ANSI/NEMA WC 23058 (ICEA S-75-381-2025) Explained: Key Technical Revisions Replacing WC 58-2017 for Portable Mining and Feeder Cables

Engineering breakdown of ANSI/NEMA WC 23058 (ICEA S-75-381-2025) replacing WC 58-2017: 6 section scope, 90 °C EPR walls, Type SHD-GC, Type G-GC, Type MP-GC, and MSHA 30 CFR Part 7 flame tests.

TEBAOFLEX JyenOperations & Technical Engineer11 min read
Walking dragline operating on a surface mine bench powered by medium-voltage trailing cable under ANSI/NEMA WC 23058 duty
Updated
Reading time
11 min read
In this article22 sections
  1. 011. Architecture of ANSI/NEMA WC 23058 (ICEA S-75-381-2025): Six Sections and Two Supplements
  2. Structural Breakdown of the 125 Page Standard
  3. 022. Five Technical Revisions Engineers Must Update in 2026 Mine Cable Specifications
  4. 1. Consolidated 90 °C EPR Insulation Wall Tables (100% vs. 133% Levels)
  5. 2. Minimum Phase Conductor Sizes for 5 kV to 25 kV Shielded Cables
  6. 3. Rope-Lay Stranding (ASTM B172) vs. Concentric Feeder Stranding (ASTM B8)
  7. 4. Extra-Heavy-Duty Jacket Tear, Tensile, and Oil-Immersion Thresholds
  8. 5. Ground-Check (GC) Pilot Insulation and Interstitial Ground Sizing
  9. 033. Section 3 Portable Cables vs. Section 4 Mine Power Feeder Cables: Selecting Type G-GC, Type SHD-GC, and Type MP-GC
  10. 1. Type MP-GC (Section 4, 5 kV to 35 kV): Borehole, Shaft, and Substation Feeders
  11. 2. Type SHD-GC (Section 3, 2 kV to 25 kV): Shielded Mobile Shovel, Drill, and Longwall Trailing
  12. 3. Type G-GC (Section 3, 2,000 V): Unshielded Low-Voltage Loaders, Pumps, and Shuttle Cars
  13. 044. MSHA 30 CFR Part 7 Flame Approval vs. ICEA Construction Compliance: Why Buyers Need Both
  14. 055. How Do You Verify Ampacity, Reel Derating, and Section 6 FAT Compliance on WC 23058 Orders?
  15. Worked Sizing Check: Section 4 Type MP-GC Borehole Feeder + Section 3 Type SHD-GC Trailing Tail
  16. Five-Point Section 6 Factory Acceptance Test (FAT) Checklist for Purchase Orders
  17. 06Frequently Asked Questions (FAQ)
  18. Did ANSI/NEMA WC 23058 (ICEA S-75-381-2025) change cable outer diameters or coupler gland sizes?
  19. Can existing cable stock embossed with NEMA WC 58 still be installed in US mines?
  20. What is the structural difference between Section 3 Type SHD-GC and Section 4 Type MP-GC?
  21. Why is 4 AWG the smallest 8 kV cable permitted under ANSI/NEMA WC 23058?
  22. Does ANSI/NEMA WC 23058 allow XLPE insulation on portable trailing cables?
TL;DR: ANSI/NEMA WC 23058 (ICEA S-75-381-2025) is the 125 page North American cable standard published in September 2025. It replaces ANSI/NEMA WC 58-2017 for portable trailing, reeling, and mine feeder cables from 600 V to 35 kV. Specifically, the new edition shifts NEMA codes to five digits (WC 23058) and links test rules to ANSI/ICEA T-27-581 / NEMA WC 23053-2025. It also unifies 90 °C EPR wall tables (100% and 133% levels, NEMA WC 23058, 2025) and tightens tear limits for CPE, PCP, and TPU jackets. Mine buyers updating purchase orders must pair WC 23058 dimensions with MSHA 30 CFR Part 7 flame print and full-reel partial discharge checks.
  • Joint Standard Number: Legacy Designation (2017 Edition): ANSI/NEMA WC 58-2017 / ICEA S-75-381 | Active Revision (September 2025 Edition): ANSI/NEMA WC 23058 / ICEA S-75-381-2025 (125 pages) | Engineering & Procurement Impact on Mine Orders: Update ERP item masters, RFQ templates, and reel tag specs to WC 23058
  • Companion Test Standard: Legacy Designation (2017 Edition): ICEA T-27-581 / NEMA WC 53 (Legacy) | Active Revision (September 2025 Edition): ANSI/ICEA T-27-581 / NEMA WC 23053-2025 | Engineering & Procurement Impact on Mine Orders: Aligns AC hipot, insulation resistance, and physical aging tests in Section 6
  • Section 3 Portable Cables: Legacy Designation (2017 Edition): Types W, G, G-GC, G-CGC, SHD-GC (<= 2 kV to 35 kV) | Active Revision (September 2025 Edition): Retains rope-lay ASTM B33/B172 copper; unifies EPR wall & minimum AWG rules | Engineering & Procurement Impact on Mine Orders: Enforces minimum 6 AWG (5 kV), 4 AWG (8 kV), 2 AWG (15 kV), and 1 AWG (25 kV)
  • Section 4 Mine Power Feeders: Legacy Designation (2017 Edition): Types MP and MP-GC (2,001 V to 35 kV) | Active Revision (September 2025 Edition): Clarifies Class B/C stranded copper/aluminum, tape shields, and CPE/PVC jackets | Engineering & Procurement Impact on Mine Orders: Governs fixed borehole, shaft, and substation links (never mobile floor drag)
  • Outer Sheath Mechanics: Legacy Designation (2017 Edition): Heavy-duty & extra-heavy-duty thermoset/TPU tables | Active Revision (September 2025 Edition): Unified tear, tensile, and 121 °C oil-swell rules across cured CPE, PCP, and TPU | Engineering & Procurement Impact on Mine Orders: Eliminates single-layer unreinforced jackets on heavy SHD-GC drag jobs

1. Architecture of ANSI/NEMA WC 23058 (ICEA S-75-381-2025): Six Sections and Two Supplements

ANSI/NEMA WC 23058 (ICEA S-75-381-2025) is the joint American National Standard written by ICEA and NEMA to govern materials, dimensions, electrical ratings, and factory tests for surface and underground mine power cables. Released in September 2025, it replaces the 2017 edition across US, Canadian dual-rated, and Latin American mine bids. For a full crosswalk between North American ICEA designs and metric DIN VDE 0250-813 reeling lines, read our mining trailing and reeling cable engineering pillar guide.

Why did NEMA change the code from WC 58 to WC 23058? In 2025, NEMA adopted a five-digit wire and cable code block (23xxx) across joint ICEA publications. This matches the 2025 update of extruded cable test methods in ANSI/ICEA T-27-581 / NEMA WC 23053-2025 Test Methods for Extruded Dielectric Power Cables (2025). Meanwhile, the ICEA base number (S-75-381) stays the same so older mine drawings remain easy to trace.

Crawler-mounted blasthole drill rig operating on an open-pit copper mine bench powered by portable trailing cable under ANSI/NEMA WC 23058 duty

Structural Breakdown of the 125 Page Standard

As announced in the NEMA Standards Action Publication Notice for ICEA S-75-381 / NEMA WC 23058 (2025) and structured across the ANSI/NEMA WC 58 / ICEA S-75-381 Baseline Contents and Scope Outline, the 125 page standard splits into six core sections and two supplements:

  1. Section 1 (General): Sets scope, voltage classes, and unit rules. Temperatures use C, masses use g, liquid volumes use cm³, and resistivities use nOhmm. Physical wire and wall dimensions stay in US units (mils, inches, AWG, and kcmil).
  2. Section 2 (Conductors): Defines strand classes, lay lengths, tin coat checks (ASTM B33), kcmil equivalents for 4/0 AWG and smaller wires, and max 20 °C DC resistance limits.
  3. Section 3 (Portable Cables): Covers flexible trailing and reeling cables (Types W, G, G-GC, G-CGC, PCG, SH, SHD, SHD-GC, SHD-CGC) from 600 V to 35,000 V. It specifies 90 °C EPR phase walls and two-layer reinforced jackets.
  4. Section 4 (Mine Power Cables): Covers fixed feeders (Types MP and MP-GC) from 2,001 V to 35,000 V for surface substations, boreholes, and underground power skids.
  5. Section 5 (Portable Arc Welding Cables): Sets strand flex and heat rules for single-core mine shop welding leads.
  6. Section 6 & Supplements (Tests & Ampacity): Lists AC hipot, DC insulation resistance, partial discharge, tear and oil tests, 40 °C free-air ampacity tables, and drum layer derating factors.

2. Five Technical Revisions Engineers Must Update in 2026 Mine Cable Specifications

Pasting old NEMA WC 58-2017 text into new mine bid sheets triggers vendor submittal delays during drawing sign-off. Aligning specs with our ICEA S-75-381 and NEMA WC 23058 compliant mining cable range requires updating five clear technical items.

1. Consolidated 90 °C EPR Insulation Wall Tables (100% vs. 133% Levels)

Insulation level percentage (100% vs. 133%) is a dielectric wall thickness rating in ANSI/NEMA WC 23058 based on how fast the mine relay clears a phase-to-ground fault (NEMA WC 23058, 2025).

  • 100% Insulation Level: Used where ground-fault relays trip within 1 minute (NEMA WC 23058, 2025). Nominal 90 °C EPR wall thickness is 2.79 mm (110 mils) at 5 kV, 3.81 mm (150 mils) at 8 kV, 5.33 mm (210 mils) at 15 kV, and 7.49 mm (295 mils) at 25 kV.
  • 133% Insulation Level: Required on resistance-grounded or ungrounded mine grids where a fault may stay live for up to 1 hour (NEMA WC 23058, 2025). For example, at 8 kV, the EPR wall steps up from 150 mils (3.81 mm) to 175 mils (4.45 mm). At 15 kV, it steps up from 210 mils (5.33 mm) to 260 mils (6.60 mm).

2. Minimum Phase Conductor Sizes for 5 kV to 25 kV Shielded Cables

Small copper cores create high electric field stress (E_max) along the inner screen edge. To stop corona damage inside the EPR wall, WC 23058 sets strict minimum phase sizes:

  • 5 kV Class: Minimum 6 AWG (13.3 mm²)
  • 8 kV Class: Minimum 4 AWG (21.2 mm²)
  • 15 kV Class: Minimum 2 AWG (33.6 mm²)
  • 25 kV Class: Minimum 1 AWG (42.4 mm²)

You can check the radial stress math (E_max = U0 / [r ln(R/r)]) in our guide on ICEA S-75-381 8 kV cable minimum conductor size and EPDM/PUR design.

3. Rope-Lay Stranding (ASTM B172) vs. Concentric Feeder Stranding (ASTM B8)

Section 3 portable cables (Types W, G-GC, SHD-GC) use soft rope-lay tinned copper (133 to 703 fine wires) built to ASTM B33-10(2020)e1 Standard Specification for Tin-Coated Soft or Annealed Copper Wire (2020) and ASTM B172. Section 4 Type MP-GC feeder cables use stiff 19 wire or 37 wire Class B concentric strands (ASTM B8). Putting stiff Type MP-GC onto a moving drill or shuttle car reel work-hardens and snaps the copper cores within weeks.

4. Extra-Heavy-Duty Jacket Tear, Tensile, and Oil-Immersion Thresholds

Section 3 portable cables require a two-layer reinforced jacket (inner rubber bed + cord mesh + outer skin) cured from CPE, PCP, or TPU. Under WC 23058 and WC 23053-2025 lab tests, extra-heavy-duty thermoset skins must pass unaged tensile checks (>= 16.5 MPa / 2,400 psi) and tear strength (>= 7.0 kN/m / 40 lbf/in). They must also pass hot oil soak tests at 121 °C for 18 hours in IRM 902 oil.

5. Ground-Check (GC) Pilot Insulation and Interstitial Ground Sizing

Every -GC cable (Type G-GC, Type G-CGC, Type SHD-GC, Type MP-GC) carries a yellow polypropylene or EPR ground-check pilot wire (10 AWG or 8 AWG min). Bare or semicon-covered ground cores fill the outer valleys and hold at least 50% to 60% of a single phase core's copper area (NEMA WC 23058, 2025).

  • 2,000 V (Type G-GC / SHD-GC): Min Phase Gauge (WC 23058): 8 AWG (8.37 mm²) | 100% EPR Wall (mils / mm): 60-80 mils (1.52-2.03 mm by AWG) | 133% EPR Wall (mils / mm): Not applicable (2 kV class) | Mandatory Phase Shielding (Section 3): Optional (G-GC unshielded; SHD-GC braided) | Factory AC Test Voltage (5-minute Soak): 5.0 kV to 7.5 kV AC (by AWG range)
  • 5,000 V (Type SHD-GC / MP-GC): Min Phase Gauge (WC 23058): 6 AWG (13.3 mm²) | 100% EPR Wall (mils / mm): 110 mils (2.79 mm) | 133% EPR Wall (mils / mm): 110-140 mils (2.79-3.56 mm) | Mandatory Phase Shielding (Section 3): Semicon screen + >= 60% Cu/nylon braid | Factory AC Test Voltage (5-minute Soak): 18.0 kV AC (100% wall)
  • 8,000 V (Type SHD-GC / MP-GC): Min Phase Gauge (WC 23058): 4 AWG (21.2 mm²) | 100% EPR Wall (mils / mm): 150 mils (3.81 mm) | 133% EPR Wall (mils / mm): 175 mils (4.45 mm) | Mandatory Phase Shielding (Section 3): Inner/outer semicon + >= 60% Cu/nylon braid | Factory AC Test Voltage (5-minute Soak): 24.0 kV AC (100%) / 28.0 kV AC (133%)
  • 15,000 V (Type SHD-GC / MP-GC): Min Phase Gauge (WC 23058): 2 AWG (33.6 mm²) | 100% EPR Wall (mils / mm): 210 mils (5.33 mm) | 133% EPR Wall (mils / mm): 260 mils (6.60 mm) | Mandatory Phase Shielding (Section 3): Inner/outer semicon + >= 60% Cu/nylon braid | Factory AC Test Voltage (5-minute Soak): 34.0 kV AC (100%) / 42.0 kV AC (133%)
  • 25,000 V (Type SHD-GC / MP-GC): Min Phase Gauge (WC 23058): 1 AWG (42.4 mm²) | 100% EPR Wall (mils / mm): 295 mils (7.49 mm) | 133% EPR Wall (mils / mm): 360 mils (9.14 mm) | Mandatory Phase Shielding (Section 3): Inner/outer semicon + >= 60% Cu/nylon braid | Factory AC Test Voltage (5-minute Soak): 48.0 kV AC (100%) / 58.0 kV AC (133%)

3. Section 3 Portable Cables vs. Section 4 Mine Power Feeder Cables: Selecting Type G-GC, Type SHD-GC, and Type MP-GC

A common error on greenfield mine bills of materials (BOMs) is mixing up Section 4 fixed mine feeders (Type MP-GC) with Section 3 mobile trailing lines (Type SHD-GC and Type G-GC). Both carry -GC pilot wires and 90 °C EPR walls, yet their strands, shields, and jackets serve very different jobs across our mining and tunnelling cable portfolio and heavy-duty trailing cable series.

