Contact

UL 5390 / 5400 550 °C 600 V Mica-Glass High-Temp WireExtreme 550 °C pure nickel / nickel-Cu mica-tape fibreglass furnace wire

UL 5390 / 5400 550 °C Mica Wire wraps stranded nickel-plated copper (or pure nickel) in multi-layer phlogopite mica tape under a white high-temperature treated fibreglass outer braid rated 600 V and +550 °C continuous.

Flame-retardant
Oil-resistant
Approved
Order designation
UL 5390/5400 550°C Mica Wire 1×12 AWG
Outer Ø
4.0 mm
Max. R20
6.395 Ω/km
Weight
66 kg/km
Min. bend R
32 mm
All sizes (8)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
600 V
Test voltage 2.5 kV AC
Temp. (fixed)
-60°C…+550°C
Flexing: -40 °C to +450 °C
Construction
Mica + Glass
Multi-layer overlapping phlogopite
Min. bend radius
8 × OD
High-current flexible routing
Conductor
Nickel-Plated Cu
Per UL AWM Style 5390
Size range
1×18 AWG–1×4 AWG
8 standard configurations

Typical values for this cable type, based on UL AWM Style 5390 · UL AWM Style 5400 · UL 758 — confirmed in the datasheet and quotation for your order.

Application fit

Is UL 5390/5400 550°C Mica Wire right for your machine?

UL 5390 / 5400 550 °C Mica Wire wraps stranded nickel-plated copper (or pure nickel) in multi-layer phlogopite mica tape under a white high-temperature treated fibreglass outer braid rated 600 V and +550 °C continuous.

Furnace, kiln & high-temp zone

Suitable

Thermal-rated 600 V Mica build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.

Fixed installation

Suitable

Durable 600 V Mica geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.

High-temperature boiler & thermal plant

Suitable

Thermal-aged 600 V Mica insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.

Motor stator & transformer coil winding

Suitable

High-dielectric 600 V Mica winding insulation handles compact submersible, traction, and industrial motor stator slots reliably.

Energy chain / drag chain

Not suitable

600 V Mica construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Immersion & wet locations

Not suitable

600 V Mica outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.

Use EMC-VFD Submersible EPDM
Typical machinesSteelworks, rolling mills & aluminum smeltersIndustrial ovens, ceramic kilns & glassworksCommercial heating elements & cartridge heatersPower plants, boiler rooms & hot switchgear

Construction

Layer by layer

Representative construction of UL 5390/5400 550°C Mica Wire: ASTM B355 Class K stranded nickel-plated copper (27% Ni high-temp), Multi-layer overlapping phlogopite mica tape primary dielectric, and White high-temperature varnished fibreglass outer braid (mica/glass).

123
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorASTM B355 Class K stranded nickel-plated copper (27% Ni high-temp)ASTM B355 Nickel Cu
2Mica / PTFE tape dielectricMulti-layer overlapping phlogopite mica tape primary dielectricUL AWM Style 5390
3Fibreglass outer braidWhite high-temperature varnished fibreglass outer braid (mica/glass)550 °C Continuous Rating

UL 5390/5400 550°C Mica Wire Mica-Glass

Single high-temperature conductor wrapped in overlapping thermal dielectric tape and varnished fibreglass outer braid.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL AWM Style 5390 · UL AWM Style 5400 · UL 758. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
600 V
Test voltage
2.5 kV AC
Conductor
Nickel-Plated Cu
Core / dielectric
Multi-layer overlapping phlogopite mica
Impedance / insulation
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-60 °C to +550 °C
Temp. range (flexing)
-40 °C to +450 °C
Peak / short-circuit
+600 °C (short-term)
Min. bending radius
8 × OD

Resistance

Primary performance
550 °C Continuous Rating
Environment / duty
UL VW-1 Non-Flammable
Mechanical / special
Phlogopite Mica Barrier
Outer finish
White high-temperature varnished

Sizes

High-Temp Mica/Glass Wire (AWG)
Conductor
AWG
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
8×D mm
1×18 AWG2.725.98482022
1×16 AWG3.016.464122824
1×14 AWG3.510.158194328
1×12 AWG4.06.395316632
1×10 AWG4.64.021499937
1×8 AWG5.42.5317815343
1×6 AWG6.41.59012423751
1×4 AWG7.70.99919737162
  • Conductor DC resistance R20 at 20 °C per ASTM B355 Nickel Cu.
  • Minimum bending radius calculated at 8 × nominal outer diameter (OD). Custom terminations available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
High-voltage dielectric withstand test2.5 kV AC without breakdownEvery manufactured length
Continuity & conductor DC resistancePer ASTM B355 Nickel Cu at 20 °CEvery drum / assembly
Sample tests
Tensile, dimensional & pressure checkRated -60 °C to +550 °C continuousPer production lot
Environmental, thermal & mechanical qualification550 °C Continuous Rating · UL VW-1 Non-FlammableType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL AWM Style 5390UL AWM Style 5400UL 758EN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

UL 5390/5400 550°C Mica Wire 600 V TEBAOFLEX.COM [UL AWM Style 5390] [Size] [Metre mark]
Delivery form
Custom assemblies, coils or export drums
Standard lengths
Cut-to-length · 100 m · 500 m · 1,000 m
MOQ
1 assembly / 50 m (stock) · 300 m (custom)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-23
Updated
2026-11-23

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes UL 5390/5400 550°C Mica Wire suited for demanding 600 V installations?
UL 5390/5400 550°C Mica Wire combines ASTM B355 Class K stranded nickel-plated copper (27% Ni high-temp) with Multi-layer overlapping phlogopite mica tape primary dielectric and White high-temperature varnished fibreglass outer braid (mica/glass). Survives 550 °C continuous oven, kiln, and foundry radiant zones where silicone and PTFE degrade rapidly.
What minimum bending radius should be respected for UL 5390/5400 550°C Mica Wire?
Maintain a minimum bending radius of 8 × OD across -40 °C to +450 °C flexing temperatures to ensure long mechanical and dielectric service life.
Can UL 5390/5400 550°C Mica Wire be delivered pre-terminated with custom lugs, water fittings, or subsea connectors?
Yes. TEBAOFLEX supplies UL 5390/5400 550°C Mica Wire either in bulk lengths or factory-assembled with copper lugs, water-cooled swivel fittings, or molded subsea wet-mate connectors.
What quality tests and certificates accompany every shipment of UL 5390/5400 550°C Mica Wire?
UL 5390/5400 550°C Mica Wire conforms to UL AWM Style 5390, UL AWM Style 5400, UL 758 (550 °C Continuous Rating) and ships with an EN 10204 3.1 routine factory test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for UL 5390/5400 550°C Mica Wire

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

UL 5390 / 5400 550 °C 600 V Mica-Glass High-Temp Wire

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote