Contact

9409 300V PLTC / CMG 1-Pair 18 AWG Process Instrumentation CableUL 13 PLTC / UL 2250 ITC / CMG FT4 (300 V, -30 to +105 °C) 1-pair 18 AWG (16×30) tinned copper unshielded tray instrumentation cable for 4–20 mA and HART loops.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Oil-resistant
Outdoor & humid
Approved
Order designation
9409 1 Pair × 18 AWG (16×30) PLTC
Outer diameter
5.6 mm
Cable weight
42 kg/km
Min. bend radius
45 mm
Conductor & shield
16×30 AWG Tinned Cu + 105 °C PVC + Ripcord
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
300 V
UL 13 PLTC / UL 444 CMG
Temperature
−30…+105 °C
Fixed / flex duty
Min. bend radius
8 × OD
5.6–9.9 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
Industrial PVC
Oil & sunlight resistant
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per UL 13 PLTC / UL 444 CMG (9409 300V PLTC / CMG) — confirmed in the datasheet and quotation for your order.

Application fit

Is 9409 300V PLTC / CMG right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for open cable tray, raceway and supported industrial runs per standard installation rules.

Switchgear & control cabinet wiring

Suitable

Controlled characteristic impedance and low mutual capacitance preserve signal eye opening over long trunks.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

Offshore platform & shipboard deck trays

Suitable

Outer sheath compound resists industrial cutting fluids, mineral oils and outdoor sunlight.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use TRA 0.6/1 kV PUR Reeling Cable

Process instrumentation & DCS field loop

Suitable

Low-noise 300 V PVC pair/core geometry preserves 4–20 mA and sensor signals from field transmitters to DCS marshalling cabinets.

Typical machinesOil & Gas CableIndustrial automation & control cabinetsInverter-fed motor drive systemsProcess instrumentation & oil/gas skidsMachine tools & robotic cellsData centers, stadiums & broadcast facilities

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

9409 300V PLTC / CMG – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
11 Twisted Pair (18 AWG Tinned Copper)16×30 AWG Stranded Tinned Copper Conductors
2105 °C Flame-Retardant PVC InsulationBlack & Red Color-Coded 0.41mm PVC Core Insulation
3Precision Short-Lay Pair Twist + Ripcord50.8mm Twist Lay for Balanced CMRR + Nylon Ripcord
4Chrome Grey Sunlight-Resistant PVC JacketUL 13 PLTC / CMG / ITC Rated Outer Sheath (5.64 mm OD)

1 × 2 × 18 AWG (0.82 mm²)

16×30 AWG Tinned Cu + 105 °C PVC + Ripcord · Outer diameter 5.64 mm.

2 × 2 × 18 AWG (0.82 mm²)

16×30 AWG Tinned Cu + 105 °C PVC + Ripcord · Outer diameter 8.15 mm.

4 × 2 × 18 AWG (0.82 mm²)

16×30 AWG Tinned Cu + 105 °C PVC + Ripcord · Outer diameter 9.95 mm.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per UL 13 PLTC / UL 444 CMG (9409 300V PLTC / CMG). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
300 V
Conductor & core insulation
16×30 AWG Stranded Tinned Copper Conductors · Black & Red Color-Coded 0.41mm PVC Core Insulation
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
−30…+105 °C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
UL 13 PLTC / UL 444 CMG

Mechanical

Minimum bending radius
8 × OD
Screening / armour architecture
Unshielded multi-core construction · mechanical protection via outer jacket
Outer sheath material & colour
UL 13 PLTC / CMG / ITC Rated Outer Sheath (5.64 mm OD)

Reference standards

Reference standard
UL 13 PLTC / UL 2250 ITC / UL 444 CMG / CSA C22.2 No. 214 FT4 / IEEE 1202
Hazardous Substance Compliance
CE, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Copper weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
9409 300V PLTC / CMG
1 × 2 × 18 AWG (0.82 mm²)16×30 AWG Tinned Cu + 105 °C PVC + RipcordBlack & Red Color-Coded 0.41mm PVC Core InsulationIndustrial PVC5.64521.9015.842300 V · 88.6 pF/m (27 pF/ft) · 0.56 µH/m9409 1 Pair × 18 AWG (16×30) PLTC
2 × 2 × 18 AWG (0.82 mm²)16×30 AWG Tinned Cu + 105 °C PVC + RipcordBlack & Red Color-Coded 0.41mm PVC Core InsulationIndustrial PVC8.26521.9031.678300 V · 88.6 pF/m (27 pF/ft) · 0.56 µH/m9409-2P 2 Pairs × 18 AWG (16×30) PLTC
4 × 2 × 18 AWG (0.82 mm²)16×30 AWG Tinned Cu + 105 °C PVC + RipcordBlack & Red Color-Coded 0.41mm PVC Core InsulationIndustrial PVC10.08021.9063.2134300 V · 88.6 pF/m (27 pF/ft) · 0.56 µH/m9409-4P 4 Pairs × 18 AWG (16×30) PLTC
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °CEvery manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation or shieldEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing within standard char limitType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 13 PLTC / UL 444 CMG CompliantEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX 9409 300V PLTC / CMG UL 13 PLTC / UL 444 CMG 300 V CE ROHS — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
305 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-03
Updated
2026-11-03

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is 9409 300V PLTC / CMG designed for?
9409 300V PLTC / CMG is engineered for industrial installations under UL 13 PLTC / UL 444 CMG, operating over −30…+105 °C with a minimum bending radius of 8 × OD.
How does the construction of 9409 300V PLTC / CMG protect signal and power integrity?
Its multi-layer build combines 1 Twisted Pair (18 AWG Tinned Copper) with 105 °C Flame-Retardant PVC Insulation and Chrome Grey Sunlight-Resistant PVC Jacket to ensure mechanical stability and electrical performance.
What standards and fire ratings apply to 9409 300V PLTC / CMG?
The cable is qualified to UL 13 PLTC / UL 2250 ITC / UL 444 CMG / CSA C22.2 No. 214 FT4 / IEEE 1202, meeting vertical flame propagation and industrial jacket durability requirements.
Can 9409 300V PLTC / CMG be supplied in custom lengths or configurations?
Yes. Standard configurations include 9409 1 Pair × 18 AWG (16×30) PLTC, 9409-2P 2 Pairs × 18 AWG (16×30) PLTC and 9409-4P 4 Pairs × 18 AWG (16×30) PLTC, supplied on 305 m, 500 m or 1,000 m export drums.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 9409 300V PLTC / CMG

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

9409 300V PLTC / CMG 1-Pair 18 AWG Process Instrumentation Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp