PVC build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of VFD-THIN 600/1000V TC-ER: bare copper conductors, Thin-wall high-dielectric thermoset XLPE (90 °C), 100% foil + ≥ 85% tinned copper braid shield, and Black reduced-OD oil- & UV-resistant PVC outer jacket.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorASTM B8 Class B stranded bare annealed copperASTM B8 Class B / UL 44
2Core insulationThin-wall high-dielectric thermoset XLPE (90 °C)UL 1277 Type TC-ER
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeUL 1277 Type TC-ER
4EMC metallic screen100% foil + ≥ 85% tinned copper braid shieldEMC ≥ 85% / 100% foil
5Outer sheathBlack reduced-OD oil- & UV-resistant PVC outer jacketUL 1685 / FT4 Flame

VFD-THIN 600/1000V TC-ER 3C + 3G Symmetrical

Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 2277 Type WTTC · UL 44 XHHW-2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
600/1000 V
AC test voltage
4 kV AC / 5 min
Conductor class
ASTM B8 Class B bare Cu
EMC screen
100% foil + ≥ 85% tinned copper braid shield
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-20 °C to +90 °C
Short-circuit temp.
+250 °C (5 s)
Min. bending radius
8 × OD (fixed)

Resistance

Flame retardance
UL 1685 / FT4 Flame
Oil & chemical perf.
UL Oil Res I/II
Environmental / EMC
Sunlight Resistant
Outer sheath
Black reduced-OD oil- & UV-resistant PVC

Sizes

3C + 3G Symmetrical (AWG/kcmil)
Cores ×
AWG/kcmil
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
8×D mm
3×14 AWG + 3×18 AWG10.28.45010820682
3×12 AWG + 3×16 AWG11.25.31015828490
3×10 AWG + 3×14 AWG12.53.340236404100
3×8 AWG + 3×14 AWG15.62.100331582125
3×6 AWG + 3×12 AWG17.61.320505848141
3×4 AWG + 3×12 AWG21.30.8327321,232170
3×2 AWG + 3×10 AWG25.50.5231,1381,879204
3×1/0 AWG + 3×6 AWG29.70.3291,9173,027238
3×2/0 AWG + 3×6 AWG32.10.2612,3053,620257
3×4/0 AWG + 3×4 AWG38.80.1643,6335,629310
3×350 kcmil + 3×2 AWG47.90.0995,9239,073383
3×500 kcmil + 3×2 AWG55.00.0708,03212,247440
  • Max. conductor DC resistance R20 at 20 °C per ASTM B172 / B8 (bare copper).
  • Minimum bending radius calculated at 8 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer ASTM B172 / B8 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation checkFoil + TCWB continuity & wall thicknessPer production lot
Flame & environmental qualificationUL 1685 / FT4 Flame · UL Oil Res I/IIType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ERUL 2277 Type WTTCUL 44 XHHW-2EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

VFD-THIN 600/1000V TC-ER 600/1000 V TEBAOFLEX.COM [UL 1277 Type TC-ER] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes VFD-THIN 600/1000V TC-ER suitable for 600/1000 V industrial installations?
VFD-THIN 600/1000V TC-ER combines bare copper conductors, Thin-wall high-dielectric thermoset XLPE (90 °C), and 100% foil + ≥ 85% tinned copper braid shield inside a Black reduced-OD oil- & UV-resistant PVC outer jacket. Thin-wall geometry fits compact EMC cable glands and high-density drive control panels.
Can VFD-THIN 600/1000V TC-ER operate inside continuous drag chains or moving axes?
No. VFD-THIN 600/1000V TC-ER is engineered for stationary tray, conduit, or machine-frame routing at 8 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of VFD-THIN 600/1000V TC-ER be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany VFD-THIN 600/1000V TC-ER?
VFD-THIN 600/1000V TC-ER conforms to UL 1277 Type TC-ER, UL 2277 Type WTTC, UL 44 XHHW-2 (UL 1685 / FT4 Flame) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for VFD-THIN 600/1000V TC-ER

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

VFD-THIN 600/1000 V TC-ER Thin-Wall VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote