Screened power & VFD / motor supply cablesDIN VDE 0250 · EN 55011U0/U 0.6/1 kV · 4 kV Test3+3 Symmetrical · UV Black PVC

2YSL(St)CYK-J 3PLUS 0.6/1 kV Symmetrical VFD CableSymmetrical 3+3 low-capacitance PE VFD cable with UV PVC sheath

Symmetrical 3+3 EMC motor supply cable built to DIN VDE 0250 with Class 5 bare copper, low-capacitance PE insulation (2Y), Al/PET foil (St) plus ≥ 85% tinned copper braid (C), and black UV-resistant RAL 9005 FR-PVC sheath.

Low-EMC design
EMC screen
Outdoor & humid
Flame-retardant
Order designation
2YSL(St)CYK-J 3PLUS 3×35 + 3G6
Outer Ø
26.4 mm
Max. R20
0.554 Ω/km
Weight
1,938 kg/km
Min. bend R
264 mm
All sizes (14)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 4 kV (0.7/1.2 kV max.)
EMC screening
Al/PET + TCWB
100% St foil + ≥ 85% tinned Cu braid
Conductor temp.
+70 °C max.
Low-capacitance PE (2Y) dielectric
Ambient temp.
−40…+70 °C
fixed (−5…+70 °C occasional flex)
Min. bend radius
10 × OD
fixed (15 × OD occasional flexing)
Size range
2.5–240 mm²
3+3 symmetrical · UV RAL 9005 PVC

Typical values for this cable type, based on DIN VDE 0250 · EN 55011 · IEC 60228 Cl.5 · HD 308 S2 — confirmed in the datasheet and quotation for your order.

Application fit

Is 2YSL(St)CYK-J 3PLUS 0.6/1 kV right for your machine?

Symmetrical 3+3 EMC motor supply cable built to DIN VDE 0250 with Class 5 bare copper, low-capacitance PE insulation (2Y), Al/PET foil (St) plus ≥ 85% tinned copper braid (C), and black UV-resistant RAL 9005 FR-PVC sheath.

VFD inverter to AC motor screened feeder

Suitable

3+3 symmetrical split earths and low-capacitance PE suppress zero-sequence currents on long inverter runs.

Motor stator, traction & converter leads

Suitable

Dual 100% Al/PET static foil plus ≥ 85% tinned copper braid delivers EN 55011 EMC shielding.

Outdoor UV-exposed cable rack

Suitable

Black RAL 9005 UV-stabilised PVC sheath (YK) withstands direct sunlight on outdoor pipe bridges and racks.

Fixed installation

Suitable

Installs reliably on indoor or outdoor cable trays, ladders, and plant bridges from −40 to +70 °C.

Energy chain / drag chain

Not suitable

Engineered for fixed and occasional-flex routing rather than continuous energy-chain travel.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

Not designed for motorised cable drums; specify a rubber reeling cable for mobile spooling.

Use RG / RG-D (N)SHTOEU-J
Typical machinesIndustrial Automation CableOutdoor & indoor VFD pump stationsHVAC, fans & cooling towersMaterial handling & crane bridgesProcess & water treatment plantsAutomated industrial drives

Construction

Layer by layer

Shown: 2YSL(St)CYK-J 3PLUS 0.6/1 kV 3×35 + 3G6 mm² — three Class 5 bare copper PE phase cores and three symmetrical green/yellow split earths inside Al/PET foil, tinned Cu braid, and UV-resistant black PVC.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 5 fine-wire bare annealed copperDIN VDE 0295 / IEC 60228 Class 5
2Phase & earth insulationLow-capacitance PE (2Y), HD 308 S2 colour codeBrown, black, grey + 3 × green/yellow split earths
3Core wrapPolyester wrapping tape over symmetrical 3+3 assemblyCompact circular profile
4Static foil screen (St)Aluminium/polyester laminate foil (100% coverage)High-frequency electrostatic containment
5Braid screen (C)Tinned copper wire braid (≥ 85% coverage)EN 55011 low transfer impedance
6Outer sheath (YK)Black UV-resistant flame-retardant PVC (RAL 9005)Outdoor UV & weather-stabilised PVC

2YSL(St)CYK-J 3PLUS (3+3)

Three low-capacitance PE phases (brown, black, grey) plus three symmetrically arranged green/yellow PE conductors (2.5–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0250 · EN 55011 · IEC 60228 Cl.5 · HD 308 S2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV (max. 0.7/1.2 kV AC)
AC test voltage
4 kV (core/core & core/screen)
Conductor class
IEC 60228 / VDE 0295 Class 5
Dual EMC screen
100% Al/PET (St) + ≥ 85% TCWB (C)
Transfer impedance
≤ 250 mΩ/m at 30 MHz

Thermal

Max. conductor temp.
+70 °C continuous (PE 2Y)
Ambient temp. (fixed)
−40 °C to +70 °C
Ambient temp. (flexed)
−5 °C to +70 °C
Min. bending radius
10 × OD fixed / 15 × OD flexed

Resistance

Flame retardance
IEC 60332-1-2 / VDE 0482-332-1-2
UV & outdoor rating
UV-resistant black PVC (RAL 9005)
EMC compliance
EN 55011 / EN 61800-3

Sizes

3+3 Symmetrical (3PLUS)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
3×2.5 + 3G0.512.87.980117249128
3×4 + 3G0.7514.04.950168333140
3×6 + 3G115.33.300233439153
3×10 + 3G1.517.31.910362642173
3×16 + 3G2.519.61.210559944196
3×25 + 3G423.90.7808581,438239
3×35 + 3G626.40.5541,1921,938264
3×50 + 3G1030.10.3861,7212,737301
3×70 + 3G1635.10.2722,4453,855351
3×95 + 3G1639.00.2063,1384,910390
3×120 + 3G2542.80.1614,0776,291428
3×150 + 3G2548.50.1294,9117,667485
3×185 + 3G3553.10.1066,1539,528531
3×240 + 3G5058.80.0808,07912,360588
  • Conductor max. DC resistance R20 follows DIN VDE 0295 / IEC 60228 Class 5 bare annealed copper at 20 °C.
  • For higher +90 °C continuous conductor temperature and higher ampacity, specify XLPE-insulated 3-PLUS-2XSLCYK-J 0.6/1 kV.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC (core/core & core/screen)Every manufactured drum
Conductor DC resistance testPer IEC 60228 / VDE 0295 Class 5 at 20 °CEvery drum length
Sample tests
Dual-screen & capacitance check100% Al/PET foil + ≥ 85% TCWB coveragePer production lot
Vertical flame propagationSelf-extinguishing per IEC 60332-1-2Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0250 Symmetrical 3+3 VFD CableEN 55011 / EN 61800-3 EMC ComplianceIEC 60332-1-2 Flame Retardant · UV Resistant

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

2YSL(ST)CYK-J 3PLUS 0.6/1 kV TEBAOFLEX.COM [Cores×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What is the benefit of the 3PLUS symmetrical earth layout in 2YSL(St)CYK-J?
Splitting the protective earth into three smaller conductors laid symmetrically in the outer interstices cancels magnetic flux asymmetry, lowering induced shaft currents and reducing overall cable OD compared with 4-core layouts.
Can 2YSL(St)CYK-J 3PLUS be routed outdoors?
Yes. The K-suffix black RAL 9005 PVC outer sheath is UV- and weather-stabilised for outdoor cable trays, rooftops, and exposed plant bridges within −40…+70 °C fixed service.
Should I choose 2YSL(St)CYK-J 3PLUS (PE) or 3-PLUS-2XSLCYK-J (XLPE)?
Choose 2YSL(St)CYK-J 3PLUS (PE, +70 °C) for the lowest dielectric capacitance on long cable runs, or upgrade to 3-PLUS-2XSLCYK-J (XLPE, +90 °C) when higher current-carrying capacity and +250 °C short-circuit margin are needed.
How should the EMC shield and symmetrical grounds of 2YSL(St)CYK-J 3PLUS 0.6/1 kV be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 2YSL(St)CYK-J 3PLUS 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

2YSL(St)CYK-J 3PLUS 0.6/1 kV Symmetrical VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 