Fixed installation
Helically cabled triplex bundle reduces mutual inductance, pulls in a single operation and separates cleanly for 3-phase terminations.
Product
RG7H1RX 12/20 (24) kV medium-voltage triplex power cable comprising three helically cabled single-core phases with Class 2 copper conductors, triple-extruded G7 HEPR insulation, H1 copper wire/tape metallic screens and individual red Rz PVC phase jackets.
Typical values for this cable type, based on CEI UNEL 35756 / IEC 60502-2 — confirmed in the datasheet and quotation for your order.
Application fit
RG7H1RX 12/20 (24) kV medium-voltage triplex power cable comprising three helically cabled single-core phases with Class 2 copper conductors, triple-extruded G7 HEPR insulation, H1 copper wire/tape metallic screens and individual red Rz PVC phase jackets.
Helically cabled triplex bundle reduces mutual inductance, pulls in a single operation and separates cleanly for 3-phase terminations.
High-modulus G7 HEPR insulation allows +90 °C continuous conductor temperature and +250 °C short-circuit rating.
Suitable for fixed gallery and culvert trays where CEI 20-22 II / IEC 60332-1-2 PVC is specified.
Class 2 rigid stranded copper triplex cable for static distribution; not for mobile reeling drums.
ARG7H1ORConstruction
Shown: RG7H1RX (CEI UNEL 35756 / IEC 60502-2) featuring phase conductors (3x1x50 mm²), conductor screen and triplex phase jackets (rx) (6-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Phase Conductors (3x1x50 mm²) | Class 2 compact circular stranded plain annealed copper conductors (Code R) in a visible three-phase triplex assemblyCEI UNEL 35756 / IEC 60502-2 |
| 2 | Conductor Screen | Extruded thermosetting semiconductive elastomer conductor screen ensuring void-free interface with the primary dielectricCEI UNEL 35756 / IEC 60502-2 |
| 3 | MV Primary Insulation (G7) | High-modulus ethylene propylene rubber (G7 HEPR) primary insulation rated for 90 °C continuous / 250 °C short-circuit serviceCEI UNEL 35756 / IEC 60502-2 |
| 4 | Insulation Screen | Cold-strippable extruded outer semiconductive elastomer insulation screen for clean medium-voltage terminationCEI UNEL 35756 / IEC 60502-2 |
| 5 | Metallic Phase Screen (H1) | Concentric layer of plain copper wires bound by an open counter-helix copper equalizing tape (H1) over each phaseCEI UNEL 35756 / IEC 60502-2 |
| 6 | Triplex Phase Jackets (RX) | Three individual flame-retardant red Rz PVC outer sheaths helically cabled into a self-supporting triplex bundle (RX)CEI UNEL 35756 / IEC 60502-2 |
Built to CEI UNEL 35756 / IEC 60502-2 with phase conductors (3x1x50 mm²) and triplex phase jackets (rx)
Available in custom drum lengths, core counts or factory-terminated assemblies
Supplied with EN 10204 3.1 routine electrical, dielectric & dimensional inspection report
Technical data
Sizes
Manufactured to CEI UNEL 35756 / IEC 60502-2 for heavy-duty industrial and specialty engineering systems.
| Order designation | Configuration | Core / stranding | Outer Ø ≈ mm | Weight ≈ kg/km | Tensile load kN ≈ | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| RG7H1RX Construction Schedule (−25…+90 °C) | |||||||
| RG7H1RX 3×(1×35/16) mm² 12/20 kV | 3 × (1 × 35/16 mm² Cu) | Class 2 Cu + H1 wire/tape screen | 53.0 | 2,490 | 18.0 | 795 | |
| RG7H1RX 3×(1×50/16) mm² 12/20 kV | 3 × (1 × 50/16 mm² Cu) | Class 2 Cu + H1 wire/tape screen | 56.0 | 2,980 | 25.5 | 840 | |
| RG7H1RX 3×(1×70/16) mm² 12/20 kV | 3 × (1 × 70/16 mm² Cu) | Class 2 Cu + H1 wire/tape screen | 60.0 | 3,740 | 35.5 | 900 | |
| RG7H1RX 3×(1×95/16) mm² 12/20 kV | 3 × (1 × 95/16 mm² Cu) | Class 2 Cu + H1 wire/tape screen | 64.0 | 4,680 | 48.0 | 960 | |
| RG7H1RX 3×(1×120/16) mm² 12/20 kV | 3 × (1 × 120/16 mm² Cu) | Class 2 Cu + H1 wire/tape screen | 68.0 | 5,620 | 60.5 | 1,020 | |
| Configuration | Max. DC R₂₀ / Atten. Ω/km or dB/km | Rating / Capacity | Operating temp. |
|---|---|---|---|
| 3 × (1 × 35/16 mm² Cu) | 0.52 | 12/20 kV / 178 A | −25…+90 °C |
| 3 × (1 × 50/16 mm² Cu) | 0.39 | 12/20 kV / 212 A | −25…+90 °C |
| 3 × (1 × 70/16 mm² Cu) | 0.27 | 12/20 kV / 262 A | −25…+90 °C |
| 3 × (1 × 95/16 mm² Cu) | 0.19 | 12/20 kV / 316 A | −25…+90 °C |
| 3 × (1 × 120/16 mm² Cu) | 0.15 | 12/20 kV / 362 A | −25…+90 °C |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & dimensional verification (CEI UNEL 35756 / IEC 60502-2) | Electrical parameters and outer diameter within CEI UNEL 35756 / IEC 60502-2 tolerances | Every manufactured drum / length |
| High-voltage dielectric & insulation resistance test (CEI UNEL 35756 / IEC 60502-2) | Zero dielectric breakdown and verified insulation resistance over full length | Every manufactured drum / length |
| Sample tests | ||
| Thermal ageing, mechanical flexing & environmental qualification (CEI UNEL 35756 / IEC 60502-2) | Verified structural and dielectric integrity across −25…+90 °C | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.