Fixed installation
Approved for exposed ladder tray, direct earth burial, underground ducts and wet/corrosive industrial bays.
Product
TECK90 is the iconic Canadian heavy-duty industrial and mining armoured power cable governed by CSA C22.2 No. 131. Originally developed for Teck-Hughes gold mines in northern Ontario, it features RW90 cross-linked polyethylene (XLPE, +90 °C wet/dry) copper con
Typical values for this cable type, based on CSA C22.2 No. 131 / CEC Part I — confirmed in the datasheet and quotation for your order.
Application fit
Specified across Canadian and international underground/open-pit mines, pulp-and-paper mills, petrochemical refineries, LNG terminals, wastewater plants and Class I/II/III hazardous locations on open ladder trays, direct burial and vertical mine shafts.
Approved for exposed ladder tray, direct earth burial, underground ducts and wet/corrosive industrial bays.
Suitable for vertical mine-shaft drop suspension when supported with armoured shaft clamps.
Terminates into TECK-style wet/hazardous-location elastomer sealing glands without rigid conduit.
Fixed installation armoured cable; not for reeling drums or festoons.
SEOOW 600 V flexible cordConstruction
Class B concentric stranded bare copper conductors (14 AWG to 750 MCM) + RW90 XLPE insulation + bare stranded copper bonding wire + extruded -40 °C PVC inner jacket + interlocking 5052 aluminum (AIA) strip armour + FT4 / AG14 UV-resistant PVC outer jacket.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Class B stranded copper + bare Cu bond | Compressed concentric stranded annealed copper phase conductors plus uninsulated stranded copper equipment bonding conductorCSA C22.2 No. 131 |
| 2 | RW90 cross-linked polyethylene (XLPE) | Thermoset XLPE insulation rated +90 °C dry and wet (+250 °C short-circuit), colour-coded Black, Red, Blue (+ White)CSA C22.2 No. 38 |
| 3 | Extruded PVC inner bedding jacket | -40 °C lead-free flame-retardant PVC inner jacket sealing the core assembly against moisture and corrosive gasesCSA C22.2 No. 131 |
| 4 | Interlocking aluminum armour (AIA) | Helically interlocked 5052 aluminum alloy (or galvanized steel) strip armour providing high crush and impact protectionCSA C22.2 No. 131 |
| 5 | FT4 / AG14 outer PVC jacket | Sunlight-, oil-, acid- and -40 °C cold-impact-resistant outer PVC sheath (Black for 1000 V, Orange for 600 V, Yellow for 5 kV)CSA C22.2 No. 131 |
Multi-core control and instrumentation TECK90 with numbered or colour-coded XLPE cores.
Standard 3-conductor and 4-conductor + bare ground industrial feeder TECK90.
Medium-voltage 5,000 V TECK90 feeder cable for mine distribution and large MV motors.
Technical data
Sizes
Nominal dimensions, copper weight, total mass and electrical parameters for TECK90 per CSA C22.2 No. 131 / CEC Part I.
| Designation | Cores × AWG/MCM (1kV) | Bond Wire / CEC 90°C A | Nom. OD mm | Copper kg/km | Total mass ≈ kg/km | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| TECK90 size schedule | |||||||
| TECK90 3C 14 AWG | 3C × 14 AWG | 14 AWG Bond · 25 A | 15.80 | 68.0 | 295.0 | 110.6 | |
| TECK90 3C 12 AWG | 3C × 12 AWG | 14 AWG Bond · 30 A | 16.90 | 98.0 | 345.0 | 118.3 | |
| TECK90 3C 10 AWG | 3C × 10 AWG | 12 AWG Bond · 40 A | 18.40 | 152.0 | 430.0 | 128.8 | |
| TECK90 3C 8 AWG | 3C × 8 AWG | 10 AWG Bond · 55 A | 21.20 | 240.0 | 585.0 | 148.4 | |
| TECK90 3C 6 AWG | 3C × 6 AWG | 8 AWG Bond · 75 A | 24.10 | 382.0 | 810.0 | 168.7 | |
| TECK90 3C 4 AWG | 3C × 4 AWG | 8 AWG Bond · 95 A | 27.20 | 565.0 | 1,080.0 | 190.4 | |
| TECK90 3C 2 AWG | 3C × 2 AWG | 6 AWG Bond · 130 A | 30.80 | 895.0 | 1,520.0 | 215.6 | |
| TECK90 3C 1/0 AWG | 3C × 1/0 AWG | 6 AWG Bond · 170 A | 35.80 | 1,360.0 | 2,180.0 | 250.6 | |
| TECK90 3C 2/0 AWG | 3C × 2/0 AWG | 6 AWG Bond · 195 A | 38.40 | 1,685.0 | 2,610.0 | 268.8 | |
| TECK90 3C 3/0 AWG | 3C × 3/0 AWG | 4 AWG Bond · 225 A | 41.20 | 2,160.0 | 3,210.0 | 288.4 | |
| TECK90 3C 4/0 AWG | 3C × 4/0 AWG | 4 AWG Bond · 260 A | 44.50 | 2,670.0 | 3,880.0 | 311.5 | |
| TECK90 3C 250 MCM | 3C × 250 MCM | 4 AWG Bond · 290 A | 48.20 | 3,110.0 | 4,490.0 | 337.4 | |
| TECK90 3C 350 MCM | 3C × 350 MCM | 3 AWG Bond · 350 A | 53.60 | 4,310.0 | 5,980.0 | 375.2 | |
| TECK90 3C 500 MCM | 3C × 500 MCM | 2 AWG Bond · 430 A | 60.50 | 6,110.0 | 8,190.0 | 423.5 | |
| Cores × AWG/MCM (1kV) | Max. DC R @ 20 °C Ω/km | Current in air A | Installed / duty A |
|---|---|---|---|
| 3C × 14 AWG | 8.450 | 25 | 20 |
| 3C × 12 AWG | 5.310 | 30 | 24 |
| 3C × 10 AWG | 3.340 | 40 | 32 |
| 3C × 8 AWG | 2.100 | 55 | 44 |
| 3C × 6 AWG | 1.320 | 75 | 60 |
| 3C × 4 AWG | 0.830 | 95 | 76 |
| 3C × 2 AWG | 0.520 | 130 | 104 |
| 3C × 1/0 AWG | 0.328 | 170 | 136 |
| 3C × 2/0 AWG | 0.261 | 195 | 156 |
| 3C × 3/0 AWG | 0.207 | 225 | 180 |
| 3C × 4/0 AWG | 0.164 | 260 | 208 |
| 3C × 250 MCM | 0.139 | 290 | 232 |
| 3C × 350 MCM | 0.099 | 350 | 280 |
| 3C × 500 MCM | 0.070 | 430 | 344 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 3.5 kV AC dielectric test, spark test & DC resistance | Zero breakdown; resistance per CSA C22.2 No. 131 | 100 % of reels |
| Sample tests | ||
| -40 °C cold impact, -40 °C cold bend & XLPE hot-set | Passes -40 °C arctic hammer impact without jacket cracking | Every batch |
| CSA FT4 vertical tray flame, AG14 acid gas & HL crush test | CSA Certified Type TECK90 to C22.2 No. 131 | Type qualification |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.