BPYJVP 0.6/1 kV Symmetrical Shielded VFD Cable90 °C XLPE 3+3 symmetrical VFD motor cable with copper braid EMC screen

Symmetrical 3+3 low-voltage VFD motor supply cable rated 0.6/1 kV with Class 5 bare copper conductors, 90 °C XLPE insulation, overall bare copper wire braid EMC screen (≥ 85%), and black flame-retardant ST2 PVC sheath.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
BPYJVP 3×35 + 3×6
Outer Ø
31.0 mm
Max. R20
0.554 Ω/km
Weight
2,200 kg/km
Min. bend R
465 mm
All sizes (14)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 3.5 kV / 5 min
EMC screening
≥ 85% Cu braid
Overall bare Cu wire braid (P)
Conductor temp.
+90 °C max.
+250 °C short-circuit (5 s)
Ambient temp.
−15…+70 °C
fixed (≥ 0 °C during installation)
Min. bend radius
15 × OD
fixed laying (12 × OD after clamping)
Size range
2.5–240 mm²
3+3 symmetrical split-earth range

Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228 — confirmed in the datasheet and quotation for your order.

Application fit

Is BPYJVP 0.6/1 kV right for your machine?

Symmetrical 3+3 low-voltage VFD motor supply cable rated 0.6/1 kV with Class 5 bare copper conductors, 90 °C XLPE insulation, overall bare copper wire braid EMC screen (≥ 85%), and black flame-retardant ST2 PVC sheath.

VFD inverter to AC motor screened feeder

Suitable

Symmetrical 3+3 geometry and ≥ 85% bare copper braid balance phase impedance and cut PWM common-mode noise.

Motor stator, traction & converter leads

Suitable

Class 5 bare copper and three interstitial split earths simplify motor box routing and protect bearings.

Process pump & compressor skid

Suitable

90 °C XLPE insulation and flexible Class 5 stranding fit industrial centrifugal pump and compressor skids.

Fixed installation

Suitable

Black ST2 flame-retardant PVC outer sheath installs cleanly on indoor trays, racks, and cable trenches.

Energy chain / drag chain

Not suitable

ST2 PVC sheath and fixed-lay 3+3 geometry are not rated for continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not engineered for motorised drum reeling or tensile winding; specify rubber reeling cables instead.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableIndustrial VFD motor drivesMetallurgy & rolling millsPumps, fans & compressorsChemical & process plantsAutomated manufacturing lines

Construction

Layer by layer

Shown: BPYJVP 0.6/1 kV 3×35 + 3×6 mm² — three Class 5 bare copper phase cores and three symmetrical green/yellow split earth conductors inside a bare copper wire braid screen.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 5 flexible bare annealed copperGB/T 3956 / IEC 60228 Class 5
2Phase & earth insulation90 °C cross-linked polyethylene (XLPE), GB/T 6995 coloursYellow, green, red + 3 × green/yellow split earths
3Fillers & binder tapeNon-hygroscopic polypropylene (PP) fillers & polyester binder tapeSymmetrical 3+3 round cabled core
4EMC braid screenOverall bare annealed copper wire braid (P, ≥ 85% coverage)TICW/06-2009 high-frequency EMC containment
5Outer sheathBlack flame-retardant PVC compound (ST2)GB/T 12706.1 / IEC 60502-1 ST2

BPYJVP 3+3 Symmetrical

Three phase cores (yellow, green, red) plus three symmetrically laid green/yellow split earth cores (2.5–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV
AC test voltage
3.5 kV / 5 min
EMC screen coverage
≥ 85% bare annealed copper braid
Core symmetry
3+3 symmetrical split-earth geometry
Conductor DC resistance
Per IEC 60228 / GB/T 3956 Class 5
Current rating basis
Per GB/T 12706.1 / IEC 60502-1 (+90 °C)

Thermal

Max. conductor temperature
+90 °C continuous
Short-circuit temperature
+250 °C (max. 5 s)
Operating temperature, fixed
−15 °C to +70 °C ambient
Min. installation temperature
0 °C (preheat below 0 °C)

Mechanical

Min. bending radius, installation
15 × OD
Min. bending radius, fixed
12 × OD (clamped)
Max. pulling tension
50 N/mm² on copper conductors
Cable profile
Circular symmetrical 3+3 construction

Resistance

Flame retardance
IEC 60332-1-2 / GB/T 18380.12
Oil & chemical resistance
Resistant to industrial lubricants & dust
UV & weather
Black UV-stabilised ST2 PVC jacket
Moisture protection
Non-hygroscopic PP interstitial fillers

Reference standards

Design specification
TICW/06-2009 · GB/T 12706.1
International alignment
IEC 60502-1 · IEC 60228 · IEC 60332-1-2
Core identification
GB/T 6995 (Y/G/R + 3 × GNYE)
RoHS · REACH
2011/65/EU & EC 1907/2006 compliant

Identification

Sheath colour
Black (RAL 9005), ST2 FR-PVC
Core colours
Yellow, green, red + 3 × green/yellow
Sheath marking
BPYJVP 0.6/1 kV TEBAOFLEX.COM
Customs tariff (HS)
8544.49

Sizes

14 standard sizes (3+3 symmetrical VFD range)

Typical dimensions, IEC 60228 Class 5 conductor resistance, copper index, and approximate weights for BPYJVP 0.6/1 kV.

Dimensions & weights
Order designationCores × mm²Outer Ø ≈
mm
Max. R20
Ω/km
Copper
kg/km
Weight ≈
kg/km
Min. bend R
15×D mm
Enquiry
BPYJVP 3×2.5 + 3×0.53×2.5 + 3×0.513.57.980122290203
BPYJVP 3×4 + 3×0.753×4 + 3×0.7515.04.950184375225
BPYJVP 3×6 + 3×13×6 + 3×116.83.300258490252
BPYJVP 3×10 + 3×1.53×10 + 3×1.519.81.910410760297
BPYJVP 3×16 + 3×2.53×16 + 3×2.523.01.2106281,100345
BPYJVP 3×25 + 3×43×25 + 3×427.80.7809601,665417
BPYJVP 3×35 + 3×63×35 + 3×631.00.5541,3202,200465
BPYJVP 3×50 + 3×103×50 + 3×1035.80.3861,8803,050537
BPYJVP 3×70 + 3×103×70 + 3×1040.50.2722,4804,050608
BPYJVP 3×95 + 3×163×95 + 3×1646.00.2063,3705,425690
BPYJVP 3×120 + 3×253×120 + 3×2551.00.1614,3306,700765
BPYJVP 3×150 + 3×253×150 + 3×2556.50.1295,2108,150848
BPYJVP 3×185 + 3×353×185 + 3×3562.50.1066,47010,150938
BPYJVP 3×240 + 3×503×240 + 3×5071.00.0808,43013,2501,065
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Conductor max. DC resistance R20 follows IEC 60228 / GB/T 3956 Class 5 bare annealed copper at 20 °C.
  • Copper index includes 3 phase cores, 3 symmetrical split earth cores, and the overall bare copper wire braid screen (≥ 85% coverage).

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test3.5 kV AC for 5 min without breakdownEvery manufactured drum length
Conductor DC resistance checkPer IEC 60228 / GB/T 3956 Class 5 at 20 °CEvery drum length
Sample tests
XLPE hot-set & braid coverage checkGB/T 12706.1 hot-set & ≥ 85% Cu braid coveragePer production lot
Vertical flame propagationSelf-extinguishing per IEC 60332-1-2 / GB/T 18380.12Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

TICW/06-2009 Symmetrical VFD Cable SpecificationGB/T 12706.1 / IEC 60502-1 (0.6/1 kV)IEC 60332-1-2 / GB/T 18380.12 Flame Retardant

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

BPYJVP 0.6/1 kV TEBAOFLEX.COM [Cores×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

Why does BPYJVP 0.6/1 kV use a symmetrical 3+3 core layout instead of a standard 4-core power cable?
Splitting the protective earth into three smaller conductors laid symmetrically in the outer interstices of the three phase cores balances phase-to-ground capacitance and neutralises zero-sequence currents. This reduces induced shaft voltages and prevents premature bearing currents in variable frequency drive motors.
What advantages does the 90 °C XLPE insulation provide on VFD motor feeders?
Cross-linked polyethylene (XLPE) operates continuously up to +90 °C and withstands +250 °C for 5 seconds under short-circuit conditions, delivering higher current-carrying capacity and lower dielectric permittivity than 70 °C PVC insulation while reducing PWM capacitive charging peaks over longer motor runs.
How should the bare copper wire braid screen be terminated at the drive and motor?
Terminate the ≥ 85% bare annealed copper braid circumferentially using 360-degree EMC cable glands at both the inverter cabinet and the motor terminal box, while bonding all three symmetrical green/yellow split earth conductors together to the protective earth busbar.
Can BPYJVP 0.6/1 kV be installed in continuous drag chains or motorised cable reels?
No. BPYJVP 0.6/1 kV is engineered for fixed industrial routing and occasional installation flexing (minimum bending radius 15 × OD). For continuous drag-chain motion choose a PUR-sheathed servo cable, or for reeling duty select a rubber-sheathed (N)SSHCÖU VFD cable.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for BPYJVP 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

BPYJVP 0.6/1 kV Symmetrical Shielded VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote