Product
Utility substation, MV/LV switchgear and Class F motor lead wire dual-certified to UL 44 Type SIS Switchboard Wire (90 °C, 600 V) and UL AWM Style 3173 / CSA CL1251 (125 °C, 600 V), featuring tinned copper conductors (22–4/0 AWG) and thermoset XLPE insulation.
Typical values for this cable type, based on UL 44 Type SIS · UL 758 Style 3173 · CSA CL1251 — confirmed in the datasheet and quotation for your order.
Application fit
Specify dual-rated UL 3173 / Type SIS wherever ANSI/IEEE C37 switchgear standards, utility substation protection panels or Class B/F rotating machines demand a 600 V thermoset XLPE wire that will never deform or melt under CT secondary circuits, heater strips or lug hotspots.
ANSI C37 MV/LV switchgear cubicles, utility relay panels, CT/PT secondary wiring and Class B/F motor leads.
Thermoset XLPE insulation resists corona and thermal stress in drive cabinets; unscreened single-core.
Fixed switchboard, conduit and internal apparatus wire.
Use EN 50264-2-2For NFPA 79 PLC panels where thermoplastic PVC MTW is specified, see UL 1015 / MTW / TEW.
Use UL 1015 / MTWConstruction
Shown: UL 3173 / Type SIS 14 AWG (41/30 or 7-strand Class B) — tinned annealed copper conductor (2.08 mm²), 0.76 mm (30 mil) grey or black flame-retardant cross-linked polyethylene (XLPE) dielectric and VW-1 / FT1 surface legend.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Tinned or bare annealed copper | 7-strand Class B (for utility switchboard terminal blocks) or flexible 19/41/65-strand tinned copper (for hinged relay doors and motor leads)ASTM B33 / B8 · UL 44 · UL 758 |
| 2 | 0.76 mm (30 mil) flame-retardant XLPE | Chemically or electron-beam cross-linked polyethylene meeting both UL 44 Type SIS and UL 758 Style 3173UL 44 Type SIS · UL 758 Style 3173 |
| 3 | Low-friction VW-1 switchboard finish | Smooth thermoset outer surface engineered for neat 90-degree bundle dressing and high-density terminal-block wiring in utility panelsUL 44 · CSA C22.2 No. 38 / No. 210 |
Semi-rigid 7-strand tinned copper preferred by electric utilities for self-supporting relay-panel wiring
Flexible 19/26/41/65-strand tinned copper for hinged breaker doors, motor leads and transformer coils
Technical data
Sizes
Typical UL 44 Type SIS · UL 758 Style 3173 · CSA CL1251 outer diameter limits, copper content and cable weight.
| Order designation | Cores × mm² / AWG | AWG ≈ | Outer Ø min mm | Outer Ø max mm | Copper kg/km | Weight ≈ kg/km | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|---|
| 600 V Switchboard & Relay Panel Wire (UL 44 SIS / AWM 3173, 20–10 AWG) | ||||||||
| UL 3173 20 AWG (10/30) | 20 AWG (0.52 mm²) | 20 | 2.3 | 2.5 | 5 | 10 | 10 | |
| UL 3173 / SIS 18 AWG | 18 AWG (0.82 mm²) | 18 | 2.6 | 2.8 | 7 | 13 | 11 | |
| UL 3173 / SIS 16 AWG | 16 AWG (1.31 mm²) | 16 | 2.9 | 3.1 | 12 | 19 | 12 | |
| UL 3173 / SIS 14 AWG | 14 AWG (2.08 mm²) | 14 | 3.2 | 3.5 | 20 | 27 | 14 | |
| UL 3173 / SIS 12 AWG | 12 AWG (3.31 mm²) | 12 | 3.7 | 4.0 | 31 | 40 | 16 | |
| UL 3173 / SIS 10 AWG | 10 AWG (5.26 mm²) | 10 | 4.3 | 4.7 | 50 | 61 | 19 | |
| 600 V Heavy Switchgear & CT/Motor Leads (UL 44 SIS / AWM 3173, 8–2 AWG) | ||||||||
| UL 3173 / SIS 8 AWG | 8 AWG (8.37 mm²) | 8 | 5.9 | 6.4 | 80 | 104 | 26 | |
| UL 3173 / SIS 6 AWG | 6 AWG (13.3 mm²) | 6 | 7.5 | 8.1 | 127 | 165 | 32 | |
| UL 3173 / SIS 4 AWG | 4 AWG (21.2 mm²) | 4 | 8.7 | 9.5 | 203 | 252 | 38 | |
| UL 3173 / SIS 2 AWG | 2 AWG (33.6 mm²) | 2 | 10.2 | 11.1 | 322 | 385 | 44 | |
| Cross-section mm² | AWG ≈ | Max. DC resistance 20 °C, Ω/km | Single wire in air 30 °C, A | Multi-core bundle 30 °C, A |
|---|---|---|---|---|
| 0.52 | 20 | 34.6 | 10 | 7 |
| 0.82 | 18 | 24 | 14 | 11 |
| 1.31 | 16 | 15.1 | 20 | 15 |
| 2.08 | 14 | 9.8 | 27 | 21 |
| 3.31 | 12 | 6.2 | 36 | 27 |
| 5.26 | 10 | 3.88 | 50 | 36 |
| 8.37 | 8 | 2.42 | 68 | 48 |
| 13.3 | 6 | 1.48 | 92 | 65 |
| 21.2 | 4 | 0.92 | 125 | 88 |
| 33.6 | 2 | 0.58 | 165 | 115 |
Reel check
A first screen using datasheet values. Engineering confirms drum geometry, acceleration and tension with your quotation.
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC dielectric voltage test | 2.0 kV AC (50/60 Hz) | Every manufactured length |
| Conductor DC resistance | IEC 60228 / ASTM (tinned copper) | Every manufactured length |
| Sample tests | ||
| Flame propagation test | IEC 60332-1-2 / UL VW-1 / ISO 6722-1 | Per production batch |
| Insulation & sheath material physical properties | UL 44 Type SIS · UL 758 Style 3173 · CSA CL1251 | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.