Contact
ASTM B976 ACCRASTM B976 / IEEE 738Up to 500 kV AC−40…+210 °C

Aluminum Conductor Composite Reinforced Overhead ConductorASTM B976 / IEEE 738 · Up to 500 kV AC · -40 °C to +210 °C industrial ACCR construction

Aluminum Conductor Composite Reinforced Overhead Conductor (ACCR) engineered to ASTM B976 / IEEE 738 for Up to 500 kV AC service across -40 °C to +210 °C, featuring al₂o₃ metal-matrix composite (mmc) core and heat-resistant al-zr outer stranding layers with

Approved
Outdoor & humid
Ozone, UV & moisture
Order designation
ACCR 240 mm²
Outer Ø ≈
21.8 mm
Total weight ≈
885 kg/km
Rated tensile ≈
84.5 kN
Stranding
26/3.44 + 7/2.68
All sizes (10)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
Up to 500 kV AC
Per ASTM B976 / IEEE 738
Operating temp.
−40…+210 °C
Continuous thermal rating (ASTM B976)
Min. bend radius
20 × OD
Installed / fixed routing
Conductor
Al₂O₃ metal-matr
Stranded continuous alumina ceramic
Outer layer
Heat-resistant
Concentric stranded
Standard
ASTM B976
ASTM B976 / IEEE 738

Typical values for this cable type, based on ASTM B976 / IEEE 738 — confirmed in the datasheet and quotation for your order.

Application fit

Is ACCR right for your machine?

Aluminum Conductor Composite Reinforced Overhead Conductor (ACCR) engineered to ASTM B976 / IEEE 738 for Up to 500 kV AC service across -40 °C to +210 °C, featuring al₂o₃ metal-matrix composite (mmc) core and heat-resistant al-zr outer stranding layers with

Fixed installation

Suitable

Engineered and verified for fixed service in accordance with ASTM B976 / IEEE 738.

Switchgear & control cabinet wiring

Suitable

Suitable for switchgear, control panels and equipment terminations within 20 × OD bend radius.

TBM gantry & advancing tunnel reel

With conditions

Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.

Motorised monospiral reel

Not suitable

Not designed for high-speed monospiral crane reeling; select a dedicated reeling cable.

NSHTOU Reeling Cable
Typical machinesRenewable Energy & EV ChargingHigh-Voltage Grid & Substation InterconnectsWind, Solar & Hydro Power EvacuationUtility Overhead & Underground DistributionIndustrial Power InfrastructureMetallurgical, Glass & Ceramic Furnaces

Construction

Layer by layer

Shown: ACCR (ASTM B976 / IEEE 738) with al₂o₃ metal-matrix composite (mmc) core, heat-resistant al-zr outer stranding layers and heat-resistant al-zr outer stranding layers (2-layer construction).

12
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Al₂O₃ metal-matrix composite (MMC) coreStranded continuous alumina ceramic fiber in pure aluminum matrix core wiresASTM B976 / IEEE 738
2Heat-resistant Al-Zr outer stranding layersConcentric stranded aluminum-zirconium (AT1 / AT2) thermal-resistant outer wires (+210 °C)ASTM B976 / IEEE 738

ACCR — Standard Execution

Built to ASTM B976 / IEEE 738 with al₂o₃ metal-matrix composite (mmc) core and heat-resistant al-zr outer

ACCR — Custom Cross-Sections

Full range of metric mm² and AWG/kcmil conductor sizes per ASTM B976 / IEEE 738

ACCR — Export Drum Supply

Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on ASTM B976 / IEEE 738. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / duty
Up to 500 kV AC (ASTM B976 / IEEE 738)
Conductor construction
Al₂O₃ metal-matrix composite (MMC) core — Stranded continuous alumina ceramic fiber in pure aluminum matrix core wires
Primary insulation / dielectric
Heat-resistant Al-Zr outer stranding layers — Concentric stranded aluminum-zirconium (AT1 / AT2) thermal-resistant outer wires (+210 °C)

Thermal

Continuous operating temperature
−40…+210 °C per ASTM B976 / IEEE 738
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s adiabatic limit depending on dielectric class)
Minimum installation temperature
−5 °C (thermoplastic) / −25 °C (cross-linked or elastomer) / −40 °C (metallic)

Mechanical

Outer protection / covering
Heat-resistant Al-Zr outer stranding layers — Concentric stranded aluminum-zirconium (AT1 / AT2) thermal-resistant outer wires (+210 °C)
Minimum bending radius
20 × OD (installed / static routing)
Layer count & geometry
2 concentric/structural layers verified by cross-section inspection

Resistance

Environmental & chemical durability
Engineered for industrial service in accordance with ASTM B976 / IEEE 738
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing product standard
ASTM B976 / IEEE 738
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
ACCR
Customs tariff (HS)
8544.49 / 8544.60 / 7614.10

Sizes

10 standard ACCR overhead conductor sizes

Manufactured to ASTM B976 / IEEE 738 in standard cross-sections from 50 mm² to 630 mm² (and North American AWG/kcmil code words).

Dimensions, stranding, breaking load & weights
Order designationNominal areaStrandingOuter Ø ≈
mm
Weight ≈
kg/km
Rated tensile
kN ≈
Min. sheave R
mm
Enquiry
ACCR Standard Transmission & Distribution Schedule (−40…+210 °C)
ACCR 50 mm²50 mm²7/3.00 mm9.013814.5180
ACCR 95 mm²95 mm²19/2.52 mm12.626228.2252
ACCR 120 mm²120 mm²19/2.85 mm14.333436.4286
ACCR 150 mm²150 mm²26/2.70 + 7/2.1017.154653.8342
ACCR 185 mm²185 mm²26/3.00 + 7/2.3319.067465.2380
ACCR 240 mm²240 mm²26/3.44 + 7/2.6821.888584.5436
ACCR 300 mm²300 mm²26/3.86 + 7/3.0024.51,110104.2490
ACCR 400 mm²400 mm²54/3.08 + 7/3.0827.71,432126.0554
ACCR 500 mm²500 mm²54/3.44 + 7/3.4431.01,790156.5620
ACCR 630 mm²630 mm²54/3.86 + 19/2.3234.82,245194.0696
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Custom kcmil/code-word sizes, grease-filled corrosion protection and non-specular surface finishes available per ASTM B976 / IEEE 738.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor DC resistance & dimensional verification (ASTM B976 / IEEE 738)DC resistance at 20 °C and geometry within ASTM B976 / IEEE 738 class limitsEvery manufactured drum / spool
Routine dielectric / spark / structural integrity test (ASTM B976 / IEEE 738)Zero breakdown or structural defect over full production lengthEvery manufactured drum / spool
Sample tests
Thermal aging, mechanical & material qualification (ASTM B976 / IEEE 738)Full compliance with ASTM B976 / IEEE 738 across −40…+210 °CType qualification & periodic sample audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

ASTM B976 CompliantEN 10204 3.1 Routine Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX ACCR <size> ASTM B976 Up to 500 kV AC CE
Delivery form
Non-returnable fumigated wooden drums or precision DIN spools
Standard lengths
500 m · 1000 m · 2000 m drums (custom cut lengths on request)
MOQ
500 m (stock sizes) · 1000 m (custom production)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-21
Updated
2026-10-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define ACCR (Aluminum Conductor Composite Reinforced Overhead Conductor)?
ACCR (Aluminum Conductor Composite Reinforced Overhead Conductor) is manufactured in accordance with ASTM B976 / IEEE 738 for Up to 500 kV AC service over -40 °C to +210 °C. Its 2-layer construction comprises al₂o₃ metal-matrix composite (mmc) core, heat-resistant al-zr outer stranding layers.
What is the minimum bending radius and installation temperature for ACCR?
The minimum installed bending radius for ACCR is 20 × OD across its continuous operating temperature range of -40 °C to +210 °C, ensuring mechanical and dielectric stability without conductor or insulation strain.
How are the concentric layers of ACCR arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Al₂O₃ metal-matrix composite (MMC) core (Stranded continuous alumina ceramic fiber in pure aluminum matrix core wires); (02) Heat-resistant Al-Zr outer stranding layers (Concentric stranded aluminum-zirconium (AT1 / AT2) thermal-resistant outer wires (+210 °C)).
What factory test certificates are supplied with ACCR?
Every production drum or spool of ACCR undergoes routine conductor DC resistance, dimensional and dielectric/integrity testing per ASTM B976 / IEEE 738, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for ACCR

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

ACCR Aluminum Conductor Composite Reinforced Overhead Conductor

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote