Screened power & VFD / motor supply cablesUL 1277 TC-ER · ICEA S-138-738ICEA Method 3 (Blk/Red/Blu)5-mil Cu Tape · Silicone-Free PVC

SPEC 45451 2000 V TC-ER Copper Tape VFD CableICEA Method 3 coloured 2 kV RHH/RHW-2 copper tape VFD cable

2,000 V UL 1277 TC-ER / ICEA S-138-738 VFD tray cable featuring Class B compressed bare copper, ICEA Method 3 colour-coded RHH/RHW-2 XLPE phases (Black/Red/Blue), three bare grounds, 5-mil copper tape (≥ 50% lap), and silicone-free PVC jacket.

Low-EMC design
EMC screen
Oil-resistant
Flame-retardant
Order designation
SPEC 45451 2000V 3×2 AWG + 3×8 AWG
Outer Ø
30.8 mm
Max. R20
0.523 Ω/km
Weight
2,222 kg/km
Min. bend R
370 mm
All sizes (15)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
2,000 V (2 kV)
90 °C wet/dry RHH/RHW-2 XLPE
Phase colour ID
ICEA Method 3
1-Black, 2-Red, 3-Blue (numbered)
EMC screening
5-mil Cu tape
Helical bare Cu tape (≥ 50% overlap)
Conductor class
Class B bare Cu
ASTM B3 / B8 bare annealed copper
Min. bend radius
12 × OD
Fixed tray, conduit & exposed runs
Size range
14 AWG–500 MCM
3C + 3× bare Cu · Silicone-free PVC

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHH/RHW-2 · ICEA S-138-738 — confirmed in the datasheet and quotation for your order.

Application fit

Is SPEC 45451 2000V TC-ER right for your machine?

2,000 V UL 1277 TC-ER / ICEA S-138-738 VFD tray cable featuring Class B compressed bare copper, ICEA Method 3 colour-coded RHH/RHW-2 XLPE phases (Black/Red/Blue), three bare grounds, 5-mil copper tape (≥ 50% lap), and silicone-free PVC jacket.

VFD inverter to AC motor screened feeder

Suitable

5-mil helical copper tape (≥ 50% overlap) delivers double-thickness 100% EMI containment per ICEA S-138-738.

Silicone-free coating & factory tray

Suitable

PWIS/silicone-free oil- and UV-resistant PVC outer jacket prevents coating defects in automotive paint lines.

Motor stator, traction & converter leads

Suitable

ICEA Method 3 coloured phases (1-Black, 2-Red, 3-Blue) prevent phase-rotation errors at commissioning.

Fixed installation

Suitable

UL 1277 Type TC-ER, Direct Burial, and NEC Class I Div 2 rated for plant trays and exposed drops.

Energy chain / drag chain

Not suitable

Class B compressed copper and 5-mil copper tape are for stationary routing, not continuous drag chains.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not engineered for motorised cable reels; select a rubber reeling cable for spooled machinery.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableAutomotive & silicone-free paint plantsIndustrial process & factory traysOil, gas & chemical motor feedersWater treatment & HVAC plantsNEC Class I Div 2 hazardous locations

Construction

Layer by layer

Shown: SPEC 45451 2000 V TC-ER 3×2 AWG + 3×8 AWG — Class B compressed bare copper phases in ICEA Method 3 Black/Red/Blue RHH/RHW-2 XLPE with three bare copper grounds, 5-mil ≥ 50%-lap Cu tape, and silicone-free PVC jacket.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass B compressed stranded bare annealed copperASTM B3 / B8 Class B compressed
2Phase insulation2 kV RHH/RHW-2 XLPE (ICEA Method 3: 1-Black, 2-Red, 3-Blue)UL 44 RHH/RHW-2 + 3 × bare Cu grounds
3Fillers & binder tapeNon-hygroscopic polypropylene fillers & binder tapeSymmetrical 3+3 round core assembly
45-mil copper tape shield5-mil (0.127 mm) helical annealed bare copper tape (≥ 50% lap)ICEA S-138-738 double-thickness overlap
5Outer jacketBlack PWIS-free sunlight- & oil-resistant PVCUL 1277 Type TC-ER · Oil Res I/II

SPEC 45451 2000 V (ICEA M3)

Three ICEA Method 3 coloured XLPE phases (1-Black, 2-Red, 3-Blue) + three compressed bare Cu grounds under 5-mil ≥ 50%-lap Cu tape (14 AWG–500 kcmil).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHH/RHW-2 · ICEA S-138-738. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
2,000 V (2 kV) AC
Conductor class
ASTM B8 Class B compressed bare Cu
Phase identification
ICEA Method 3 (1-Black, 2-Red, 3-Blue)
EMC shield
5-mil bare Cu tape (≥ 50% overlap)

Thermal

Max. conductor temp.
+90 °C wet or dry (RHH/RHW-2)
Ambient temp. (fixed)
−40 °C to +90 °C
Min. bending radius
12 × OD (Cu-tape shielded)

Resistance

Flame test
IEEE 1202 / UL 1685 / CSA FT4
Jacket formulation
PWIS-free sunlight & oil-resistant PVC
Installation ratings
TC-ER · Direct Burial · Class I Div 2

Sizes

3C+3G Symmetrical (ICEA Method 3)
Phase + 3×
Ground (AWG)
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
12×D mm
3×14 AWG + 3×18 AWG15.58.450128330186
3×12 AWG + 3×16 AWG16.55.310179416198
3×10 AWG + 3×14 AWG17.83.340257544214
3×8 AWG + 3×14 AWG20.62.100351737247
3×6 AWG + 3×12 AWG22.71.3205271,019272
3×4 AWG + 3×12 AWG26.40.8327561,432317
3×2 AWG + 3×8 AWG30.80.5231,2492,222370
3×1 AWG + 3×8 AWG32.80.4151,4962,618394
3×1/0 AWG + 3×6 AWG35.00.3291,9433,278420
3×2/0 AWG + 3×6 AWG37.50.2612,3333,889450
3×3/0 AWG + 3×4 AWG41.00.2073,0444,965492
3×4/0 AWG + 3×4 AWG44.20.1643,6635,926530
3×250 kcmil + 3×4 AWG48.30.1394,2116,874580
3×350 kcmil + 3×2 AWG54.00.0995,9599,453648
3×500 kcmil + 3×2 AWG61.20.0708,07012,656734
  • Conductor max. DC resistance R20 follows ASTM B8 Class B compressed bare annealed copper at 20 °C.
  • Silicone-free outer PVC jacket is compatible with automotive paint shops and surface-finishing facilities.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric testPer UL 44 RHH/RHW-2 2,000 V ratingEvery manufactured reel
Conductor DC resistance checkPer ASTM B8 Class B at 20 °CEvery reel length
Sample tests
5-mil Cu tape overlap & crush test≥ 50% helical overlap & UL 1277 crushPer production lot
Vertical tray flame testIEEE 1202 / UL 1685 / FT4Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ER (2,000 V) · UL 44 RHH/RHW-2ICEA S-138-738 Symmetrical VFD SpecificationIEEE 1202 / FT4 · Sunlight & Oil Resistant · Direct Burial

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

SPEC 45451 2000V TC-ER TEBAOFLEX.COM UL 1277 RHH/RHW-2 ICEA M3 [Size]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What is ICEA Method 3 phase identification on SPEC 45451?
ICEA Method 3 pairs solid phase insulation colours (1-Black, 2-Red, 3-Blue) with printed phase numbers so electricians can verify phase rotation visually without ringing out conductors.
Why does SPEC 45451 specify a silicone-free PVC jacket?
Silicone-free jacketing prevents paint-cratering contamination in automotive body shops, coating booths, and surface-finishing factories while retaining oil and UV resistance.
Why is ≥ 50% overlap specified for the 5-mil copper tape shield?
A minimum 50% helical overlap maintains continuous double-layer copper thickness (10 mils effective) across the entire cable length even at the 12 × OD minimum bend radius.
How should the EMC shield and symmetrical grounds of SPEC 45451 2000V TC-ER be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for SPEC 45451 2000V TC-ER

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

SPEC 45451 2000 V TC-ER Copper Tape VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 