Contact
Screened power & VFD / motor supply cablesDIN VDE 0250 · EN 55011U0/U 0.6/1 kV · 4 kV TestLow-Cap PE · Transparent PVC

2YSL(St)CY-J 0.6/1 kV Double-Screened VFD CableLow-capacitance PE 4-core EMC motor cable with transparent PVC

European EMC-optimised 0.6/1 kV 4-core VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, low-capacitance PE insulation (2Y), Al/PET static foil (St) plus tinned copper braid (C), and transparent FR-PVC sheath.

Low-EMC design
EMC screen
Flame-retardant
Oil-resistant
Order designation
2YSL(St)CY-J 4G16
Outer Ø
22.4 mm
Max. R20
1.210 Ω/km
Weight
1,090 kg/km
Min. bend R
224 mm
All sizes (15)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 4 kV (max. 0.7/1.2 kV)
EMC screening
Al/PET + TCWB
100% St foil + ≥ 85% tinned Cu braid
Conductor temp.
+70 °C max.
Low-capacitance PE (2Y) dielectric
Ambient temp.
−40…+70 °C
fixed (−5…+70 °C occasional flex)
Min. bend radius
10 × OD
fixed (15 × OD occasional flexing)
Size range
4G1.5–240 mm²
HD 308 S2 4-core · Class 5 Cu

Typical values for this cable type, based on DIN VDE 0250 · EN 55011 · IEC 60228 Cl.5 · HD 308 S2 — confirmed in the datasheet and quotation for your order.

Application fit

Is 2YSL(St)CY-J 0.6/1 kV right for your machine?

European EMC-optimised 0.6/1 kV 4-core VFD motor supply cable built to DIN VDE 0250 with Class 5 bare copper, low-capacitance PE insulation (2Y), Al/PET static foil (St) plus tinned copper braid (C), and transparent FR-PVC sheath.

VFD inverter to AC motor screened feeder

Suitable

Low-permittivity PE (2Y) lowers capacitive charging currents while Al/PET + TCWB meets EN 55011 EMC.

Motor stator, traction & converter leads

Suitable

Class 5 bare copper and compact 4G HD 308 S2 profile wire cleanly into IEC industrial motor boxes.

Switchgear & control cabinet wiring

Suitable

Transparent FR-PVC outer sheath enables fast visual inspection of tinned copper braid continuity in OEM panels.

Fixed installation

Suitable

Suitable for indoor dry, damp, and wet factory trays and conduits within −40…+70 °C fixed service.

Outdoor UV-exposed cable rack

Not suitable

Transparent PVC sheath is not UV-stabilised for direct outdoor sunlight; choose black UV-rated 2YSL(St)CYK-J 3PLUS.

Use 2YSL(St)CYK-J 3PLUS

Energy chain / drag chain

Not suitable

PVC jacket is rated for fixed and occasional flexing only, not continuous drag-chain travel.

Use (N)12YRDC11Y-J/O PUR
Typical machinesIndustrial Automation CableIndustrial automation & OEM panelsMachine tools & conveyor drivesPackaging & textile linesIndoor plant HVAC & pump drivesEN 55011 EMC-sensitive factories

Construction

Layer by layer

Shown: 2YSL(St)CY-J 0.6/1 kV 4G16 mm² — four Class 5 bare copper PE cores (HD 308 S2) shielded by plastic-coated aluminium static foil and tinned copper braid inside a transparent FR-PVC sheath.

123456
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorClass 5 fine-wire bare annealed copperDIN VDE 0295 / IEC 60228 Class 5
2Core insulationLow-capacitance polyethylene (2Y / PE), HD 308 S2 coloursBrown, black, grey + green/yellow earth
3Core wrapPolyester separator foil over cabled 4-core bundleClean strip & thermal barrier
4Static foil screen (St)Plastic-coated aluminium laminate static screen (100%)DIN VDE 0250 high-frequency EMI shield
5Braid screen (C)Tinned copper wire braid (≥ 85% optical coverage)EN 55011 low transfer impedance ≤ 250 mΩ/m
6Outer sheathTransparent flame-retardant special PVCDIN VDE 0250 / IEC 60332-1-2

2YSL(St)CY-J 4G (HD 308 S2)

Four low-capacitance PE cores (brown, black, grey, green/yellow) under Al/PET static foil + tinned copper braid (1.5–240 mm²).

