Fixed installation
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Product
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Typical values for this cable type, based on Reference specification per UL 1277 TC-ER / UL 1424 NPLF (1121A 600V TC-ER / 150V NPLF) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Controlled characteristic impedance and low mutual capacitance preserve signal eye opening over long trunks.
Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.
Outer sheath compound resists industrial cutting fluids, mineral oils and outdoor sunlight.
Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.
Use TRA 0.6/1 kV PUR Reeling CableLow-noise 600/150 V PVC pair/core geometry preserves 4–20 mA and sensor signals from field transmitters to DCS marshalling cabinets.
Construction
Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

| # | Layer | Material & reference |
|---|---|---|
| 1 | 1 Triad (3×18 AWG Stranded Bare Copper) | 7×26 AWG Stranded Bare Copper Triad |
| 2 | PVC/Nylon (THHN/THWN) Core Insulation | Black, Red, Blue Numbered 600 V PVC/Nylon |
| 3 | 100% Aluminum/Polyester Foil Shield | Overall Foil Tape Screen + 20 AWG Tinned Cu Drain |
| 4 | Sunlight & Oil Resistant Black PVC Jacket | UL 1277 TC-ER & UL 1424 NPLF Outer Sheath (6.91 mm OD) |
7×26 AWG Bare Cu + PVC/Nylon + 100% Foil · Outer diameter 6.91 mm.
7×24 AWG Bare Cu + PVC/Nylon + 100% Foil · Outer diameter 7.62 mm.
7×26 AWG Bare Cu + PVC/Nylon + 100% Foil · Outer diameter 13.4 mm.
Technical data
Sizes
Representative configurations from the series specification; select a row to prefill the quotation tool.
| Configuration | Conductor & shield | Insulation / wall | Outer sheath | Outer diameter mm | Min. bend radius mm | Max. conductor resistance @ 20 °C Ω/km | Copper weight kg/km | Cable weight kg/km | Key electrical / optical rating | Part designation | Enquiry |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1121A 600V TC-ER / 150V NPLF | |||||||||||
| 1 × 3 × 18 AWG (0.82 mm²) | 7×26 AWG Bare Cu + PVC/Nylon + 100% Foil | Black, Red, Blue Numbered 600 V PVC/Nylon | Industrial PVC | 6.9 | 55 | 21.00 | 28.5 | 61 | 600 V TC-ER / 150 V NPLF (RTD / 4–20 mA) | 1121A 1 Triad × 18 AWG (7×26) TC-ER | |
| 1 × 3 × 16 AWG (1.31 mm²) | 7×24 AWG Bare Cu + PVC/Nylon + 100% Foil | Black, Red, Blue Numbered 600 V PVC/Nylon | Industrial PVC | 7.6 | 61 | 13.20 | 45.4 | 79 | 600 V TC-ER / 150 V NPLF (RTD / 4–20 mA) | 1122A 1 Triad × 16 AWG (7×24) TC-ER | |
| 4 × 3 × 18 AWG (0.82 mm²) | 7×26 AWG Bare Cu + PVC/Nylon + 100% Foil | Black, Red, Blue Numbered 600 V PVC/Nylon | Industrial PVC | 13.4 | 107 | 21.00 | 106.0 | 210 | 600 V TC-ER / 150 V NPLF (RTD / 4–20 mA) | 1124A 4 Triads × 18 AWG (7×26) TC-ER | |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & continuity | Within maximum Ω/km limit at 20 °C | Every manufactured drum length |
| Dielectric withstand / spark test | No breakdown across insulation or shield | Every manufactured drum length |
| Sample tests | ||
| Vertical flame propagation & jacket qualification | Self-extinguishing within standard char limit | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.