VFD inverter to AC motor screened feeder
90 °C XLPE (2X) raises current rating up to 20% over 70 °C PE while retaining dual Al/PET + TCWB shielding.
Product
High-ampacity 0.6/1 kV symmetrical 3+3 VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, 90 °C XLPE insulation (2X), Al/PET foil plus ≥ 85% tinned copper braid, and oil- and UV-resistant black PVC sheath.
Typical values for this cable type, based on DIN VDE 0250 · DIN VDE 0276-603 · IEC 60228 Cl.5 · EN 55011 — confirmed in the datasheet and quotation for your order.
Application fit
High-ampacity 0.6/1 kV symmetrical 3+3 VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, 90 °C XLPE insulation (2X), Al/PET foil plus ≥ 85% tinned copper braid, and oil- and UV-resistant black PVC sheath.
90 °C XLPE (2X) raises current rating up to 20% over 70 °C PE while retaining dual Al/PET + TCWB shielding.
3+3 symmetrical split earths and +250 °C short-circuit rating protect high-ampacity AC motor drives.
Oil- and UV-resistant RAL 9005 special PVC sheath endures exposed outdoor plant racks and oily trays.
Compact 10 × OD fixed bend radius simplifies routing across industrial trays, racks, and ducts.
Designed for stationary and occasional-flex feeders, not continuous drag-chain bending.
Use (N)12YRDC11Y-J/O PURNot rated for motorised cable reels; select a rubber reeling cable for drum-wound equipment.
Use RG / RG-D (N)SHTOEU-JConstruction
Shown: 3-PLUS-2XSLCYK-J 0.6/1 kV 3×50 + 3G10 mm² — three Class 5 bare copper 90 °C XLPE phases and three green/yellow split earths under Al/PET foil, tinned Cu braid, and oil/UV-resistant black PVC.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | Class 5 fine-wire bare annealed copperDIN VDE 0295 / IEC 60228 Class 5 |
| 2 | Phase & earth insulation | 90 °C cross-linked polyethylene (2X / XLPE), HD 308 S2Brown, black, grey + 3 × green/yellow split earths |
| 3 | Separator tape | Non-woven polyester separator tape over 3+3 coreSmooth circular assembly |
| 4 | Foil screen | Plastic-coated aluminium laminate foil (100% coverage)High-frequency EMI containment |
| 5 | Braid screen | Tinned copper wire braid (≥ 85% coverage)EN 55011 low transfer impedance |
| 6 | Outer sheath | Black oil- & UV-resistant special PVC (RAL 9005)Outdoor UV & industrial oil resistance |
Three 90 °C XLPE phase cores (brown, black, grey) plus three symmetrical green/yellow split earths (2.5–240 mm²).
Technical data
Sizes
| Cores × mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 10×D mm |
|---|---|---|---|---|---|
| 3×2.5 + 3G0.5 | 13.0 | 7.980 | 118 | 256 | 130 |
| 3×4 + 3G0.75 | 14.1 | 4.950 | 169 | 340 | 141 |
| 3×6 + 3G1 | 15.4 | 3.300 | 234 | 447 | 154 |
| 3×10 + 3G1.5 | 17.4 | 1.910 | 362 | 651 | 174 |
| 3×16 + 3G2.5 | 19.8 | 1.210 | 560 | 960 | 198 |
| 3×25 + 3G4 | 24.1 | 0.780 | 858 | 1,458 | 241 |
| 3×35 + 3G6 | 26.7 | 0.554 | 1,193 | 1,969 | 267 |
| 3×50 + 3G10 | 30.4 | 0.386 | 1,722 | 2,777 | 304 |
| 3×70 + 3G16 | 35.5 | 0.272 | 2,446 | 3,912 | 355 |
| 3×95 + 3G16 | 39.4 | 0.206 | 3,139 | 4,980 | 394 |
| 3×120 + 3G25 | 43.2 | 0.161 | 4,078 | 6,377 | 432 |
| 3×150 + 3G25 | 49.0 | 0.129 | 4,913 | 7,777 | 490 |
| 3×185 + 3G35 | 53.7 | 0.106 | 6,154 | 9,665 | 537 |
| 3×240 + 3G50 | 59.4 | 0.080 | 8,081 | 12,531 | 594 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC high-voltage dielectric test | 4 kV AC (core/core & core/screen) | Every manufactured drum |
| Conductor DC resistance test | Per IEC 60228 / VDE 0295 Class 5 at 20 °C | Every drum length |
| Sample tests | ||
| XLPE hot-set & dual-screen check | IEC 60811-507 hot-set & ≥ 85% TCWB | Per production lot |
| Flame propagation test | Self-extinguishing per IEC 60332-1-2 | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.