Fixed installation
Engineered and verified for fixed service in accordance with SANS 97 / BS 6480 / IEC 60055.
Product
SANS 97 / BS 6480 Belted Paper-Insulated Lead-Covered (PILC) Steel-Tape Armoured Power Cable (PILC BELTED) engineered to SANS 97 / BS 6480 / IEC 60055 for 0.6/1 kV – 6.35/11 kV service across -10 °C to +80 °C, featuring stranded copper conductor and pvc outer
Typical values for this cable type, based on SANS 97 / BS 6480 / IEC 60055 — confirmed in the datasheet and quotation for your order.
Application fit
SANS 97 / BS 6480 Belted Paper-Insulated Lead-Covered (PILC) Steel-Tape Armoured Power Cable (PILC BELTED) engineered to SANS 97 / BS 6480 / IEC 60055 for 0.6/1 kV – 6.35/11 kV service across -10 °C to +80 °C, featuring stranded copper conductor and pvc outer
Engineered and verified for fixed service in accordance with SANS 97 / BS 6480 / IEC 60055.
Suitable for switchgear, control panels and equipment terminations within 15 × OD bend radius.
Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.
Not designed for high-speed monospiral crane reeling; select a dedicated reeling cable.
NSHTOU Reeling CableConstruction
Shown: PILC BELTED (SANS 97 / BS 6480 / IEC 60055) with stranded copper conductor, impregnated paper tapes and pvc outer serving (8-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Stranded copper conductor | High-conductivity copper conductor per SANS 97 / BS 6480 / IEC 60055SANS 97 / BS 6480 / IEC 60055 |
| 2 | Impregnated paper tapes | Impregnated paper tapes (individual core / group layer)SANS 97 / BS 6480 / IEC 60055 |
| 3 | Impregnated paper belt | Impregnated paper belt (lapped tape)SANS 97 / BS 6480 / IEC 60055 |
| 4 | Lead alloy sheath | Extruded Lead alloy sheath protective layer (continuous layer)SANS 97 / BS 6480 / IEC 60055 |
| 5 | PVC armour bedding | PVC armour bedding mechanical protection (continuous layer)SANS 97 / BS 6480 / IEC 60055 |
| 6 | Inner steel armour tape | Inner steel armour tape mechanical protection (lapped tape)SANS 97 / BS 6480 / IEC 60055 |
| 7 | Outer steel armour tape | Outer steel armour tape mechanical protection (lapped tape)SANS 97 / BS 6480 / IEC 60055 |
| 8 | PVC outer serving | Extruded PVC outer serving protective layer (continuous layer)SANS 97 / BS 6480 / IEC 60055 |
Built to SANS 97 / BS 6480 / IEC 60055 with stranded copper conductor and pvc outer serving
Full range of metric mm² and AWG/kcmil conductor sizes per SANS 97 / BS 6480 / IEC 60055
Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate
Technical data
Sizes
Manufactured to SANS 97 / BS 6480 / IEC 60055 across standard single-core and multi-core cross-sections.
| Order designation | Configuration | Outer Ø ≈ mm | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|
| PILC BELTED Standard Production Schedule (0.6/1 kV – 6.35/11 kV · −10…+80 °C) | |||||
| PILC BELTED 3G1.5 | 3 × 1.5 mm² | 8.4 | 105 | 68 | |
| PILC BELTED 4G1.5 | 4 × 1.5 mm² | 9.2 | 128 | 74 | |
| PILC BELTED 5G1.5 | 5 × 1.5 mm² | 10.1 | 156 | 81 | |
| PILC BELTED 3G2.5 | 3 × 2.5 mm² | 9.8 | 148 | 78 | |
| PILC BELTED 4G2.5 | 4 × 2.5 mm² | 10.8 | 186 | 86 | |
| PILC BELTED 5G2.5 | 5 × 2.5 mm² | 11.9 | 228 | 95 | |
| PILC BELTED 4G4 | 4 × 4.0 mm² | 12.6 | 268 | 101 | |
| PILC BELTED 4G6 | 4 × 6.0 mm² | 14.2 | 365 | 114 | |
| PILC BELTED 4G10 | 4 × 10 mm² | 17.5 | 580 | 140 | |
| PILC BELTED 4G16 | 4 × 16 mm² | 20.4 | 845 | 163 | |
| PILC BELTED 4G25 | 4 × 25 mm² | 24.8 | 1,290 | 198 | |
| PILC BELTED 4G35 | 4 × 35 mm² | 27.9 | 1,710 | 223 | |
| Cross-section | Max. DC R₂₀ Ω/km | Current in air A (30 °C) ≈ | Voltage drop mV/A·m |
|---|---|---|---|
| 1.5 mm² (AWG 16) | 13.30 | 18 | 29.0 |
| 2.5 mm² (AWG 14) | 7.98 | 26 | 17.5 |
| 4.0 mm² (AWG 12) | 4.95 | 34 | 10.9 |
| 6.0 mm² (AWG 10) | 3.30 | 44 | 7.3 |
| 10 mm² (AWG 8) | 1.91 | 61 | 4.2 |
| 16 mm² (AWG 6) | 1.21 | 82 | 2.7 |
| 25 mm² (AWG 4) | 0.78 | 108 | 1.7 |
| 35 mm² (AWG 2) | 0.55 | 135 | 1.2 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor DC resistance & dimensional verification (SANS 97 / BS 6480 / IEC 60055) | DC resistance at 20 °C and geometry within SANS 97 / BS 6480 / IEC 60055 class limits | Every manufactured drum / spool |
| Routine dielectric / spark / structural integrity test (SANS 97 / BS 6480 / IEC 60055) | Zero breakdown or structural defect over full production length | Every manufactured drum / spool |
| Sample tests | ||
| Thermal aging, mechanical & material qualification (SANS 97 / BS 6480 / IEC 60055) | Full compliance with SANS 97 / BS 6480 / IEC 60055 across −10…+80 °C | Type qualification & periodic sample audit |
Marking & supply
Sheath marking
Technical documents
FAQ