Heavy-duty 0.6/1 kV symmetrical 3+3 VFD power cable combining Class 5 bare copper conductors, 90 °C XLPE insulation, dual bare copper tape (P2) plus copper wire braid (P) EMC shielding, and black FR-PVC outer sheath.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
BPYJVPP2 3×70 + 3×16
Outer Ø
36.9 mm
Max. R20
0.272 Ω/km
Weight
4,254 kg/km
Min. bend R
554 mm
All sizes (13)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 3.5 kV / 5 min
EMC screening
Cu tape + braid
100% P2 tape + ≥ 85% P Cu braid
Conductor temp.
+90 °C max.
+250 °C short-circuit (5 s)
Ambient temp.
−15…+70 °C
fixed (≥ 0 °C during installation)
Min. bend radius
15 × OD
fixed laying in trays & tunnels
Size range
4–240 mm²
Class 5 Cu · 3+3 symmetrical

Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228 Cl.5 — confirmed in the datasheet and quotation for your order.

Application fit

Is BPYJVPP2 0.6/1 kV right for your machine?

Heavy-duty 0.6/1 kV symmetrical 3+3 VFD power cable combining Class 5 bare copper conductors, 90 °C XLPE insulation, dual bare copper tape (P2) plus copper wire braid (P) EMC shielding, and black FR-PVC outer sheath.

VFD inverter to AC motor screened feeder

Suitable

Dual 100% copper tape (P2) plus ≥ 85% copper braid (P) minimizes transfer impedance across kHz–MHz harmonics.

Dual-tier power & PLC tray

Suitable

Double copper screening allows high-kW VFD feeders to run safely near PLC and instrumentation trays.

Motor stator, traction & converter leads

Suitable

Class 5 copper conductors ease large-gauge cabinet terminations while 3+3 split earths cut bearing currents.

Fixed installation

Suitable

Heavy-duty black FR-PVC sheath resists mechanical stress in industrial trays, tunnels, and racks.

Energy chain / drag chain

Not suitable

Dual copper-tape plus braid construction is designed for fixed routing, not continuous drag-chain cycles.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not rated for motorised cable drums; specify a rubber reeling cable for spooled mobile machinery.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableHigh-power VFD drive baysRolling mills & heavy metallurgyPetrochemical & process plantsPower generation auxiliariesInstrumentation-adjacent trays

Construction

Layer by layer

Shown: BPYJVPP2 0.6/1 kV 3×70 + 3×16 mm² — Class 5 bare copper phase cores and three green/yellow split earths shielded by overlapping copper tape plus copper wire braid.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 5 flexible bare annealed copperGB/T 3956 / IEC 60228 Class 5
2Phase & earth insulation90 °C cross-linked polyethylene (XLPE), GB/T 6995 coloursYellow, green, red + 3 × green/yellow split earths
3Fillers & binder tapePolypropylene fillers & flame-retardant wrapping tapeSymmetrical 3+3 round core assembly
4Inner copper tape screenOverlapping bare annealed copper tape (P2, 100% coverage)High-frequency electrostatic barrier
5Outer copper braid screenBare annealed copper wire braid (P, ≥ 85% coverage)Low-impedance EMC return & mechanical tie
6Outer sheathBlack heavy-duty flame-retardant PVC (ZR-PVC / ST2)GB/T 12706.1 / IEC 60502-1 ST2

BPYJVPP2 3+3 Dual-Shield

Three XLPE phase cores (yellow, green, red) plus three green/yellow split earths under dual Cu tape + Cu braid (4–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228 Cl.5. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV
AC test voltage
3.5 kV / 5 min
Conductor class
IEC 60228 Class 5 bare Cu
Dual EMC screen
100% Cu tape (P2) + ≥ 85% Cu braid (P)
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Max. conductor temp.
+90 °C continuous
Short-circuit temp.
+250 °C (max. 5 s)
Ambient temp. (fixed)
−15 °C to +70 °C
Min. installation temp.
0 °C
Min. bending radius
15 × OD (fixed)

Resistance

Flame retardance
IEC 60332-1-2 / GB/T 18380.12
Sheath compound
Black heavy-duty FR-PVC (ST2)
Chemical & oil resistance
Good industrial oil resistance

Sizes

3+3 Symmetrical (Dual Cu Screen)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
15×D mm
3×4 + 3×0.7514.74.950181388220
3×6 + 3×116.03.300247503240
3×10 + 3×1.518.11.910377727272
3×16 + 3×2.520.61.2105771,062309
3×25 + 3×425.10.7808791,607376
3×35 + 3×627.70.5541,2162,154416
3×50 + 3×1031.60.3861,7483,028474
3×70 + 3×1636.90.2722,4764,254554
3×95 + 3×1640.90.2063,1735,404614
3×120 + 3×2544.90.1614,1156,908674
3×150 + 3×2550.90.1294,9558,426764
3×185 + 3×3555.80.1066,20010,458837
3×240 + 3×5061.80.0808,13213,544927
  • Conductor max. DC resistance R20 follows IEC 60228 / GB/T 3956 Class 5 bare annealed copper at 20 °C.
  • Copper index accounts for 3 phases, 3 split earths, inner overlapping copper tape, and outer ≥ 85% bare copper braid.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test3.5 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer IEC 60228 / GB/T 3956 Class 5 at 20 °CEvery drum length
Sample tests
Dual-screen & XLPE hot-set check100% Cu tape lap + ≥ 85% braid + hot-setPer production lot
Vertical flame propagationSelf-extinguishing per IEC 60332-1-2Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

TICW/06-2009 Double-Shielded VFD SpecificationGB/T 12706.1 / IEC 60502-1 (0.6/1 kV)IEC 60332-1-2 / GB/T 18380.12 Flame Retardant

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

BPYJVPP2 0.6/1 kV TEBAOFLEX.COM [Cores×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

When is dual copper tape + copper braid shielding (BPYJVPP2) necessary?
Specify BPYJVPP2 on high-kW VFD feeders routed alongside PLC, encoder, or analogue signal trays where a single tape or braid cannot achieve sufficient high-frequency attenuation and low ground-return impedance.
Why does BPYJVPP2 use Class 5 copper conductors on large cross-sections?
Class 5 fine-wire stranding significantly reduces pulling stiffness in tight drive cabinets and motor terminal boxes compared with Class 2 cables of the same 70–240 mm² cross-section.
Should both the inner copper tape and outer copper braid be bonded at termination?
Yes. Both copper screen layers are in direct electrical contact and should be clamped 360° inside an EMC cable gland at both drive and motor ends for minimal transfer impedance.
How should the EMC shield and symmetrical grounds of BPYJVPP2 0.6/1 kV be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for BPYJVPP2 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

BPYJVPP2 0.6/1 kV Double-Shielded VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote