VFD inverter to AC motor screened feeder
Low-capacitance 0.6/1 kV XLPE/PE construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Product
2XSL(St)CYK-J 0.6/1 kV combines Class 5 bare copper conductors, 90 °C XLPE insulation, dual aluminium-foil and tinned copper braid EMC screening, and a black UV-resistant PVC/PE outer sheath for indoor and outdoor drives.
Typical values for this cable type, based on DIN VDE 0250 · IEC 60502-1 · IEC 60228 Class 5 — confirmed in the datasheet and quotation for your order.
Application fit
2XSL(St)CYK-J 0.6/1 kV combines Class 5 bare copper conductors, 90 °C XLPE insulation, dual aluminium-foil and tinned copper braid EMC screening, and a black UV-resistant PVC/PE outer sheath for indoor and outdoor drives.
Low-capacitance 0.6/1 kV XLPE/PE construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Balanced 0.6/1 kV XLPE/PE geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.
UV-stabilised weather-resistant 0.6/1 kV XLPE/PE outer sheath withstands direct sunlight, rain, and outdoor rack exposure year-round.
Durable 0.6/1 kV XLPE/PE construction powers industrial process pumps, boosters, and compressor skids under continuous plant duty.
0.6/1 kV XLPE/PE construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR0.6/1 kV XLPE/PE build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.
Use RG / RG-D (N)SHTOEU-JConstruction
Representative construction of 2XSL(St)CYK-J 0.6/1 kV: bare copper conductors, 90 °C cross-linked polyethylene (XLPE 2X), Al-laminated plastic foil (St) + ≥ 85% tinned copper braid, and Black UV- & weather-resistant PVC/PE outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 5 flexible bare annealed copperIEC 60228 Class 5 |
| 2 | Core insulation | 90 °C cross-linked polyethylene (XLPE 2X)DIN VDE 0250 |
| 3 | Core assembly & separator | Concentric cabled assembly with low-friction fleece or polyester binder tapeDIN VDE 0250 |
| 4 | EMC metallic screen | Al-laminated plastic foil (St) + ≥ 85% tinned copper braidEMC ≥ 85% / 100% foil |
| 5 | Outer sheath | Black UV- & weather-resistant PVC/PE outer sheathIEC 60332-1-2 Flame |
Colour-coded or numbered phase conductors with protective green/yellow earth under overall EMC screening.
Technical data
Sizes
| Cores × mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 10×D mm |
|---|---|---|---|---|---|
| 4G1.5 | 11.6 | 13.300 | 84 | 191 | 116 |
| 4G2.5 | 12.8 | 7.980 | 123 | 259 | 128 |
| 4G4 | 14.1 | 4.950 | 181 | 355 | 141 |
| 4G6 | 15.5 | 3.300 | 257 | 478 | 155 |
| 4G10 | 18.7 | 1.910 | 411 | 743 | 187 |
| 4G16 | 22.4 | 1.210 | 638 | 1,128 | 224 |
| 4G25 | 25.5 | 0.780 | 974 | 1,650 | 255 |
| 4G35 | 29.4 | 0.554 | 1,348 | 2,261 | 294 |
| 4G50 | 33.1 | 0.386 | 1,903 | 3,115 | 331 |
| 4G70 | 38.3 | 0.272 | 2,644 | 4,294 | 383 |
| 4G95 | 44.2 | 0.206 | 3,568 | 5,778 | 442 |
| 4G120 | 48.0 | 0.161 | 4,488 | 7,173 | 480 |
| 4G185 | 56.3 | 0.106 | 6,875 | 10,765 | 563 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC high-voltage dielectric test | 4 kV AC for 5 min without breakdown | Every manufactured drum |
| Conductor DC resistance test | Per IEC 60228 at 20 °C | Every drum length |
| Sample tests | ||
| EMC screen coverage & insulation check | Foil + TCWB continuity & wall thickness | Per production lot |
| Flame & environmental qualification | IEC 60332-1-2 Flame · UV & Weather Resistant | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.