Contact
Screened power & VFD / motor supply cablesDIN VDE 0250U0/U 0.6/1 kV · 4 kV ACEMC Screened

9YSLCY-JB 0.6/1 kV PP Low-Cap VFD Motor Cable90 °C polypropylene-insulated double-screened transparent-sheath VFD cable

9YSLCY-JB 0.6/1 kV uses 90 °C low-capacitance polypropylene (PP 9Y) insulation, Class 5 bare copper conductors, dual foil/braid EMC screening, and a transparent PVC outer sheath for extended VFD motor feeders.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
9YSLCY-JB 0.6/1 kV 4G16
Outer Ø
22.4 mm
Max. R20
1.210 Ω/km
Weight
1,128 kg/km
Min. bend R
224 mm
All sizes (13)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 4 kV AC
EMC screening
Foil + TCWB
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -5 °C to +70 °C
Min. bend radius
10 × OD
Fixed routing in trays & ducts
Conductor
Bare Cu · Cl.5
IEC 60228 stranded copper
Size range
4G1.5–4G185
13 standard configurations

Typical values for this cable type, based on DIN VDE 0250 · IEC 60228 Class 5 · HD 308 S2 — confirmed in the datasheet and quotation for your order.

Application fit

Is 9YSLCY-JB 0.6/1 kV right for your machine?

9YSLCY-JB 0.6/1 kV uses 90 °C low-capacitance polypropylene (PP 9Y) insulation, Class 5 bare copper conductors, dual foil/braid EMC screening, and a transparent PVC outer sheath for extended VFD motor feeders.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 0.6/1 kV PP/PVC construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 0.6/1 kV PP/PVC geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Dual-tier power & PLC tray

Suitable

Screened 0.6/1 kV PP/PVC construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Control cabinet & internal panel wiring

Suitable

Compact flame-retardant 0.6/1 kV PP/PVC geometry routes neatly through dense switchgear ducts, control cabinets, and DIN-rail terminals.

Energy chain / drag chain

Not suitable

0.6/1 kV PP/PVC construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

0.6/1 kV PP/PVC build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of 9YSLCY-JB 0.6/1 kV: bare copper conductors, Low-capacitance polypropylene (PP 9Y, 90 °C), Al-laminated foil + ≥ 85% tinned copper braid, and Transparent oil- & flame-retardant PVC outer sheath.

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorIEC 60228 Class 5 flexible bare annealed copperIEC 60228 Class 5
2Core insulationLow-capacitance polypropylene (PP 9Y, 90 °C)DIN VDE 0250
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeDIN VDE 0250
4EMC metallic screenAl-laminated foil + ≥ 85% tinned copper braidEMC ≥ 85% / 100% foil
5Outer sheathTransparent oil- & flame-retardant PVC outer sheathIEC 60332-1-2 Flame

9YSLCY-JB 0.6/1 kV Power & Ground

Colour-coded or numbered phase conductors with protective green/yellow earth under overall EMC screening.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0250 · IEC 60228 Class 5 · HD 308 S2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV
AC test voltage
4 kV AC / 5 min
Conductor class
IEC 60228 Class 5 bare Cu
EMC screen
Al-laminated foil + ≥ 85% tinned copper braid
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-5 °C to +70 °C
Short-circuit temp.
+160 °C (5 s)
Min. bending radius
10 × OD (fixed)

Resistance

Flame retardance
IEC 60332-1-2 Flame
Oil & chemical perf.
Low-Capacitance PP (9Y)
Environmental / EMC
EN 55011 EMC
Outer sheath
Transparent oil- & flame-retardant PVC

Sizes

4-Core Screened (mm²)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
4G1.511.613.30084191116
4G2.512.87.980123259128
4G414.14.950181355141
4G615.53.300257478155
4G1018.71.910411743187
4G1622.41.2106381,128224
4G2525.50.7809741,650255
4G3529.40.5541,3482,261294
4G5033.10.3861,9033,115331
4G7038.30.2722,6444,294383
4G9544.20.2063,5685,778442
4G12048.00.1614,4887,173480
4G18556.30.1066,87510,765563
  • Max. conductor DC resistance R20 at 20 °C per IEC 60228 (bare copper).
  • Minimum bending radius calculated at 10 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer IEC 60228 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation checkFoil + TCWB continuity & wall thicknessPer production lot
Flame & environmental qualificationIEC 60332-1-2 Flame · Low-Capacitance PP (9Y)Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0250IEC 60228 Class 5HD 308 S2EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

9YSLCY-JB 0.6/1 kV 0.6/1 kV TEBAOFLEX.COM [DIN VDE 0250] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes 9YSLCY-JB 0.6/1 kV suitable for 0.6/1 kV industrial installations?
9YSLCY-JB 0.6/1 kV combines bare copper conductors, Low-capacitance polypropylene (PP 9Y, 90 °C), and Al-laminated foil + ≥ 85% tinned copper braid inside a Transparent oil- & flame-retardant PVC outer sheath. PP (9Y) dielectric achieves lower mutual capacitance and higher thermal margin (+90 °C) than standard PE.
Can 9YSLCY-JB 0.6/1 kV operate inside continuous drag chains or moving axes?
No. 9YSLCY-JB 0.6/1 kV is engineered for stationary tray, conduit, or machine-frame routing at 10 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of 9YSLCY-JB 0.6/1 kV be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany 9YSLCY-JB 0.6/1 kV?
9YSLCY-JB 0.6/1 kV conforms to DIN VDE 0250, IEC 60228 Class 5, HD 308 S2 (IEC 60332-1-2 Flame) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 9YSLCY-JB 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

9YSLCY-JB 0.6/1 kV PP Low-Cap VFD Motor Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote