Contact

VFD Symmetrical XLPE TR-3568 1000 V Cable1000 V symmetrical XLPE tinned-copper industrial VFD power cable

VFD Symmetrical XLPE TR-3568 pairs flexible tinned copper phases with three symmetrical interstitial grounds, low-capacitance XLPE insulation, and dual foil/braid shielding for heavy-duty VFD feeders.

Low-EMC design
EMC screen
Flame-retardant
Outdoor & humid
Order designation
VFD XLPE TR-3568 3×4 AWG + 3×12 AWG
Outer Ø
24.0 mm
Max. R20
0.892 Ω/km
Weight
1,322 kg/km
Min. bend R
240 mm
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
1000 V
AC test voltage 4 kV AC
EMC screening
Foil + TCWB
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -25 °C to +90 °C
Min. bend radius
10 × OD
Fixed routing in trays & ducts
Conductor
Tinned Cu · Cl.K
ASTM B172 / B8 copper
Size range
14 AWG–500 kcmil
12 standard configurations

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 2277 Type WTTC · ICEA S-95-658 — confirmed in the datasheet and quotation for your order.

Application fit

Is VFD XLPE TR-3568 right for your machine?

VFD Symmetrical XLPE TR-3568 pairs flexible tinned copper phases with three symmetrical interstitial grounds, low-capacitance XLPE insulation, and dual foil/braid shielding for heavy-duty VFD feeders.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 1000 V XLPE/CPE construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 1000 V XLPE/CPE geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Cable trench & heavy drive bay

Suitable

Rugged 1000 V XLPE/CPE construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.

Process pump & compressor skid

Suitable

Durable 1000 V XLPE/CPE construction powers industrial process pumps, boosters, and compressor skids under continuous plant duty.

Energy chain / drag chain

Not suitable

1000 V XLPE/CPE construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

1000 V XLPE/CPE build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesOil & Gas CableVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of VFD XLPE TR-3568: tinned copper conductors, 1000 V low-capacitance thermoset XLPE, 100% Al/polyester foil + ≥ 85% tinned copper braid shield, and Black UV- & oil-resistant industrial PVC/CPE jacket.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorASTM B172 Class K flexible tinned annealed copperASTM B172 Class K / UL 1277
2Core insulation1000 V low-capacitance thermoset XLPEUL 1277 Type TC-ER
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeUL 1277 Type TC-ER
4EMC metallic screen100% Al/polyester foil + ≥ 85% tinned copper braid shieldEMC ≥ 85% / 100% foil
5Outer sheathBlack UV- & oil-resistant industrial PVC/CPE jacketIEEE 1202 / FT4 Flame

VFD XLPE TR-3568 3C + 3G Symmetrical

Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 2277 Type WTTC · ICEA S-95-658. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
1000 V
AC test voltage
4 kV AC / 5 min
Conductor class
ASTM B172 Class K tinned Cu
EMC screen
100% Al/polyester foil + ≥ 85% tinned
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-25 °C to +90 °C
Short-circuit temp.
+250 °C (5 s)
Min. bending radius
10 × OD (fixed)

Resistance

Flame retardance
IEEE 1202 / FT4 Flame
Oil & chemical perf.
UL Oil Res I/II
Environmental / EMC
Direct Burial & Sun Res
Outer sheath
Black UV- & oil-resistant industrial

Sizes

3C + 3G Symmetrical (AWG/kcmil)
Cores ×
AWG/kcmil
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
3×14 AWG + 3×18 AWG12.39.070114244123
3×12 AWG + 3×16 AWG13.35.710164325133
3×10 AWG + 3×14 AWG14.73.590243451147
3×8 AWG + 3×14 AWG18.12.260338646181
3×6 AWG + 3×12 AWG20.21.420513922202
3×4 AWG + 3×12 AWG24.00.8927401,322240
3×2 AWG + 3×10 AWG28.50.5611,1471,996285
3×1/0 AWG + 3×6 AWG32.90.3531,9263,169329
3×2/0 AWG + 3×6 AWG35.50.2802,3153,782355
3×4/0 AWG + 3×4 AWG42.40.1763,6435,832424
3×350 kcmil + 3×2 AWG51.90.1075,9359,348519
3×500 kcmil + 3×2 AWG59.40.0758,04412,590594
  • Max. conductor DC resistance R20 at 20 °C per ASTM B172 / B8 (tinned copper).
  • Minimum bending radius calculated at 10 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer ASTM B172 / B8 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation checkFoil + TCWB continuity & wall thicknessPer production lot
Flame & environmental qualificationIEEE 1202 / FT4 Flame · UL Oil Res I/IIType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ERUL 2277 Type WTTCICEA S-95-658EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

VFD XLPE TR-3568 1000 V TEBAOFLEX.COM [UL 1277 Type TC-ER] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes VFD XLPE TR-3568 suitable for 1000 V industrial installations?
VFD XLPE TR-3568 combines tinned copper conductors, 1000 V low-capacitance thermoset XLPE, and 100% Al/polyester foil + ≥ 85% tinned copper braid shield inside a Black UV- & oil-resistant industrial PVC/CPE jacket. Low-capacitance XLPE minimizes charging current on long cable runs from MCC to motor.
Can VFD XLPE TR-3568 operate inside continuous drag chains or moving axes?
No. VFD XLPE TR-3568 is engineered for stationary tray, conduit, or machine-frame routing at 10 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of VFD XLPE TR-3568 be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany VFD XLPE TR-3568?
VFD XLPE TR-3568 conforms to UL 1277 Type TC-ER, UL 2277 Type WTTC, ICEA S-95-658 (IEEE 1202 / FT4 Flame) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for VFD XLPE TR-3568

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

VFD Symmetrical XLPE TR-3568 1000 V Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote