Furnace, kiln & high-temp zone
Thermal-rated 0.6/1 kV SiR build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.
Product
YGC 0.6/1 kV Silicone pairs IEC 60228 Class 5 bare copper power cores with 180 °C halogen-free silicone rubber insulation and a red-oxide silicone outer sheath for steelworks, power plants, and high-ambient machinery.
Typical values for this cable type, based on JB/T 8734 (ref.) · IEC 60502-1 (ref.) · IEC 60228 Class 5 — confirmed in the datasheet and quotation for your order.
Application fit
YGC 0.6/1 kV Silicone pairs IEC 60228 Class 5 bare copper power cores with 180 °C halogen-free silicone rubber insulation and a red-oxide silicone outer sheath for steelworks, power plants, and high-ambient machinery.
Thermal-rated 0.6/1 kV SiR build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.
Durable 0.6/1 kV SiR geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Rugged 0.6/1 kV SiR construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.
Thermal-aged 0.6/1 kV SiR insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.
0.6/1 kV SiR construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR0.6/1 kV SiR outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of YGC 0.6/1 kV Silicone Cable: IEC 60228 Class 5 flexible bare annealed copper, Colour-coded 180 °C halogen-free silicone rubber core insulation, and Red-oxide ozone- & heat-resistant halogen-free silicone outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 5 flexible bare annealed copperIEC 60228 Class 5 |
| 2 | Cooling core / primary dielectric | Colour-coded 180 °C halogen-free silicone rubber core insulationJB/T 8734 (ref.) |
| 3 | Outer sheath / hose | Red-oxide ozone- & heat-resistant halogen-free silicone outer sheath180 °C Continuous Silicone |
Multi-element core assembly with color-coded conductors and protective heavy-duty outer sheath.
Technical data
Sizes
| Cores × mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 10×D mm |
|---|---|---|---|---|---|
| 3G2.5 mm² | 10.6 | 7.980 | 72 | 203 | 106 |
| 4G2.5 mm² | 11.6 | 7.980 | 96 | 258 | 116 |
| 4G4 mm² | 13.4 | 4.950 | 154 | 381 | 134 |
| 4G6 mm² | 15.2 | 3.300 | 230 | 537 | 152 |
| 4G10 mm² | 18.6 | 1.910 | 384 | 861 | 186 |
| 4G16 mm² | 21.8 | 1.210 | 614 | 1,309 | 218 |
| 4G25 mm² | 26.2 | 0.780 | 960 | 1,996 | 262 |
| 4G35 mm² | 29.8 | 0.554 | 1,344 | 2,730 | 298 |
| 4G50 mm² | 34.6 | 0.386 | 1,920 | 3,838 | 346 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| High-voltage dielectric withstand test | 3.5 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 5 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -60 °C to +180 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | 180 °C Continuous Silicone · Halogen-Free Self-Extinguishing | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.