Screened power & VFD / motor supply cablesUL 1277 TC-ER · IEEE 12022 kV FR-XLPE (VW-1 · ICEA M4)5-mil Cu Tape · Lead-Free PVC

SPEC 4580 2000 V TC-ER Symmetrical VFD Cable2 kV VW-1 FR-XLPE 5-mil copper tape TC-ER VFD cable

2,000 V UL 1277 Type TC-ER VFD tray cable with Class B bare copper conductors, VW-1 flame-retardant XLPE insulation (ICEA Method 4 black numbered), three bare copper grounds, 5-mil ≥ 50%-lap copper tape, and lead-free PVC jacket.

Low-EMC design
EMC screen
Outdoor & humid
Flame-retardant
Order designation
SPEC 4580 2000V 3×1/0 AWG + 3×6 AWG
Outer Ø
35.1 mm
Max. R20
0.329 Ω/km
Weight
3,317 kg/km
Min. bend R
421 mm
All sizes (15)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
2,000 V (2 kV)
90 °C wet/dry UL 1277 TC-ER
Insulation grade
FR-XLPE (VW-1)
ICEA Method 4 black numbered phases
EMC screening
5-mil Cu tape
Helical bare Cu tape (≥ 50% overlap)
Conductor class
Class B bare Cu
ASTM B8 stranded annealed copper
Min. bend radius
12 × OD
Fixed tray, conduit & direct burial
Size range
14 AWG–500 MCM
3C + 3× bare Cu · Lead-free PVC

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHH/RHW-2 · IEEE 1202 · ICEA M4 — confirmed in the datasheet and quotation for your order.

Application fit

Is SPEC 4580 2000V TC-ER right for your machine?

2,000 V UL 1277 Type TC-ER VFD tray cable with Class B bare copper conductors, VW-1 flame-retardant XLPE insulation (ICEA Method 4 black numbered), three bare copper grounds, 5-mil ≥ 50%-lap copper tape, and lead-free PVC jacket.

VFD inverter to AC motor screened feeder

Suitable

5-mil ≥ 50%-lap bare copper tape bonded to three bare copper grounds provides 100% VFD EMI shielding.

Motor stator, traction & converter leads

Suitable

Individual VW-1 flame-retardant XLPE phases (ICEA Method 4) enhance fire safety inside MCC cabinets.

Direct-burial & wet conduit run

Suitable

Lead-free RoHS sunlight-resistant PVC jacket and 90 °C wet/dry XLPE support direct burial and ducts.

Fixed installation

Suitable

UL 1277 Type TC-ER and IEEE 1202 / FT4 rated for exposed runs and Class I Div 2 plant cable trays.

Energy chain / drag chain

Not suitable

Class B bare copper and 5-mil copper tape are for fixed installations, not continuous drag chains.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not rated for motorised cable drums; specify a rubber reeling cable for reeling duty.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableHeavy industrial VFD drive roomsPulp, paper & steel millsChemical & petrochemical refineriesWater & power plant auxiliariesNEC Class I Div 2 tray systems

Construction

Layer by layer

Shown: SPEC 4580 2000 V TC-ER 3×1/0 AWG + 3×6 AWG — Class B bare copper VW-1 FR-XLPE phases (ICEA Method 4) and three uninsulated bare copper grounds inside 5-mil ≥ 50%-lap Cu tape and lead-free PVC jacket.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass B stranded bare annealed copperASTM B3 / B8 Class B
2Phase insulation2 kV flame-retardant XLPE (VW-1, ICEA Method 4 black numbered)UL 44 VW-1 + 3 × bare Cu grounds
3Fillers & core wrapPolypropylene fillers & flame-retardant core wrapSymmetrical 3+3 round core assembly
45-mil copper tape shield5-mil helically applied annealed bare copper tape (≥ 50% overlap)Continuous 100% double-lap EMI shield
5Outer jacketBlack lead-free sunlight-resistant direct-burial PVCUL 1277 Type TC-ER · RoHS / IEEE 1202

SPEC 4580 2000 V (ICEA M4)

