Contact
Screened power & VFD / motor supply cablesDIN VDE 0250 · EN 55011U0/U 0.6/1 kV · 90 °C XLPE3+3 Symmetrical · Foil + TCWB

3-PLUS-2XSLCYK-J 0.6/1 kV XLPE VFD Cable90 °C XLPE 3+3 symmetrical EMC drive cable with UV/oil PVC

High-ampacity 0.6/1 kV symmetrical 3+3 VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, 90 °C XLPE insulation (2X), Al/PET foil plus ≥ 85% tinned copper braid, and oil- and UV-resistant black PVC sheath.

Low-EMC design
EMC screen
Oil-resistant
Flame-retardant
Order designation
3-PLUS-2XSLCYK-J 3×50 + 3G10
Outer Ø
30.4 mm
Max. R20
0.386 Ω/km
Weight
2,777 kg/km
Min. bend R
304 mm
All sizes (14)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
Max. 0.7/1.2 kV AC · 4 kV test
EMC screening
Al/PET + TCWB
100% foil + ≥ 85% tinned Cu braid
Conductor temp.
+90 °C max.
+250 °C short-circuit (5 s)
Ambient temp.
−40…+80 °C
fixed (−5…+80 °C occasional flex)
Min. bend radius
10 × OD
fixed (15 × OD occasional flexing)
Size range
2.5–240 mm²
3+3 symmetrical · 90 °C XLPE (2X)

Typical values for this cable type, based on DIN VDE 0250 · DIN VDE 0276-603 · IEC 60228 Cl.5 · EN 55011 — confirmed in the datasheet and quotation for your order.

Application fit

Is 3-PLUS-2XSLCYK-J 0.6/1 kV right for your machine?

High-ampacity 0.6/1 kV symmetrical 3+3 VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, 90 °C XLPE insulation (2X), Al/PET foil plus ≥ 85% tinned copper braid, and oil- and UV-resistant black PVC sheath.

VFD inverter to AC motor screened feeder

Suitable

90 °C XLPE (2X) raises current rating up to 20% over 70 °C PE while retaining dual Al/PET + TCWB shielding.

Motor stator, traction & converter leads

Suitable

3+3 symmetrical split earths and +250 °C short-circuit rating protect high-ampacity AC motor drives.

Outdoor UV-exposed cable rack

Suitable

Oil- and UV-resistant RAL 9005 special PVC sheath endures exposed outdoor plant racks and oily trays.

Fixed installation

Suitable

Compact 10 × OD fixed bend radius simplifies routing across industrial trays, racks, and ducts.

Energy chain / drag chain

Not suitable

Designed for stationary and occasional-flex feeders, not continuous drag-chain bending.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not rated for motorised cable reels; select a rubber reeling cable for drum-wound equipment.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableHigh-ampacity industrial VFD drivesProcess plants, pumps & fansOutdoor crane & port facilitiesAutomotive & heavy manufacturingRenewable power converters

Construction

Layer by layer

Shown: 3-PLUS-2XSLCYK-J 0.6/1 kV 3×50 + 3G10 mm² — three Class 5 bare copper 90 °C XLPE phases and three green/yellow split earths under Al/PET foil, tinned Cu braid, and oil/UV-resistant black PVC.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 5 fine-wire bare annealed copperDIN VDE 0295 / IEC 60228 Class 5
2Phase & earth insulation90 °C cross-linked polyethylene (2X / XLPE), HD 308 S2Brown, black, grey + 3 × green/yellow split earths
3Separator tapeNon-woven polyester separator tape over 3+3 coreSmooth circular assembly
4Foil screenPlastic-coated aluminium laminate foil (100% coverage)High-frequency EMI containment
5Braid screenTinned copper wire braid (≥ 85% coverage)EN 55011 low transfer impedance
6Outer sheathBlack oil- & UV-resistant special PVC (RAL 9005)Outdoor UV & industrial oil resistance

3-PLUS-2XSLCYK-J (3+3 XLPE)

Three 90 °C XLPE phase cores (brown, black, grey) plus three symmetrical green/yellow split earths (2.5–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0250 · DIN VDE 0276-603 · IEC 60228 Cl.5 · EN 55011. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV (max. 0.7/1.2 kV AC)
AC test voltage
4 kV (core/core & core/screen)
Conductor class
IEC 60228 / VDE 0295 Class 5
Dual EMC screen
100% Al/PET foil + ≥ 85% TCWB
Transfer impedance
≤ 250 mΩ/m at 30 MHz

Thermal

Max. conductor temp.
+90 °C continuous (XLPE 2X)
Short-circuit temp.
+250 °C (max. 5 s)
Ambient temp. (fixed)
−40 °C to +80 °C
Ambient temp. (flexed)
−5 °C to +80 °C
Min. bending radius
10 × OD fixed / 15 × OD flexed

Resistance

Flame retardance
IEC 60332-1-2 / VDE 0482-332-1-2
Oil & UV resistance
Oil- & UV-resistant RAL 9005 PVC
EMC compliance
EN 55011 / EN 61800-3

Sizes

3+3 Symmetrical (90 °C XLPE)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
3×2.5 + 3G0.513.07.980118256130
3×4 + 3G0.7514.14.950169340141
3×6 + 3G115.43.300234447154
3×10 + 3G1.517.41.910362651174
3×16 + 3G2.519.81.210560960198
3×25 + 3G424.10.7808581,458241
3×35 + 3G626.70.5541,1931,969267
3×50 + 3G1030.40.3861,7222,777304
3×70 + 3G1635.50.2722,4463,912355
3×95 + 3G1639.40.2063,1394,980394
3×120 + 3G2543.20.1614,0786,377432
3×150 + 3G2549.00.1294,9137,777490
3×185 + 3G3553.70.1066,1549,665537
3×240 + 3G5059.40.0808,08112,531594
  • Conductor max. DC resistance R20 follows DIN VDE 0295 / IEC 60228 Class 5 bare annealed copper at 20 °C.
  • Cross-linked polyethylene (2X) raises continuous conductor rating to +90 °C and short-circuit rating to +250 °C (5 s).

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC (core/core & core/screen)Every manufactured drum
Conductor DC resistance testPer IEC 60228 / VDE 0295 Class 5 at 20 °CEvery drum length
Sample tests
XLPE hot-set & dual-screen checkIEC 60811-507 hot-set & ≥ 85% TCWBPer production lot
Flame propagation testSelf-extinguishing per IEC 60332-1-2Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0250 / 0276-603 XLPE Symmetrical VFDEN 55011 / EN 61800-3 EMC ComplianceIEC 60332-1-2 Flame Retardant · Oil & UV Resistant

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

3-PLUS-2XSLCYK-J 0.6/1 kV TEBAOFLEX.COM [Cores×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

Why choose 3-PLUS-2XSLCYK-J (XLPE) over 2YSL(St)CYK-J (PE)?
3-PLUS-2XSLCYK-J replaces +70 °C thermoplastic PE with +90 °C thermoset XLPE (2X), delivering higher current-carrying capacity, stronger thermal overload resistance, and +250 °C short-circuit durability in the same compact diameter.
How does 3-PLUS-2XSLCYK-J handle industrial oils and outdoor UV?
Its black RAL 9005 special PVC outer sheath is formulated for both UV stability and industrial oil resistance, permitting exposed outdoor racks as well as oily plant trays.
Is 3-PLUS-2XSLCYK-J compliant with European EMC directives?
Yes. The 3+3 symmetrical earth arrangement combined with 100% Al/PET foil and ≥ 85% tinned copper wire braid keeps transfer impedance ≤ 250 mΩ/m at 30 MHz to meet EN 55011 / EN 61800-3.
How should the EMC shield and symmetrical grounds of 3-PLUS-2XSLCYK-J 0.6/1 kV be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 3-PLUS-2XSLCYK-J 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

3-PLUS-2XSLCYK-J 0.6/1 kV XLPE VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote