BPYJVP2 0.6/1 kV Copper Tape Shielded VFD Cable90 °C XLPE 3+3 symmetrical VFD cable with copper tape screen

Symmetrical 3+3 fixed-installation VFD power cable rated 0.6/1 kV with Class 2 bare copper conductors, 90 °C XLPE insulation, 100% overlapping bare annealed copper tape screen (P2), and black flame-retardant PVC sheath.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
BPYJVP2 3×50 + 3×10
Outer Ø
30.1 mm
Max. R20
0.387 Ω/km
Weight
2,687 kg/km
Min. bend R
452 mm
All sizes (13)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 3.5 kV / 5 min
EMC screening
100% Cu tape
Overlapping bare Cu tape (P2)
Conductor temp.
+90 °C max.
+250 °C short-circuit (5 s)
Ambient temp.
−15…+70 °C
fixed (≥ 0 °C during installation)
Min. bend radius
15 × OD
fixed routing in trays & ducts
Size range
4–240 mm²
Class 2 Cu · 3+3 symmetrical

Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228 Cl.2 — confirmed in the datasheet and quotation for your order.

Application fit

Is BPYJVP2 0.6/1 kV right for your machine?

Symmetrical 3+3 fixed-installation VFD power cable rated 0.6/1 kV with Class 2 bare copper conductors, 90 °C XLPE insulation, 100% overlapping bare annealed copper tape screen (P2), and black flame-retardant PVC sheath.

VFD inverter to AC motor screened feeder

Suitable

Overlapping bare copper tape (P2) provides 100% radial coverage against high-frequency PWM emissions.

Motor stator, traction & converter leads

Suitable

Symmetrical 3+3 split earths balance phase-to-ground capacitance and suppress motor shaft voltages.

Cable trench & heavy drive bay

Suitable

Class 2 bare copper and 100% copper tape screen excel in stationary steel-mill and heavy plant cable trenches.

Fixed installation

Suitable

Black FR-PVC (ST2) outer sheath suits stationary cable ladders, concrete trenches, and conduit ducts.

Energy chain / drag chain

Not suitable

Class 2 conductors and helical copper tape are for stationary runs, not continuous drag-chain bending.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not rated for motorised cable drums or dynamic reeling; select a rubber reeling cable instead.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableHeavy industrial VFD feedersMetallurgy & steel plantsPump & compressor stationsChemical processing linesHVAC & plant power distribution

Construction

Layer by layer

Shown: BPYJVP2 0.6/1 kV 3×50 + 3×10 mm² — Class 2 bare copper phase cores and three symmetrical green/yellow split earths inside an overlapping bare copper tape screen.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 2 stranded bare annealed copperGB/T 3956 / IEC 60228 Class 2
2Phase & earth insulation90 °C cross-linked polyethylene (XLPE), GB/T 6995 coloursYellow, green, red + 3 × green/yellow split earths
3Fillers & binder tapeNon-hygroscopic polypropylene fillers & FR binder tapeSymmetrical 3+3 round cabled core
4EMC copper tape screenOverlapping bare annealed copper tape (P2, 100% coverage)TICW/06-2009 continuous EMC & ground-fault path
5Outer sheathBlack flame-retardant PVC compound (ZR-PVC / ST2)GB/T 12706.1 / IEC 60502-1 ST2

BPYJVP2 3+3 Symmetrical

Three XLPE phase cores (yellow, green, red) plus three symmetrically laid green/yellow split earths (4–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on TICW/06-2009 · GB/T 12706.1 · IEC 60502-1 · IEC 60228 Cl.2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV
AC test voltage
3.5 kV / 5 min
Conductor class
IEC 60228 Class 2 bare Cu
EMC screen
100% overlapping bare Cu tape (P2)
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Max. conductor temp.
+90 °C continuous
Short-circuit temp.
+250 °C (max. 5 s)
Ambient temp. (fixed)
−15 °C to +70 °C
Min. installation temp.
0 °C
Min. bending radius
15 × OD (fixed)

Resistance

Flame retardance
IEC 60332-1-2 / GB/T 18380.12
Sheath compound
Black FR-PVC (ZR-PVC / ST2)
Chemical & oil resistance
Good industrial oil resistance

Sizes

3+3 Symmetrical (Class 2 Cu)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
15×D mm
3×4 + 3×0.7514.04.610160320210
3×6 + 3×115.33.080224423230
3×10 + 3×1.517.31.830351622260
3×16 + 3×2.519.61.150547920294
3×25 + 3×423.90.7278431,405358
3×35 + 3×626.40.5241,1761,899396
3×50 + 3×1030.10.3871,7032,687452
3×70 + 3×1635.10.2682,4243,789526
3×95 + 3×1639.00.1933,1154,832585
3×120 + 3×2542.80.1534,0516,195642
3×150 + 3×2548.50.1244,8827,553728
3×185 + 3×3553.10.0996,1219,391796
3×240 + 3×5058.80.0758,04412,191882
  • Conductor max. DC resistance R20 follows IEC 60228 / GB/T 3956 Class 2 bare annealed copper at 20 °C.
  • Copper index includes 3 phase cores, 3 symmetrical split earths, and the overlapping annealed bare copper tape screen.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test3.5 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer IEC 60228 / GB/T 3956 Class 2 at 20 °CEvery drum length
Sample tests
XLPE hot-set & Cu tape overlapGB/T 12706.1 hot-set & 100% tape lapPer production lot
Vertical flame propagationSelf-extinguishing per IEC 60332-1-2Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

TICW/06-2009 Symmetrical VFD Cable SpecificationGB/T 12706.1 / IEC 60502-1 (0.6/1 kV)IEC 60332-1-2 / GB/T 18380.12 Flame Retardant

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

BPYJVP2 0.6/1 kV TEBAOFLEX.COM [Cores×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

How does BPYJVP2 differ from BPYJVP?
BPYJVP2 uses an overlapping bare annealed copper tape screen (P2, 100% radial coverage) with Class 2 stranded conductors for fixed industrial runs, whereas BPYJVP uses a bare copper wire braid screen (P) with Class 5 conductors for greater routing flexibility.
Why specify a 3+3 symmetrical split-earth cable for VFD motors?
Placing three split earth conductors symmetrically in the interstices balances phase-to-ground impedance and suppresses zero-sequence currents, helping protect motor bearings from circulating shaft currents.
How should the copper tape screen be terminated?
Bond the overlapping copper tape screen 360° using EMC shielding clamps or constant-force springs at both the inverter output and motor terminal box, while connecting all three split earth cores to protective earth.
How should the EMC shield and symmetrical grounds of BPYJVP2 0.6/1 kV be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for BPYJVP2 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

BPYJVP2 0.6/1 kV Copper Tape Shielded VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote