VFD inverter to AC motor screened feeder
Low-capacitance 600/1000 V XLPE/PVC construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Product
TC-ER 600/1000 V Tri-Ground VFD uses stranded bare copper phases with three symmetrical interstitial bare grounds and dual EMC screening to balance ground impedance and protect AC motor bearings.
Typical values for this cable type, based on UL 1277 Type TC-ER · UL 2277 Type WTTC · ICEA S-95-658 — confirmed in the datasheet and quotation for your order.
Application fit
TC-ER 600/1000 V Tri-Ground VFD uses stranded bare copper phases with three symmetrical interstitial bare grounds and dual EMC screening to balance ground impedance and protect AC motor bearings.
Low-capacitance 600/1000 V XLPE/PVC construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Balanced 600/1000 V XLPE/PVC geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.
High-capacity 600/1000 V XLPE/PVC feeder connects motor control centers (MCC) cleanly to heavy plant machinery and main distribution panels.
Moisture-resistant 600/1000 V XLPE/PVC protection allows direct-burial trenching, underground sand beds, and damp concrete ducts.
600/1000 V XLPE/PVC construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR600/1000 V XLPE/PVC build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.
Use RG / RG-D (N)SHTOEU-JConstruction
Representative construction of TC-ER 600/1000V Tri-Ground VFD: bare copper conductors, UL 44 XHHW-2 thermoset XLPE (90 °C wet/dry), 100% foil + ≥ 85% tinned copper braid + 3 symmetrical bare Cu grounds, and Black UV- & oil-resistant PVC outer jacket.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | ASTM B8 Class B stranded bare annealed copperASTM B8 Class B / UL 44 |
| 2 | Core insulation | UL 44 XHHW-2 thermoset XLPE (90 °C wet/dry)UL 1277 Type TC-ER |
| 3 | Core assembly & separator | Concentric cabled assembly with low-friction fleece or polyester binder tapeUL 1277 Type TC-ER |
| 4 | EMC metallic screen | 100% foil + ≥ 85% tinned copper braid + 3 symmetrical bare Cu groundsEMC ≥ 85% / 100% foil |
| 5 | Outer sheath | Black UV- & oil-resistant PVC outer jacketIEEE 1202 / FT4 Flame |
Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.
Technical data
Sizes
| Cores × AWG/kcmil | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 10×D mm |
|---|---|---|---|---|---|
| 3×14 AWG + 3×18 AWG | 12.1 | 8.450 | 113 | 240 | 121 |
| 3×12 AWG + 3×16 AWG | 13.1 | 5.310 | 163 | 320 | 131 |
| 3×10 AWG + 3×14 AWG | 14.4 | 3.340 | 242 | 445 | 144 |
| 3×8 AWG + 3×14 AWG | 17.7 | 2.100 | 336 | 634 | 177 |
| 3×6 AWG + 3×12 AWG | 19.8 | 1.320 | 511 | 909 | 198 |
| 3×4 AWG + 3×12 AWG | 23.4 | 0.832 | 738 | 1,301 | 234 |
| 3×2 AWG + 3×10 AWG | 27.8 | 0.523 | 1,145 | 1,968 | 278 |
| 3×1/0 AWG + 3×6 AWG | 32.0 | 0.329 | 1,923 | 3,127 | 320 |
| 3×2/0 AWG + 3×6 AWG | 34.5 | 0.261 | 2,312 | 3,733 | 345 |
| 3×4/0 AWG + 3×4 AWG | 41.1 | 0.164 | 3,640 | 5,757 | 411 |
| 3×350 kcmil + 3×2 AWG | 50.3 | 0.099 | 5,930 | 9,235 | 503 |
| 3×500 kcmil + 3×2 AWG | 57.5 | 0.070 | 8,039 | 12,439 | 575 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC high-voltage dielectric test | 4 kV AC for 5 min without breakdown | Every manufactured drum |
| Conductor DC resistance test | Per ASTM B172 / B8 at 20 °C | Every drum length |
| Sample tests | ||
| EMC screen coverage & insulation check | Foil + TCWB continuity & wall thickness | Per production lot |
| Flame & environmental qualification | IEEE 1202 / FT4 Flame · UL Oil Res I/II | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.