Horizontal cutaway of Type MP-GC medium-voltage mine power feeder cable showing Class B stranded copper conductors, EPR insulation, copper tape phase shields, ground conductors, ground-check pilot, and heavy CPE jacket

1. Type MP-GC (Section 4, 5 kV to 35 kV): Borehole, Shaft, and Substation Feeders

Type MP-GC mine power feeder cable is a stationary MV distribution cable built under ANSI/NEMA WC 23058 Section 4 with 19 or 37 strand Class B cores and EPR or XLPE walls. It uses lapped 5 mil copper tape phase shields, two bare ground cores, one GC pilot, and a single heavy CPE or PVC jacket. Lapped copper tape cracks quickly if bent over moving sheaves. Specify our Type MP-GC mine power feeder cable (5 kV to 35 kV) strictly for cable trays, aerial messenger wires, vertical boreholes, and fixed substation ties.

2. Type SHD-GC (Section 3, 2 kV to 25 kV): Shielded Mobile Shovel, Drill, and Longwall Trailing

Whenever a power line drags behind an electric rope shovel, walking dragline, blasthole drill, or longwall shearer, pick our Type SHD-GC shielded heavy-duty portable mining cable. Type SHD-GC swaps stiff tape shields for a soft tinned-copper and nylon braid (>= 60% cover, NEMA WC 23058, 2025) over 259 to 703 wire rope-lay copper strands. A cured two-layer cord-reinforced jacket protects the core against sharp pit rock. Watch a 2 kV 3x2 AWG drill reel pass factory tests in our Type SHD-GC 2 kV blasthole drill trailing cable FAT video.

Horizontal cutaway of Type G-GC 2,000 V portable mining cable showing rope-lay tinned copper phase conductors, EPR insulation, twin grounding cores, yellow ground-check wire, and reinforced thermoset CPE jacket

3. Type G-GC (Section 3, 2,000 V): Unshielded Low-Voltage Loaders, Pumps, and Shuttle Cars

For 480 V, 600 V, and 995 V AC mobile gear up to 2,000 V where phase shields are not required, pick our Type G-GC 2,000 V portable mining power cable. It packs three rope-lay EPR phase cores, two ground wires, and one yellow GC pilot inside a tough CPE or PCP skin. For high-amp (> 150 A) coal shuttle cars where uneven ground wires can cause frame sparks, step up to the balanced 3 ground Type G-CGC build in Section 3.

4. MSHA 30 CFR Part 7 Flame Approval vs. ICEA Construction Compliance: Why Buyers Need Both

MSHA 30 CFR Part 7 Subpart K flame-resistance approval is a mandatory US federal safety credential for underground mine cables. It verifies that a 204 °C pre-heated cable sample self-extinguishes within 60 seconds with a char length at or below 152 mm (6.0 inches) over a 955 °C burner.

Buyers must never assume that ICEA S-75-381-2025 compliance automatically grants MSHA mine approval. Each rule tests a separate safety layer:

  • What ANSI/NEMA WC 23058 (ICEA S-75-381-2025) Covers: Wall thickness, copper flex life, 90 °C EPR voltage strength, partial discharge (<= 5 pC), ampacity, and jacket tear limits.
  • What MSHA 30 CFR Part 7 and Part 75 / Part 77 Cover: Flame burn limits (30 CFR 7.407), permanent jacket print (P-07-KAxxxx-MSHA), breaker trip settings under eCFR 30 CFR Part 77 Subpart G Trailing Cables Rules (2026), and underground splice rules (30 CFR 75.603).
Underground coal mine steel-arch gallery showing overhead power feeder cable routing and confined roadway conditions governed by MSHA flame-resistance rules

For Canadian mines in Ontario, Quebec, Saskatchewan, and British Columbia, buyers often pair ANSI/NEMA WC 23058 dimensions with CSA C22.2 No. 96 (FT1 / FT4 / FT5 flame and -40 °C cold-impact tests). Always list your exact regional code on the purchase order so jacket markings pass site safety audits.

5. How Do You Verify Ampacity, Reel Derating, and Section 6 FAT Compliance on WC 23058 Orders?

Section 6 and the supplements of ANSI/NEMA WC 23058 set clear ampacity boundaries and Factory Acceptance Test (FAT) pass marks.

Worked Sizing Check: Section 4 Type MP-GC Borehole Feeder + Section 3 Type SHD-GC Trailing Tail

Consider a 13.8 kV (15 kV 133% wall, 6.60 mm / 260 mils EPR) mine circuit feeding a longwall power skid at 185 A continuous load (40 °C air, cos(phi) = 0.85). A 1.2 km borehole Type MP-GC feeder connects to a 250 m Type SHD-GC trailing cable wound in 1 drum layer (K_reel = 0.85):

Feeder (Type MP-GC in air/messenger, 40 °C): | I_required = 185 A -> Select 2/0 AWG MP-GC (I_base = 235 A at 15 kV) | Delta_V_feeder = 1.732 * 185 A * 1.2 km * (0.312 * 0.85 + 0.118 * 0.527) = 125.9 V (0.91%) | Trailing Tail (Type SHD-GC with 1 drum layer, K_reel = 0.85): | 2/0 AWG SHD-GC (I_base = 239 A at 15 kV) -> 239 A * 0.85 = 203.2 A (> 185 A OK) | Delta_V_tail = 1.732 * 185 A * 0.25 km * (0.334 * 0.85 + 0.116 * 0.527) = 27.6 V (0.20%) | Total Circuit Voltage Drop = 153.5 V (1.11% of 13.8 kV, well under the 3%-5% mine cap)

For full 8 kV, 15 kV, and 25 kV impedance tables, consult our guide on Type SHD-GC 8 kV, 15 kV, and 25 kV ampacity and voltage drop calculations.

Five-Point Section 6 Factory Acceptance Test (FAT) Checklist for Purchase Orders

Before releasing final shipment payment on any WC 23058 order, require serialized reel test sheets aligned with U.S. Mine Safety and Health Administration (MSHA) Equipment Approval Guidelines (2025) and NEMA WC 23053-2025:

  1. 20 °C DC Conductor & Pilot Resistance (Section 2 & 6): Check phase, ground, and GC wire resistance on 100% of finished reels (NEMA WC 23058, 2025).
  2. Full-Reel Partial Discharge (Section 6): Test all shielded MV reels (>= 5 kV) inside a Faraday room. Require <= 5 pC discharge at 1.73 U0 after 2.0 U0 pre-stress.
  3. 5-minuteute AC High-Voltage Withstand (Section 6): Confirm zero breakdown at the table voltage (e.g., 28 kV AC for 8 kV 133% wall; 42 kV AC for 15 kV 133% wall).
  4. Insulation Resistance Constant (Ki): Measure DC insulation resistance corrected to 15.6 °C (Ki >= 20,000 MOhm1,000 ft for 90 °C EPR).
  5. Permanent Jacket Embossing & Length Audit: Inspect molded or indent jacket print confirming voltage, AWG, Type SHD-GC / G-GC / MP-GC, WC 23058, and MSHA code. You can contact our mining cable engineering desk for WC 23058 datasheets and FAT witness tests or view our test facilities on our company engineering profile.

Frequently Asked Questions (FAQ)

Did ANSI/NEMA WC 23058 (ICEA S-75-381-2025) change cable outer diameters or coupler gland sizes?

No. Nominal EPR wall thicknesses (100% and 133% levels, NEMA WC 23058, 2025), rope-lay copper diameters, and outer diameter (OD) tolerances in ANSI/NEMA WC 23058 (ICEA S-75-381-2025) match WC 58-2017. Existing PLM, Patton & Cooke, and TJB medium-voltage mine couplers fit WC 23058 cables with zero gland changes.

Can existing cable stock embossed with NEMA WC 58 still be installed in US mines?

Yes. Field inspectors under MSHA 30 CFR Part 75 and Part 77 check for valid MSHA flame print (P-07-KAxxxx-MSHA), proper ampacity sizing, undamaged jackets, and working ground-check relays. Existing WC 58-2017 stock stays legal for mine installation, while new factory runs ship under WC 23058.

What is the structural difference between Section 3 Type SHD-GC and Section 4 Type MP-GC?

Type SHD-GC (Section 3) is a flexible mobile trailing cable built with 259 to 703 wire rope-lay tinned copper (ASTM B172). It uses soft tinned-copper and nylon braid shields (>= 60% cover, NEMA WC 23058, 2025) inside a two-layer cord-reinforced rubber or TPU jacket. Type MP-GC (Section 4) is a fixed feeder cable built with stiff 19 or 37 wire Class B strands (ASTM B8), lapped 5 mil copper tape shields, and a single CPE or PVC jacket for boreholes and trays.

Why is 4 AWG the smallest 8 kV cable permitted under ANSI/NEMA WC 23058?

Wires smaller than 4 AWG (5.89 mm strand diameter) create high electric field stress (kV/mm) at the inner semiconductive screen when energized at 8 kV (U0 = 4.62 kV). WC 23058 sets 4 AWG as the 8 kV floor size to stop corona treeing and preserve mechanical pull strength during rock dragging.

Does ANSI/NEMA WC 23058 allow XLPE insulation on portable trailing cables?

While Section 3 and Section 4 tables list both XLPE and EPR walls, stiff XLPE is used almost exclusively in Section 4 fixed Type MP-GC borehole and shaft feeders. Mobile Section 3 trailing and reeling cables (Types W, G-GC, G-CGC, SHD-GC) use flexible 90 °C thermoset EPR rubber so cores never crack under tight bending.

Image credits: Walking dragline hero photo derived from "Dragline, Luminant Energy Kosse lignite mine (5556780431)" by Roy Luck via Wikimedia Commons (CC BY 2.0, modified to remove equipment unit marking); open-pit blasthole drill rig photo derived from "Drilling rig (Continental Mine, Butte, Montana, USA) 10" by James St. John via Wikimedia Commons (CC BY 2.0, modified to remove boom brand marking); underground coal mine gallery photo "Kohlebergwerk, Blegny (Blegny-Mine) II, Belgique" by Horst J. Meuter via Wikimedia Commons (CC BY-SA 4.0); Type MP-GC and Type G-GC horizontal cutaway diagrams by TEBAOFLEX.

Specify it

Sizes, technical data and documents for each cable.

Type G-GC — horizontal cutaway

Rubber Cable

Type G-GC

Type G-GC provides portable power with a separate ground-check function for mining equipment. The configuration on this page is a round three-power-core, 2 kV cable with a CPE jacket.

Rated voltage
2,000 V
Sizes
1
Sizes and data →
Type MP-GC — horizontal cutaway

Rubber Cable

Type MP-GC

Type MP-GC is a mine power-feeder cable family for stationary and semi-portable distribution routes. The typical construction combines three screened phase conductors, two grounding conductors and an insulated ground-check conductor.

Rated voltage
5 kV
Sizes
2
Sizes and data →
Type SHD-GC — horizontal cutaway

Rubber Cable

Type SHD-GC

Type SHD-GC is a heavy-duty 2 kV to 25 kV three-conductor portable mining trailing cable with individually shielded EPR power cores, two grounding conductors and one insulated ground-check conductor. Flexible rope-lay tinned copper and a CPE or TPU jacket suit continuous miners, shovels, draglines and other mobile equipment where severe trailing service, flexibility and ground-continuity monitoring are required.

Rated voltage
2 kV
Standard
ICEA
Sizes and data →