2XSLCHK-JB 0.6/1 kV LSZH Halogen-Free VFD CableZero-halogen low-smoke XLPE symmetrical 3+3 EMC VFD motor cable

2XSLCHK-JB 0.6/1 kV LSZH delivers symmetrical 3+3 bare copper geometry, 90 °C XLPE insulation, dual foil/braid EMC screening, and a flame-retardant halogen-free LSZH outer sheath for public buildings and tunnels.

Low-EMC design
EMC screen
Flame-retardant
Outdoor & humid
Order designation
2XSLCHK-JB 0.6/1 kV LSZH 3×35 + 3G6
Outer Ø
26.6 mm
Max. R20
0.554 Ω/km
Weight
1,963 kg/km
Min. bend R
266 mm
All sizes (14)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
AC test voltage 4 kV AC
EMC screening
Foil + TCWB
Low transfer impedance EMC shield
Temp. (fixed)
-40°C…+90°C
Flexing: -5 °C to +90 °C
Min. bend radius
10 × OD
Fixed routing in trays & ducts
Conductor
Bare Cu · Cl.5
IEC 60228 stranded copper
Size range
3×2.5–3×240
14 standard configurations

Typical values for this cable type, based on DIN VDE 0250 · IEC 60502-1 · IEC 60228 Class 5 — confirmed in the datasheet and quotation for your order.

Application fit

Is 2XSLCHK-JB 0.6/1 kV LSZH right for your machine?

2XSLCHK-JB 0.6/1 kV LSZH delivers symmetrical 3+3 bare copper geometry, 90 °C XLPE insulation, dual foil/braid EMC screening, and a flame-retardant halogen-free LSZH outer sheath for public buildings and tunnels.

VFD inverter to AC motor screened feeder

Suitable

Low-capacitance 0.6/1 kV XLPE/LSZH construction and EMC screen suppress PWM switching noise between inverter and AC motor.

Motor stator, traction & converter leads

Suitable

Balanced 0.6/1 kV XLPE/LSZH geometry cuts common-mode bearing currents and terminates cleanly inside motor junction boxes.

Emergency fire-survival riser circuit

Suitable

Circuit-integrity 0.6/1 kV XLPE/LSZH design sustains emergency alarms, smoke extraction, and evacuation lighting during fire exposure.

Dual-tier power & PLC tray

Suitable

Screened 0.6/1 kV XLPE/LSZH construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Energy chain / drag chain

Not suitable

0.6/1 kV XLPE/LSZH construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Motorised monospiral reel

Not suitable

0.6/1 kV XLPE/LSZH build lacks anti-torsion tensile reinforcement for motorised drum reeling; select a dedicated reeling cable.

Use RG / RG-D (N)SHTOEU-J
Typical machinesBuilding & Fire SafetyVariable frequency drive (VFD) motor baysIndustrial pumps, fans & compressor skidsProcess plants, oil & gas & HVAC systemsHeavy manufacturing & plant MCC feeders

Construction

Layer by layer

Representative construction of 2XSLCHK-JB 0.6/1 kV LSZH: bare copper conductors, 90 °C halogen-free XLPE (2X), Al-laminated foil + ≥ 85% tinned copper braid, and Black UV-stabilised halogen-free LSZH polyolefin sheath (HM4).

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorIEC 60228 Class 5 flexible bare annealed copperIEC 60228 Class 5
2Core insulation90 °C halogen-free XLPE (2X)DIN VDE 0250
3Core assembly & separatorConcentric cabled assembly with low-friction fleece or polyester binder tapeDIN VDE 0250
4EMC metallic screenAl-laminated foil + ≥ 85% tinned copper braidEMC ≥ 85% / 100% foil
5Outer sheathBlack UV-stabilised halogen-free LSZH polyolefin sheath (HM4)IEC 60332-3-24 Cat C

2XSLCHK-JB 0.6/1 kV LSZH Power & Ground

Colour-coded or numbered phase conductors with protective green/yellow earth under overall EMC screening.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0250 · IEC 60502-1 · IEC 60228 Class 5. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
0.6/1 kV
AC test voltage
4 kV AC / 5 min
Conductor class
IEC 60228 Class 5 bare Cu
EMC screen
Al-laminated foil + ≥ 85% tinned copper braid
Insulation resistance
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-40 °C to +90 °C
Temp. range (flexing)
-5 °C to +90 °C
Short-circuit temp.
+250 °C (5 s)
Min. bending radius
10 × OD (fixed)

Resistance

Flame retardance
IEC 60332-3-24 Cat C
Oil & chemical perf.
IEC 60754-1/2 Halogen-Free
Environmental / EMC
IEC 61034 Low Smoke
Outer sheath
Black UV-stabilised halogen-free LSZH

Sizes

3+3 Symmetrical (mm²)
Cores ×
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
10×D mm
3×2.5 + 3G0.512.77.980116248127
3×4 + 3G0.7513.94.950167334139
3×6 + 3G115.13.300232438151
3×10 + 3G1.517.11.910360642171
3×16 + 3G2.519.51.210558950195
3×25 + 3G424.00.7808561,453240
3×35 + 3G626.60.5541,1911,963266
3×50 + 3G1030.70.3861,7212,787307
3×70 + 3G1635.70.2722,4443,919357
3×95 + 3G1639.60.2063,1374,988396
3×120 + 3G2544.80.1614,0796,465448
3×150 + 3G2548.40.1294,9087,735484
3×185 + 3G3552.20.1066,1479,558522
3×240 + 3G5057.60.0808,07312,390576
  • Max. conductor DC resistance R20 at 20 °C per IEC 60228 (bare copper).
  • Minimum bending radius calculated at 10 × nominal outer diameter (OD). Custom core counts and lengths available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
AC high-voltage dielectric test4 kV AC for 5 min without breakdownEvery manufactured drum
Conductor DC resistance testPer IEC 60228 at 20 °CEvery drum length
Sample tests
EMC screen coverage & insulation checkFoil + TCWB continuity & wall thicknessPer production lot
Flame & environmental qualificationIEC 60332-3-24 Cat C · IEC 60754-1/2 Halogen-FreeType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0250IEC 60502-1IEC 60228 Class 5EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

2XSLCHK-JB 0.6/1 kV LSZH 0.6/1 kV TEBAOFLEX.COM [DIN VDE 0250] [Size] [Metre mark]
Delivery form
Cut-to-length or wooden export drums
Standard drum lengths
500 m · 1,000 m
MOQ
100 m (stock sizes) · 500 m (production)
Lead time
2–3 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-21
Updated
2026-11-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes 2XSLCHK-JB 0.6/1 kV LSZH suitable for 0.6/1 kV industrial installations?
2XSLCHK-JB 0.6/1 kV LSZH combines bare copper conductors, 90 °C halogen-free XLPE (2X), and Al-laminated foil + ≥ 85% tinned copper braid inside a Black UV-stabilised halogen-free LSZH polyolefin sheath (HM4). Halogen-free low-smoke sheath prevents corrosive acid gas emissions in airports, tunnels, and HVAC plants.
Can 2XSLCHK-JB 0.6/1 kV LSZH operate inside continuous drag chains or moving axes?
No. 2XSLCHK-JB 0.6/1 kV LSZH is engineered for stationary tray, conduit, or machine-frame routing at 10 × OD minimum bending radius; choose a PUR drag-chain cable for continuous flexing.
How should the EMC shield of 2XSLCHK-JB 0.6/1 kV LSZH be grounded at termination?
Bond the metallic screen circumferentially (360°) at both drive and motor ends using EMC cable glands or low-impedance shielding clamps to minimize high-frequency transfer impedance.
What standards, drum lengths, and test certificates accompany 2XSLCHK-JB 0.6/1 kV LSZH?
2XSLCHK-JB 0.6/1 kV LSZH conforms to DIN VDE 0250, IEC 60502-1, IEC 60228 Class 5 (IEC 60332-3-24 Cat C) and ships cut-to-length or on export drums with an EN 10204 3.1 routine test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for 2XSLCHK-JB 0.6/1 kV LSZH

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

2XSLCHK-JB 0.6/1 kV LSZH Halogen-Free VFD Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote