Screened power & VFD / motor supply cablesUL TC-ER 2 kV · WTTC 1 kVClass K Tinned Cu · RHW-2Al/PET + ≥ 85% TCWB · Oil-Res PVC

A219 2 kV RHW-2 3C+3G Symmetrical VFD CableClass K tinned Cu 2 kV RHW-2 / WTTC VFD cable

Flexible 2,000 V UL Type TC-ER / RHW-2 and 1,000 V WTTC symmetrical 3C+3G VFD cable with Class K tinned copper conductors, thick-wall 90 °C XLPE insulation, Al/PET plus ≥ 85% TCWB shield, and oil-resistant PVC jacket.

Low-EMC design
EMC screen
Oil-resistant
Flame-retardant
Order designation
A219 2kV VFD 3×2 AWG + 3×10 AWG
Outer Ø
31.1 mm
Max. R20
0.561 Ω/km
Weight
2,210 kg/km
Min. bend R
187 mm
All sizes (11)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
2 kV / 1 kV
2 kV TC-ER RHW-2 · 1 kV WTTC
EMC screening
Al/PET + TCWB
100% foil + tinned copper braid
Conductor class
Class K tin Cu
Fine-wire ASTM B33 / B172 stranding
Conductor temp.
+90 °C dry/wet
Thick-wall thermoset RHW-2 XLPE
Min. bend radius
6 × OD
Flexible exposed-run tray routing
Size range
6 AWG–500 MCM
3C + 3× GNYE insulated grounds

Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHW-2 · UL 2277 WTTC · CSA C22.2 — confirmed in the datasheet and quotation for your order.

Application fit

Is A219 2kV RHW-2 3C+3G VFD right for your machine?

Flexible 2,000 V UL Type TC-ER / RHW-2 and 1,000 V WTTC symmetrical 3C+3G VFD cable with Class K tinned copper conductors, thick-wall 90 °C XLPE insulation, Al/PET plus ≥ 85% TCWB shield, and oil-resistant PVC jacket.

VFD inverter to AC motor screened feeder

Suitable

Thick-wall 2 kV RHW-2 XLPE plus Al/PET and ≥ 85% TCWB suppress corona and reflected-wave spikes.

Wind turbine tower & nacelle (WTTC)

Suitable

UL 2277 WTTC (1,000 V) and UL 1277 TC-ER (2,000 V) approval covers wind turbine tower and nacelle runs.

Motor stator, traction & converter leads

Suitable

Class K fine-wire tinned copper (6 × OD bend) speeds heavy-gauge motor and converter cabinet pulls.

Fixed installation

Suitable

Easy-strip Oil Res I/II, washdown-, UV- and direct-burial-rated PVC jacket meets NFPA 79 & NEC Art. 336.

Energy chain / drag chain

Not suitable

Built for trays, wind towers, and exposed machine drops rather than high-speed continuous drag chains.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not rated for motorised cable drums; select a PUR or rubber reeling cable for mobile spooling.

Use GPM-RF PUR Reeling
Typical machinesRenewable Energy & EV ChargingIndustrial automation & OEM machinesWind turbine nacelles & towers (WTTC)Food, beverage & washdown plantsPulp, paper & heavy manufacturingNorth American NEC Class I Div 2 trays

Construction

Layer by layer

Shown: A219 2 kV RHW-2 3C+3G VFD 3×2 AWG + 3×10 AWG — Class K fine-wire tinned copper phases and three green/yellow grounds under thick RHW-2 XLPE, Al/PET foil, ≥ 85% TCWB, and oil-resistant PVC.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass K fine-wire stranded tinned annealed copperASTM B33 / B172 Class K
2Phase & earth insulation2 kV thick-wall thermoset RHW-2 XLPE (Black w/ white numbers)UL 44 RHW-2 + 3 × GNYE insulated grounds
3Core wrapNon-woven polyester core wrap over 3C+3G bundleEasy-strip circular geometry
4Foil EMI shieldAluminium/polyester laminate foil shield (100% coverage)High-frequency EMI barrier
5Braid EMI shieldTinned copper wire braid shield (≥ 85%) + separator tapeLow-impedance 360° EMC shield
6Outer jacketBlack easy-strip oil- & washdown-resistant PVC (RAL 9005)UL 1277 Oil Res I/II · Sunlight Resistant

A219 2 kV RHW-2 (3C+3G)

Three black numbered RHW-2 XLPE phases + three green/yellow insulated Class K tinned Cu grounds under Al/PET + ≥ 85% TCWB (6 AWG–500 kcmil).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 1277 Type TC-ER · UL 44 RHW-2 · UL 2277 WTTC · CSA C22.2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
2,000 V TC-ER/RHW-2 · 1,000 V WTTC
Conductor class
ASTM B172 Class K tinned copper
Dual EMI shield
100% Al/PET foil + ≥ 85% TCWB

Thermal

Max. conductor temp.
+90 °C dry or wet (RHW-2)
Ambient temp. (fixed)
−40 °C to +90 °C
Min. bending radius
6 × OD (Class K flexible)

Resistance

Flame test
UL 1685 / IEEE 1202 / CSA FT4
Oil & UV ratings
Oil Res I/II · Sunlight · Direct Burial
Hazardous locations
NEC Class I Div 2 / NFPA 79

Sizes

3C+3G Symmetrical (Class K Tinned Cu)
Phase + 3×
GNYE (AWG)
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
6×D mm
3×6 AWG + 3×12 AWG23.01.4205361,072138
3×4 AWG + 3×12 AWG26.70.8927661,500160
3×2 AWG + 3×10 AWG31.10.5611,1762,210187
3×1 AWG + 3×8 AWG33.10.4451,5092,729199
3×1/0 AWG + 3×6 AWG35.30.3531,9573,410212
3×2/0 AWG + 3×6 AWG37.80.2802,3484,043227
3×3/0 AWG + 3×4 AWG41.30.2223,0605,154248
3×4/0 AWG + 3×4 AWG44.50.1763,6806,146267
3×250 kcmil + 3×4 AWG48.60.1494,2307,128292
3×350 kcmil + 3×2 AWG54.30.1075,9799,789326
3×500 kcmil + 3×2 AWG61.50.0758,09313,096369
  • Conductor max. DC resistance R20 follows ASTM B33 / B172 Class K fine-wire tinned copper at 20 °C.
  • Dual-rated 2,000 V UL Type TC-ER (RHW-2) and 1,000 V UL 2277 WTTC for industrial trays, exposed runs, and wind turbines.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric testPer UL 44 RHW-2 2,000 V ratingEvery manufactured reel
Conductor DC resistance checkPer ASTM B33 / B172 Class K at 20 °CEvery reel length
Sample tests
TC-ER crush, impact & Oil Res IIUL 1277 crush/impact & oil immersionPer production lot
Vertical tray flame testUL 1685 / IEEE 1202 / CSA FT4Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 1277 Type TC-ER (2,000 V) · UL 44 RHW-2UL 2277 WTTC (1,000 V) · NFPA 79 CompliantCSA C22.2 No. 230/239 · FT4 / IEEE 1202 · Oil Res I/II

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

A219 2kV RHW-2 3C+3G VFD TEBAOFLEX.COM UL TC-ER 2000V WTTC 1000V [Size]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

Why does A219 use thick-wall 2 kV RHW-2 XLPE on 480 V or 690 V VFD systems?
Fast-switching IGBT inverters generate reflected standing-wave voltage peaks exceeding 1,400 V on long motor runs. Heavy-wall 2 kV RHW-2 XLPE provides corona-free dielectric margin and lowers cable capacitance.
What advantage does Class K tinned copper offer over Class B bare copper?
Class K fine-wire tinned stranding sharply improves bendability (6 × OD vs. 12 × OD), resists industrial vibration and corrosion, and speeds cabinet routing without special pulling tension.
Can A219 2 kV be installed outside cable trays without conduit?
Yes. UL Type TC-ER (Exposed Run) approval permits unsupported exposed-run drops from cable tray to motor or drive enclosures in accordance with NEC Article 336.
How should the EMC shield and symmetrical grounds of A219 2kV RHW-2 3C+3G VFD be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for A219 2kV RHW-2 3C+3G VFD

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

A219 2 kV RHW-2 3C+3G Symmetrical VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 