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0250 · EN 55011 · IEC 60228 Cl.5 · HD 308 S2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV (max. 0.7/1.2 kV AC)
AC test voltage
4 kV (core/core & core/screen)
Conductor class
IEC 60228 / VDE 0295 Class 5
Dual EMC screen
100% Al/PET (St) + ≥ 85% TCWB (C)
Transfer impedance
≤ 250 mΩ/m at 30 MHz

Thermal

Max. conductor temp.
+70 °C continuous (PE 2Y)
Ambient temp. (fixed)
−40 °C to +70 °C
Ambient temp. (flexed)
−5 °C to +70 °C
Min. bending radius
10 × OD fixed / 15 × OD flexed

Resistance

Flame retardance
IEC 60332-1-2 / VDE 0482-332-1-2
Sheath compound
Transparent FR special PVC
EMC compliance
EN 55011 / EN 61800-3

Sizes

4G (3 Phases + PE)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
4G1.511.813.30087190118
4G2.513.07.980127257130
4G414.34.950185349143
4G615.73.300262469157
4G1018.91.910416724189
4G1622.41.2106441,090224
4G2525.50.7809801,591255
4G3529.40.5541,3552,179294
4G5033.10.3861,9113,000331
4G7038.10.2722,6534,124381
4G9543.50.2063,5785,523435
4G12047.30.1614,4996,860473
4G15052.40.1295,6058,522524
4G18558.10.1066,89410,481581
4G24064.10.0808,91313,398641
  • Conductor max. DC resistance R20 follows DIN VDE 0295 / IEC 60228 Class 5 bare annealed copper at 20 °C.
  • Transparent outer sheath is recommended for indoor routing; for outdoor UV exposure select black 2YSL(St)CYK-J 3PLUS.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC (core/core & core/screen)Every manufactured drum
Conductor DC resistance checkPer IEC 60228 / VDE 0295 Class 5 at 20 °CEvery drum length
Sample tests
Capacitance & braid coverageLow-cap PE check & ≥ 85% TCWB coveragePer production lot
Flame retardance testSelf-extinguishing per IEC 60332-1-2Type approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0250 Low-Capacitance EMC Motor CableEN 55011 / EN 61800-3 EMC CompatibilityIEC 60332-1-2 Flame Retardant · RoHS / CE

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

2YSL(ST)CY-J 0.6/1 kV TEBAOFLEX.COM [4G×mm²] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-20
Updated
2026-11-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What does the (St) designation mean in 2YSL(St)CY-J?
The (St) denotes a plastic-coated aluminium laminate static screen foil (100% coverage) layered directly beneath the ≥ 85% tinned copper wire braid (C), delivering broad-spectrum EMC attenuation from low harmonics into the MHz range.
Why does 2YSL(St)CY-J use a transparent PVC outer sheath?
The transparent flame-retardant PVC jacket enables immediate visual verification of screen integrity and continuity during cabinet inspection, commissioning, and plant audits.
When should I upgrade from 4G 2YSL(St)CY-J to a 3+3 symmetrical cable?
For large motor feeders above 16–25 mm² or long VFD runs where common-mode shaft currents are critical, choose symmetrical 3+3 2YSL(St)CYK-J 3PLUS or 90 °C XLPE 3-PLUS-2XSLCYK-J.
How should the EMC shield and symmetrical grounds of 2YSL(St)CY-J 0.6/1 kV be terminated?
Bond the metallic EMC shield circumferentially (360°) at both the inverter cabinet and motor terminal box using EMC cable glands or constant-force springs, and connect all protective ground conductors cleanly to the earth busbar.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 2YSL(St)CY-J 0.6/1 kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

2YSL(St)CY-J 0.6/1 kV Double-Screened VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote