Trailing & towing
Photoluminescent and retroreflective yellow TMPU jacket prevents vehicle run-over in dark tunnels and pits.
Product
PWR AFR PUR+LUM 0.6/1 kV halogen-free mobile trailing and reeling power cable featuring Class 5 copper phase, split PE and pilot cores with XLPE insulation, aramid reinforcement braid and a photoluminescent retroreflective yellow PUR sheath.
Typical values for this cable type, based on IEC 60502-1 / EN 50525-2-21 — confirmed in the datasheet and quotation for your order.
Application fit
PWR AFR PUR+LUM 0.6/1 kV halogen-free mobile trailing and reeling power cable featuring Class 5 copper phase, split PE and pilot cores with XLPE insulation, aramid reinforcement braid and a photoluminescent retroreflective yellow PUR sheath.
Photoluminescent and retroreflective yellow TMPU jacket prevents vehicle run-over in dark tunnels and pits.
Halogen-free flame-retardant construction for tunnel boring machines, underground portals and emergency power.
Aramid load-bearing reinforcement braid supports horizontal reeling and mobile generator payouts.
High-visibility optical safety sheath remains clearly visible under headlamp beams and power blackouts.
Construction
Shown: PWR AFR PUR+LUM (IEC 60502-1 / EN 50525-2-21) featuring main power cores (3x25 mm²), split pe cores (3x6 mm²) and pur+lum high-visibility sheath (5-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Main Power Cores (3x25 mm²) | Class 5 flexible plain annealed copper phase conductors with crosslinked polyethylene (XLPE) insulationIEC 60502-1 / EN 50525-2-21 |
| 2 | Split PE Cores (3x6 mm²) | Three symmetrical green/yellow XLPE-insulated protective earth conductors positioned in the outer intersticesIEC 60502-1 / EN 50525-2-21 |
| 3 | Pilot / Control Cores (2x1.0 mm²) | Two XLPE-insulated flexible plain copper pilot cores for continuity and control monitoringIEC 60502-1 / EN 50525-2-21 |
| 4 | Aramid Reinforcement Braid | High-tenacity braided aramid yarn reinforcement layer absorbing tensile and torsional reeling/trailing loadsIEC 60502-1 / EN 50525-2-21 |
| 5 | PUR+LUM High-Visibility Sheath | Halogen-free yellow thermoplastic polyurethane (TMPU) outer sheath with integrated photoluminescent and retroreflective elementsIEC 60502-1 / EN 50525-2-21 |
Built to IEC 60502-1 / EN 50525-2-21 with main power cores (3x25 mm²) and pur+lum high-visibility sheath
Available in custom drum lengths, core counts or factory-terminated assemblies
Supplied with EN 10204 3.1 routine electrical, dielectric & dimensional inspection report
Technical data
Sizes
Manufactured to IEC 60502-1 / EN 50525-2-21 for heavy-duty industrial and specialty engineering systems.
| Order designation | Configuration | Core / stranding | Outer Ø ≈ mm | Weight ≈ kg/km | Tensile load kN ≈ | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| PWR AFR PUR+LUM Construction Schedule (−40…+90 °C) | |||||||
| PWR AFR PUR+LUM 3×16+3×4+2×1.0 | 3×16 + 3×4 + 2×1.0 mm² | Class 5 Cu + aramid braid | 24.5 | 980 | 4.5 | 150 | |
| PWR AFR PUR+LUM 3×25+3×6+2×1.0 | 3×25 + 3×6 + 2×1.0 mm² | Class 5 Cu + aramid braid | 28.2 | 1,390 | 6.5 | 170 | |
| PWR AFR PUR+LUM 3×35+3×6+2×1.0 | 3×35 + 3×6 + 2×1.0 mm² | Class 5 Cu + aramid braid | 31.4 | 1,780 | 8.5 | 190 | |
| PWR AFR PUR+LUM 3×50+3×10+2×1.5 | 3×50 + 3×10 + 2×1.5 mm² | Class 5 Cu + aramid braid | 35.8 | 2,420 | 11.5 | 215 | |
| Configuration | Max. DC R₂₀ / Atten. Ω/km or dB/km | Rating / Capacity | Operating temp. |
|---|---|---|---|
| 3×16 + 3×4 + 2×1.0 mm² | 1.21 | 0.6/1 kV / 98 A | −40…+90 °C |
| 3×25 + 3×6 + 2×1.0 mm² | 0.78 | 0.6/1 kV / 131 A | −40…+90 °C |
| 3×35 + 3×6 + 2×1.0 mm² | 0.55 | 0.6/1 kV / 162 A | −40…+90 °C |
| 3×50 + 3×10 + 2×1.5 mm² | 0.39 | 0.6/1 kV / 202 A | −40…+90 °C |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & dimensional verification (IEC 60502-1 / EN 50525-2-21) | Electrical parameters and outer diameter within IEC 60502-1 / EN 50525-2-21 tolerances | Every manufactured drum / length |
| High-voltage dielectric & insulation resistance test (IEC 60502-1 / EN 50525-2-21) | Zero dielectric breakdown and verified insulation resistance over full length | Every manufactured drum / length |
| Sample tests | ||
| Thermal ageing, mechanical flexing & environmental qualification (IEC 60502-1 / EN 50525-2-21) | Verified structural and dielectric integrity across −40…+90 °C | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.