Contact

37-102 CIRVA2 2 kV TC-ER-HL Hazardous VFD Cable2000 V crush- & impact-resistant UL 2225 TC-ER-HL VFD cable

37-102 CIRVA2 2 kV TC-ER-HL delivers flexible tinned copper conductors, 2000 V thermoset XLPE/EPR insulation, copper tape + metallic armor protection, and UL 2225 Class I Div 1 hazardous-location compliance.

Low-EMC design
EMC screen
Flame-retardant
Outdoor & humid
Order designation
37-102 CIRVA2 2kV TC-ER-HL 3×2 AWG + 3×10 AWG
Outer Ø
37.0 mm
Max. R20
0.561 Ω/km
Weight
2,680 kg/km
Min. bend R
444 mm
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
2000 V
AC test voltage 6 kV AC
EMC screening
100% Cu tape
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -25 °C to +90 °C
Min. bend radius
12 × OD
Fixed routing in trays & ducts
Conductor
Tinned Cu · Cl.K
ASTM B172 / B8 copper
Size range
14 AWG–500 kcmil
12 standard configurations

Typical values for this cable type, based on UL 2225 Type TC-ER-HL · UL 1277 Type TC-ER · CSA C22.2 No. 230 — confirmed in the datasheet and quotation for your order.

Application fit

Is 37-102 CIRVA2 2kV TC-ER-HL right for your machine?

37-102 CIRVA2 2 kV TC-ER-HL delivers flexible tinned copper conductors, 2000 V thermoset XLPE/EPR insulation, copper tape + metallic armor protection, and UL 2225 Class I Div 1 hazardous-location compliance.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 2000 V XLPE/CPE construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 2000 V XLPE/CPE geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Offshore process module & hazardous zone

Suitable

Chemical- and mud-resistant 2000 V XLPE/CPE build suits offshore topside process modules, hazardous decks, and utility skids.

Direct-burial & wet conduit run

Suitable

Moisture-resistant 2000 V XLPE/CPE protection allows direct-burial trenching, underground sand beds, and damp concrete ducts.

Energy chain / drag chain

Not suitable

2000 V XLPE/CPE construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

2000 V XLPE/CPE build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesOil & Gas CableVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of 37-102 CIRVA2 2kV TC-ER-HL: tinned copper conductors, 2000 V thermoset XLPE / RHW-2 dielectric, Helical copper tape shield + 3 symmetrical tinned grounds, and Black heavy-duty oil-, mud- & UV-resistant CPE jacket.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorASTM B172 Class K flexible tinned annealed copperASTM B172 Class K / UL 1277
2Core insulation2000 V thermoset XLPE / RHW-2 dielectricUL 2225 Type TC-ER-HL
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeUL 2225 Type TC-ER-HL
4EMC metallic screenHelical copper tape shield + 3 symmetrical tinned groundsEMC ≥ 85% / 100% foil
5Metallic armourCrush- & impact-resistant metallic armor barrier (TC-ER-HL)UL 2225 Type TC-ER-HL
6Outer sheathBlack heavy-duty oil-, mud- & UV-resistant CPE jacketIEEE 1202 / FT4 Flame

37-102 CIRVA2 2kV TC-ER-HL 3C + 3G Symmetrical

Three numbered black XLPE phase conductors with three symmetrically laid interstitial grounds under EMC shield.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 2225 Type TC-ER-HL · UL 1277 Type TC-ER · CSA C22.2 No. 230. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
2000 V
AC test voltage
6 kV AC / 5 min
Conductor class
ASTM B172 Class K tinned Cu
EMC screen
Helical copper tape shield + 3
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-25 °C to +90 °C
Short-circuit temp.
+250 °C (5 s)
Min. bending radius
12 × OD (fixed)

Resistance

Flame retardance
IEEE 1202 / FT4 Flame
Oil & chemical perf.
UL Oil Res I/II
Environmental / EMC
Class I Div 1 & 2 Crush/Impact
Outer sheath
Black heavy-duty oil-, mud- &

Sizes

3C + 3G Symmetrical (AWG/kcmil)
Cores ×
AWG/kcmil
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
12×D mm
3×14 AWG + 3×18 AWG21.39.070148575256
3×12 AWG + 3×16 AWG22.45.710198680269
3×10 AWG + 3×14 AWG23.83.590278837286
3×8 AWG + 3×14 AWG26.62.2603721,078319
3×6 AWG + 3×12 AWG28.81.4205481,406346
3×4 AWG + 3×12 AWG32.50.8927771,892390
3×2 AWG + 3×10 AWG37.00.5611,1852,680444
3×1/0 AWG + 3×6 AWG41.40.3531,9663,973497
3×2/0 AWG + 3×6 AWG44.00.2802,3564,661528
3×4/0 AWG + 3×4 AWG50.90.1763,6876,922611
3×350 kcmil + 3×2 AWG61.00.1075,98410,822732
3×500 kcmil + 3×2 AWG68.50.0758,09714,353822
  • Max. conductor DC resistance R20 at 20 °C per ASTM B172 / B8 (tinned copper).
  • Minimum bending radius calculated at 12 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test6 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer ASTM B172 / B8 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation check100% Cu tape continuity & wall thicknessPer production lot
Flame & environmental qualificationIEEE 1202 / FT4 Flame · UL Oil Res I/IIType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 2225 Type TC-ER-HLUL 1277 Type TC-ERCSA C22.2 No. 230EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

37-102 CIRVA2 2kV TC-ER-HL 2000 V TEBAOFLEX.COM [UL 2225 Type TC-ER-HL] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export reels
Standard drum lengths
305 m (1,000 ft) · 500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes 37-102 CIRVA2 2kV TC-ER-HL suitable for 2000 V industrial installations?
37-102 CIRVA2 2kV TC-ER-HL combines tinned copper conductors, 2000 V thermoset XLPE / RHW-2 dielectric, and Helical copper tape shield + 3 symmetrical tinned grounds inside a Black heavy-duty oil-, mud- & UV-resistant CPE jacket. 2 kV TC-ER-HL rating withstands refinery, petrochemical, and offshore hazardous-area mechanical abuse.
Can 37-102 CIRVA2 2kV TC-ER-HL operate inside continuous drag chains or moving axes?
No. 37-102 CIRVA2 2kV TC-ER-HL is engineered for stationary tray, conduit, or machine-frame routing at 12 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of 37-102 CIRVA2 2kV TC-ER-HL be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany 37-102 CIRVA2 2kV TC-ER-HL?
37-102 CIRVA2 2kV TC-ER-HL conforms to UL 2225 Type TC-ER-HL, UL 1277 Type TC-ER, CSA C22.2 No. 230 (IEEE 1202 / FT4 Flame) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 37-102 CIRVA2 2kV TC-ER-HL

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

37-102 CIRVA2 2 kV TC-ER-HL Hazardous VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote