FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened CableCEI UNEL 35375 / CEI 20-38 · 0.6/1 kV · -25 °C to +90 °C industrial FG16HOHM16 construction

FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened LSZH Instrument Cable (FG16HOHM16) engineered to CEI UNEL 35375 / CEI 20-38 for 0.6/1 kV service across -25 °C to +90 °C, featuring stranded bare & tinned copper conductor and m16 lszh outer

Approved
Low-EMC design
EMC screen
Flame-retardant
Order designation
FG16HOHM16 4×2×1.0
Outer Ø ≈
13.5 mm
Total weight ≈
264 kg/km
Min. bend R (fixed)
108 mm
Configuration
4×2×1.0 mm²
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
Per CEI UNEL 35375 / CEI 20-38
Operating temp.
−25…+90 °C
Continuous thermal rating
Min. bend radius
10 × OD
Installed / fixed routing
Conductor
bare & tinned
High-conductivity bare & tinned
Outer layer
M16 LSZH outer
Extruded M16 LSZH outer sheath
Standard
CEI UNEL 35375
CEI UNEL 35375 / CEI 20-38

Typical values for this cable type, based on CEI UNEL 35375 / CEI 20-38 — confirmed in the datasheet and quotation for your order.

Application fit

Is FG16HOHM16 right for your machine?

FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened LSZH Instrument Cable (FG16HOHM16) engineered to CEI UNEL 35375 / CEI 20-38 for 0.6/1 kV service across -25 °C to +90 °C, featuring stranded bare & tinned copper conductor and m16 lszh outer

Fixed installation

Suitable

Engineered and verified for fixed service in accordance with CEI UNEL 35375 / CEI 20-38.

Switchgear & control cabinet wiring

Suitable

Suitable for switchgear, control panels and equipment terminations within 10 × OD bend radius.

TBM gantry & advancing tunnel reel

With conditions

Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.

Motorised monospiral reel

Not suitable

Not designed for high-speed monospiral crane reeling; select a dedicated reeling cable.

NSHTOU Reeling Cable
Typical machinesOil & Gas CableRefinery & Petrochemical Process UnitsLNG Terminals & Tank FarmsOnshore & Offshore Oil & Gas FacilitiesChemical & Hydrocarbon Processing PlantsCommercial & Residential Building Distribution

Construction

Layer by layer

Shown: FG16HOHM16 (CEI UNEL 35375 / CEI 20-38) with stranded bare & tinned copper conductor, polyester pair wrap and m16 lszh outer sheath (7-layer construction).

1234567
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Stranded bare & tinned copper conductorHigh-conductivity bare & tinned copper conductor per CEI UNEL 35375 / CEI 20-38CEI UNEL 35375 / CEI 20-38
2Polyester pair wrapHelically applied polyester pair wrapCEI UNEL 35375 / CEI 20-38
3Al/PET individual screenAl/PET individual screen metallic electromagnetic screen (individual core / group layer)CEI UNEL 35375 / CEI 20-38
4PET polyester overwrapHelically applied pet polyester overwrapCEI UNEL 35375 / CEI 20-38
5EPR G16 core insulationExtruded EPR G16 dielectric (individual core / group layer)CEI UNEL 35375 / CEI 20-38
6Overall copper braidOverall copper braid high-coverage braided layer (woven structure)CEI UNEL 35375 / CEI 20-38
7M16 LSZH outer sheathExtruded M16 LSZH outer sheath protective layer (continuous layer)CEI UNEL 35375 / CEI 20-38

FG16HOHM16 — Standard Execution

Built to CEI UNEL 35375 / CEI 20-38 with stranded bare & tinned copper conductor and m16 lszh outer sheath

FG16HOHM16 — Custom Cross-Sections

Full range of metric mm² and AWG/kcmil conductor sizes per CEI UNEL 35375 / CEI 20-38

FG16HOHM16 — Export Drum Supply

Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on CEI UNEL 35375 / CEI 20-38. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / duty
0.6/1 kV (CEI UNEL 35375 / CEI 20-38)
Conductor construction
Stranded bare & tinned copper conductor — High-conductivity bare & tinned copper conductor per CEI UNEL 35375 / CEI 20-38
Primary insulation / dielectric
Polyester pair wrap — Helically applied polyester pair wrap

Thermal

Continuous operating temperature
−25…+90 °C per CEI UNEL 35375 / CEI 20-38
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s adiabatic limit depending on dielectric class)
Minimum installation temperature
−5 °C (thermoplastic) / −25 °C (cross-linked or elastomer) / −40 °C (metallic)

Mechanical

Outer protection / covering
M16 LSZH outer sheath — Extruded M16 LSZH outer sheath protective layer (continuous layer)
Minimum bending radius
10 × OD (installed / static routing)
Layer count & geometry
7 concentric/structural layers verified by cross-section inspection

Resistance

Environmental & chemical durability
Engineered for industrial service in accordance with CEI UNEL 35375 / CEI 20-38
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing product standard
CEI UNEL 35375 / CEI 20-38
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
FG16HOHM16
Customs tariff (HS)
8544.49 / 8544.60 / 7614.10

Sizes

12 standard FG16HOHM16 cable configurations

Manufactured to CEI UNEL 35375 / CEI 20-38 in single-pair, multi-pair and multi-unit constructions.

Dimensions, construction & weights
Order designationConfigurationOuter Ø ≈
mm
Weight ≈
kg/km
Min. bend R
fixed mm
Enquiry
FG16HOHM16 Standard Construction Schedule (0.6/1 kV · −25…+90 °C)
FG16HOHM16 1×2×0.51×2×0.5 mm²6.45852
FG16HOHM16 2×2×0.52×2×0.5 mm²9.211274
FG16HOHM16 4×2×0.54×2×0.5 mm²11.417692
FG16HOHM16 8×2×0.58×2×0.5 mm²14.8295118
FG16HOHM16 12×2×0.512×2×0.5 mm²17.6420141
FG16HOHM16 1×2×1.01×2×1.0 mm²7.68661
FG16HOHM16 2×2×1.02×2×1.0 mm²11.016888
FG16HOHM16 4×2×1.04×2×1.0 mm²13.5264108
FG16HOHM16 8×2×1.08×2×1.0 mm²17.9465143
FG16HOHM16 1×2×1.51×2×1.5 mm²8.511468
FG16HOHM16 4×2×1.54×2×1.5 mm²15.2348122
FG16HOHM16 12×2×1.512×2×1.5 mm²23.4860187
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Additional pair/triad/quad counts (up to 48 pairs) and blue Ex-i intrinsically safe outer sheaths available per CEI UNEL 35375 / CEI 20-38.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor DC resistance & dimensional verification (CEI UNEL 35375 / CEI 20-38)DC resistance at 20 °C and geometry within CEI UNEL 35375 / CEI 20-38 class limitsEvery manufactured drum / spool
Routine dielectric / spark / structural integrity test (CEI UNEL 35375 / CEI 20-38)Zero breakdown or structural defect over full production lengthEvery manufactured drum / spool
Sample tests
Thermal aging, mechanical & material qualification (CEI UNEL 35375 / CEI 20-38)Full compliance with CEI UNEL 35375 / CEI 20-38 across −25…+90 °CType qualification & periodic sample audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

CEI UNEL 35375 CompliantEN 10204 3.1 Routine Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX FG16HOHM16 <size> CEI UNEL 35375 0.6/1 kV CE
Delivery form
Non-returnable fumigated wooden drums or precision DIN spools
Standard lengths
500 m · 1000 m · 2000 m drums (custom cut lengths on request)
MOQ
500 m (stock sizes) · 1000 m (custom production)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-21
Updated
2026-10-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define FG16HOHM16 (FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened LSZH Instrument Cable)?
FG16HOHM16 (FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened LSZH Instrument Cable) is manufactured in accordance with CEI UNEL 35375 / CEI 20-38 for 0.6/1 kV service over -25 °C to +90 °C. Its 7-layer construction comprises stranded bare & tinned copper conductor, polyester pair wrap, al/pet individual screen, pet polyester overwrap, epr g16 core insulation, overall copper braid, m16 lszh outer sheath.
What is the minimum bending radius and installation temperature for FG16HOHM16?
The minimum installed bending radius for FG16HOHM16 is 10 × OD across its continuous operating temperature range of -25 °C to +90 °C, ensuring mechanical and dielectric stability without conductor or insulation strain.
How are the concentric layers of FG16HOHM16 arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Stranded bare & tinned copper conductor (High-conductivity bare & tinned copper conductor per CEI UNEL 35375 / CEI 20-38); (02) Polyester pair wrap (Helically applied polyester pair wrap); (03) Al/PET individual screen (Al/PET individual screen metallic electromagnetic screen (individual core / group layer)); (04) PET polyester overwrap (Helically applied pet polyester overwrap); (05) EPR G16 core insulation (Extruded EPR G16 dielectric (individual core / group layer)); (06) Overall copper braid (Overall copper braid high-coverage braided layer (woven structure)); (07) M16 LSZH outer sheath (Extruded M16 LSZH outer sheath protective layer (continuous layer)).
What factory test certificates are supplied with FG16HOHM16?
Every production drum or spool of FG16HOHM16 undergoes routine conductor DC resistance, dimensional and dielectric/integrity testing per CEI UNEL 35375 / CEI 20-38, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for FG16HOHM16

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

FG16HOHM16 0.6/1 kV HEPR-Insulated Individual & Overall Screened Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote