Fixed installation
Approved for direct burial, underground ducts, cable trays, and masonry walls per CEI 20-67 and EN 50575 CPR Cca.
Product
FG16(O)R16 EV Charging-Station DC Connection Cable is an Italian CEI UNEL 35318 and CEI 20-13 compliant flexible hybrid power-and-control feeder rated at 0.6/1 kV AC and up to 1.5 kV DC, combining Class 5 flexible plain copper main power conductors
Typical values for this cable type, based on CEI UNEL 35318 / CEI 20-13 / EN 50575 (FG16(O)R16 0.6/1 kV AC · 1.5 kV DC) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for interconnecting central DC power rectifier cabinets to satellite DC fast-charging dispensers (50 kW to 350 kW HPC), battery energy storage systems (BESS), and AC/DC commercial EV
Approved for direct burial, underground ducts, cable trays, and masonry walls per CEI 20-67 and EN 50575 CPR Cca.
Class 5 flexible copper and G16 elastomeric insulation bend at 4×D inside tight DC dispenser pedestals.
AD8 water-immersion capable G16 HEPR/R16 construction resists flooded service stationforecourt pits.
Fixed cabinet-to-dispenser interconnect cable; not a vehicle plug tether.
EV ProInstall Cat6A SWAConstruction
Class 5 flexible plain copper power conductors (16 mm² to 150 mm² in 2C, 3G, 4G, or 5G) insulated with 90 °C G16 HEPR elastomer, laid up
| # | Layer | Material & reference |
|---|---|---|
| 1 | Class 5 flexible copper power & pilot | EN 60228 Class 5 flexible annealed copper power cores (16–150 mm²) + Class 5 pilot coresCEI EN 60228 |
| 2 | G16 HEPR rubber insulation (90 °C) | High-modulus cross-linked ethylene-propylene elastomer (G16 per CEI 20-11) on power andCEI 20-13 / UNEL 35318 |
| 3 | Individual copper screen '(O)' on | Tinned copper wire braid (≥ 85 % coverage) + polyester wrap isolating the control/pilotCEI UNEL 35318 (O) |
| 4 | Inner filler / bedding | Flame-retardant elastomeric filler maintaining circular cross-sectionCEI 20-13 |
| 5 | R16 outer sheath (CPR Cca) | Special abrasion- and hydrocarbon-resistant PVC compound Type R16 (RAL 7001 Grey)CEI 20-11 / EN 50575 Cca |
DC+/DC- power cores + protective earth + copper-screened pilot pair for 50–350 kW DC satellite dispensers.
5 power cores + screened control pair for smart AC/DC chargers with remote emergency-stop and CAN/RS-485 link.
Technical data
Sizes
Nominal dimensions, copper weights, DC resistance and current ratings for FG16(O)R16 per CEI UNEL 35318 / CEI 20-13 / EN 50575 (FG16(O)R16 0.6/1 kV AC · 1.5
| Order designation | Cores × Size | Main cross-section | Outer Ø ≈ mm | Copper kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|
| Standard FG16(O)R16 configurations | |||||||
| FG16(O)R16 5G10 + 1×(2×1.5) mm² | 5G10 + (2×1.5) | 10.0 mm² | 21.4 | 525 | 760 | 107 | |
| FG16(O)R16 5G16 + 1×(2×1.5) mm² | 5G16 + (2×1.5) | 16.0 mm² | 24.2 | 815 | 1,090 | 121 | |
| FG16(O)R16 3G35 + 1×(2×1.5) mm² DC Link | 3G35 + (2×1.5) | 35.0 mm² | 27.5 | 1,060 | 1,410 | 138 | |
| FG16(O)R16 3G50 + 1×(2×1.5) mm² DC Link | 3G50 + (2×1.5) | 50.0 mm² | 31.2 | 1,510 | 1,950 | 156 | |
| FG16(O)R16 3G70 + 1×(2×1.5) mm² DC Link | 3G70 + (2×1.5) | 70.0 mm² | 35.6 | 2,090 | 2,640 | 178 | |
| FG16(O)R16 2×95 + 1G50 + 1×(2×1.5) mm² HPC DC | 2×95 + 1G50 + (2×1.5) | 95.0 mm² | 37.8 | 2,360 | 2,980 | 189 | |
| Configuration | Max. DC R @ 20 °C Ω/km | Iz free air A | Iz tray / duct A | Isc (1 s) kA | Voltage drop mV/A/m | Dielectric test V |
|---|---|---|---|---|---|---|
| 5G10 + (2×1.5) | 1.91 | 75 | 68 | 1.43 | 3.90 | 4,000 |
| 5G16 + (2×1.5) | 1.21 | 100 | 90 | 2.29 | 2.50 | 4,000 |
| 3G35 + (2×1.5) | 0.55 | 172 | 155 | 5.01 | 1.15 | 4,000 |
| 3G50 + (2×1.5) | 0.39 | 210 | 189 | 7.15 | 0.80 | 4,000 |
| 3G70 + (2×1.5) | 0.27 | 268 | 241 | 10.01 | 0.56 | 4,000 |
| 2×95 + 1G50 + (2×1.5) | 0.21 | 328 | 295 | 13.59 | 0.42 | 4,000 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 4.0 kV AC dielectric test on power & pilot cores | 4,000 V AC for 5 min per CEI 20-13 without breakdown | 100 % of drums |
| Class 5 DC conductor resistance @ 20 °C | CEI EN 60228 Class 5 flexible copper limits | 100 % of drums |
| Sample tests | ||
| G16 HEPR elastic modulus & hot-set test | CEI 20-11 G16 high-modulus cross-linking verification | Per production batch |
| EN 50399 CPR Cca-s3,d1,a3 fire & smoke test | Heat release, flame spread & droplet compliance | Notified body DoP |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.