VFD inverter to AC motor screened feeder
Low-capacitance 600/1000 V XLPE/CPE construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Product
SPEC 10000 600/1000 V TC-ER-HL combines stranded bare copper phases, XHHW-2 XLPE insulation, helical copper tape screening, and UL 2225 crush/impact protection for refinery and hazardous-area VFD drives.
Typical values for this cable type, based on UL 2225 Type TC-ER-HL · UL 1277 Type TC-ER · UL 44 XHHW-2 — confirmed in the datasheet and quotation for your order.
Application fit
SPEC 10000 600/1000 V TC-ER-HL combines stranded bare copper phases, XHHW-2 XLPE insulation, helical copper tape screening, and UL 2225 crush/impact protection for refinery and hazardous-area VFD drives.
Low-capacitance 600/1000 V XLPE/CPE construction and EMC screen suppress PWM switching noise between inverter and AC motor.
Balanced 600/1000 V XLPE/CPE geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.
Chemical- and mud-resistant 600/1000 V XLPE/CPE build suits offshore topside process modules, hazardous decks, and utility skids.
Durable 600/1000 V XLPE/CPE construction powers industrial process pumps, boosters, and compressor skids under continuous plant duty.
600/1000 V XLPE/CPE construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR600/1000 V XLPE/CPE build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.
Use RG / RG-D (N)SHTOEU-JConstruction
Representative construction of SPEC 10000 600/1000V TC-ER-HL: bare copper conductors, UL 44 XHHW-2 thermoset XLPE (90 °C), Helical bare copper tape shield + 3 symmetrical bare grounds, and Black oil-, chemical- & UV-resistant CPE/PVC jacket.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | ASTM B8 Class B stranded bare annealed copperASTM B8 Class B / UL 44 |
| 2 | Core insulation | UL 44 XHHW-2 thermoset XLPE (90 °C)UL 2225 Type TC-ER-HL |
| 3 | Core assembly & separator | Concentric cabled assembly with low-friction fleece or polyester binder tapeUL 2225 Type TC-ER-HL |
| 4 | EMC metallic screen | Helical bare copper tape shield + 3 symmetrical bare groundsEMC ≥ 85% / 100% foil |
| 5 | Outer sheath | Black oil-, chemical- & UV-resistant CPE/PVC jacketIEEE 1202 / FT4 Flame |
Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.
Technical data
Sizes
| Cores × AWG/kcmil | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 12×D mm |
|---|---|---|---|---|---|
| 3×14 AWG + 3×18 AWG | 12.1 | 8.450 | 118 | 246 | 145 |
| 3×12 AWG + 3×16 AWG | 13.1 | 5.310 | 169 | 328 | 157 |
| 3×10 AWG + 3×14 AWG | 14.4 | 3.340 | 248 | 452 | 173 |
| 3×8 AWG + 3×14 AWG | 17.7 | 2.100 | 343 | 643 | 212 |
| 3×6 AWG + 3×12 AWG | 19.8 | 1.320 | 519 | 919 | 238 |
| 3×4 AWG + 3×12 AWG | 23.4 | 0.832 | 748 | 1,313 | 281 |
| 3×2 AWG + 3×10 AWG | 27.8 | 0.523 | 1,156 | 1,982 | 334 |
| 3×1/0 AWG + 3×6 AWG | 32.0 | 0.329 | 1,936 | 3,144 | 384 |
| 3×2/0 AWG + 3×6 AWG | 34.5 | 0.261 | 2,326 | 3,751 | 414 |
| 3×4/0 AWG + 3×4 AWG | 41.1 | 0.164 | 3,656 | 5,778 | 493 |
| 3×350 kcmil + 3×2 AWG | 50.3 | 0.099 | 5,950 | 9,261 | 604 |
| 3×500 kcmil + 3×2 AWG | 57.5 | 0.070 | 8,062 | 12,468 | 690 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC high-voltage dielectric test | 4 kV AC for 5 min without breakdown | Every manufactured drum |
| Conductor DC resistance test | Per ASTM B172 / B8 at 20 °C | Every drum length |
| Sample tests | ||
| EMC screen coverage & insulation check | 100% Cu tape continuity & wall thickness | Per production lot |
| Flame & environmental qualification | IEEE 1202 / FT4 Flame · UL Oil Res I/II | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.