Three black numbered VW-1 FR-XLPE phases (ICEA Method 4) + three bare Cu grounds under 5-mil ≥ 50%-lap Cu tape (14 AWG–500 kcmil).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHH/RHW-2 · IEEE 1202 · ICEA M4. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
2,000 V (2 kV) AC
Conductor class
ASTM B8 Class B bare copper
Phase identification
ICEA Method 4 (black numbered)
EMC shield
5-mil bare Cu tape (≥ 50% overlap)

Thermal

Max. conductor temp.
+90 °C wet or dry (FR-XLPE)
Ambient temp. (fixed)
−40 °C to +90 °C
Min. bending radius
12 × OD (Cu-tape shielded)

Resistance

Core / tray flame test
VW-1 cores · IEEE 1202 / FT4 tray
Jacket formulation
Lead-free sunlight & direct-burial PVC
Hazardous locations
NEC Class I Div 2

Sizes

3C+3G Symmetrical (ICEA Method 4)
Phase + 3×
Ground (AWG)
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
12×D mm
3×14 AWG + 3×18 AWG15.68.450129336187
3×12 AWG + 3×16 AWG16.65.310179422199
3×10 AWG + 3×14 AWG17.93.340258553215
3×8 AWG + 3×14 AWG20.72.100352749248
3×6 AWG + 3×12 AWG22.81.3205271,033274
3×4 AWG + 3×12 AWG26.50.8327561,451318
3×2 AWG + 3×10 AWG30.90.5231,1642,142371
3×1 AWG + 3×8 AWG32.90.4151,4972,651395
3×1/0 AWG + 3×6 AWG35.10.3291,9443,317421
3×2/0 AWG + 3×6 AWG37.60.2612,3333,934451
3×3/0 AWG + 3×4 AWG41.10.2073,0445,021493
3×4/0 AWG + 3×4 AWG44.30.1643,6645,993532
3×250 kcmil + 3×4 AWG48.40.1394,2126,952581
3×350 kcmil + 3×2 AWG54.10.0995,9599,556649
3×500 kcmil + 3×2 AWG61.30.0708,07012,793736
  • Conductor max. DC resistance R20 follows ASTM B8 Class B bare annealed copper at 20 °C.
  • Individual phase cores pass UL VW-1 vertical wire flame testing in addition to IEEE 1202 / FT4 cable tray flame testing.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric testPer UL 44 2,000 V RHH/RHW-2 ratingEvery manufactured reel
Conductor DC resistance checkPer ASTM B8 Class B at 20 °CEvery reel length
Sample tests
5-mil Cu tape lap & VW-1 core test≥ 50% copper tape lap & VW-1 core checkPer production lot
Vertical tray flame testIEEE 1202 / UL 1685 / CSA FT4Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ER (2,000 V) · UL 44 RHH/RHW-2 VW-1ICEA S-95-658 · ICEA Method 4 IdentificationIEEE 1202 / FT4 · Lead-Free RoHS · Direct Burial

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

SPEC 4580 2000V TC-ER TEBAOFLEX.COM UL 1277 VW-1 IEEE 1202 [Size]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

How does SPEC 4580 compare with SPEC 45451?
SPEC 4580 uses VW-1 flame-retardant XLPE with ICEA Method 4 black numbered phases and a lead-free direct-burial PVC jacket, whereas SPEC 45451 uses ICEA Method 3 coloured phases (Black/Red/Blue) and a silicone-free oil-resistant PVC jacket.
Why specify VW-1 flame-retardant XLPE insulation on VFD cables?
Once the outer jacket and shield are stripped back inside a drive cabinet or motor box, VW-1 rated phase insulation prevents flame propagation along exposed individual leads.
Does SPEC 4580 support direct burial and outdoor sunlight exposure?
Yes. The lead-free black PVC outer jacket is UL 1277 listed for sunlight resistance, direct burial, wet locations, and exposed-run tray transitions.
How should the EMC shield and symmetrical grounds of SPEC 4580 2000V TC-ER be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for SPEC 4580 2000V TC-ER

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

SPEC 4580 2000 V TC-ER Symmetrical VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote