British Coal MGM 109 / MGM 118 & PN-G-90006 Underground Mining Power CablesMGM 118 Type 6010 & 60203.8/6.6 kV · 3-Core UnscreenedSWA (6010) / DWA (6020) ≥ 75 % Earth

MGM 118 Type 6010 / 6020 Unscreened Armoured MV Feeder CableBritish Coal MGM 118 / BS 6708 3.8/6.6 kV Type 6010 (SWA) & Type 6020 (DWA) unscreened

MGM 118 Type 6010 / 6020 Unscreened Armoured MV Feeder Cable is manufactured to British Coal Specification MGM 118 and BS 6708 for 3.8/6.6 kV underground mine roadway and shaft high-voltage distribution, featuring three Class 2 tinned copper conductors (25

Flame-retardant
EMC screen
Oil-resistant
Water-resistant
Order designation
MGM 118 Type 6010 3C × 70 mm² SWA (Cu/GSW)
Outer Ø ≈
47.4 mm
Copper weight
2,280 kg/km
Total weight ≈
4,650 kg/km
Min. bend R (fixed)
569 mm
All sizes (6)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Specification
MGM 118 / BS
Type 6010 (SWA) & Type 6020 (DWA)
Rated voltage
3.8/6.6 kV AC
11 kV AC / 5 min dielectric test
Core screening
Unscreened (0)
Coordinated EPR wall + armour earth
Armouring
SWA / DWA
Galvanized steel + Cu wires (≥ 75 %)
Insulation
90 °C HV-EPR
Type GP4 / GP5 cross-linked rubber
Outer sheath
Mining FR-PVC
Heavy-duty flame-retardant PVC

Typical values for this cable type, based on British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type 6020 DWA 3.8/6.6 kV) — confirmed in the datasheet and quotation for your order.

Application fit

Is MGM 118 Type 6010 / 6020 right for your machine?

Engineered for 6.6 kV underground mine trunk roadways, pit-bottom HV substations,vertical shafts (Type 6020 DWA), and bolted 6.6 kV flameproof coupler distribution systems.

Fixed installation

Suitable

Type 6010 SWA serves horizontal HV roadways; Type 6020 DWA supports vertical shaft drops and steep incline drifts.

Switchgear & control cabinet wiring

Suitable

Unscreened 6.6 kV EPR cores fit directly into traditional compound-filled or elastomeric BS 6708 6.6 kV mining couplers.

Immersion & wet locations

Suitable

Extruded PVC bedding and mining-grade outer PVC sheath protect the 6.6 kV core assembly in wet shafts.

Energy chain / drag chain

Not suitable

Fixed armoured 6.6 kV mining trunk feeder.

MGM 118 Type 6110
Typical machines6.6 kV underground coal mine trunk roadwaysVertical mine shaft & drift HV feeders6.6 kV/3.3 kV or 6.6 kV/1.1 kV flameproof transwitch unitsMain underground dewatering & booster stations

Construction

Layer by layer

Three circular stranded tinned annealed copper conductors (BS EN 60228 Class 2, 25 to 185 mm²), conductor semi-conductive stress control

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Stranded tinned copper conductorBS EN 60228 Class 2 circular compacted tinned annealed copper (25 to 185 mm²)MGM 118 / BS EN 60228
26.6 kV EPR rubber insulation (90 °C)Conductor stress-control layer + cross-linked 90 °C EPR insulation per BS 7655-1.2MGM 118 / BS 7655-1.2
3Extruded PVC inner beddingFlame-retardant extruded PVC inner beddingMGM 118
4SWA (Type 6010) or DWA (Type 6020) ≥Single or double layer of galvanized steel round wires interspersed with tinned copperMGM 118 / BS 6708
5Mining flame-retardant PVC outer sheathHeavy-duty abrasion- and flame-retardant PVC outer sheath, Black or HV RedMGM 118 / BS 7655

MGM 118 Type 6010 Single-Wire-Armoured (3C × 25 to 185 mm²)

3.8/6.6 kV unscreened SWA feeder for horizontal underground roadways and pit-bottom switchrooms.

MGM 118 Type 6020 Double-Wire-Armoured (3C × 25 to 185 mm²)

3.8/6.6 kV unscreened DWA feeder for vertical shafts, steep drifts, and high-crush longwall gates.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type 6020 DWA 3.8/6.6 kV). Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage U0/U
3.8/6.6 kV AC (3800/6600 V)
AC dielectric test voltage
11,000 V AC for 5 minutes
Max. conductor operating temp.
+90 °C continuous · +250 °C short-circuit
Metallic armour conductance
≥ 75 % of the conductance of one phase

Thermal

Operating temperature range
-15 °C to +90 °C (fixed installation)
Minimum installation temp.
0 °C

Mechanical

Min. bending radius
10 × D (Type 6010 SWA) · 12 × D (Type 6020
Impact & crush protection
Single or double galvanized steel + copper

Resistance

Flame retardance
BS EN 60332-1-2 & British Coal MGM 118
Water, oil & chemical resistance
Heavy mining PVC oversheath resists acidic

Reference standards

Primary specification
British Coal Specification MGM 118 (Types
Material standards
BS EN 60228 · BS 7655-1.2 · BS EN 10257-1

Identification

Core identification
3-Core: Brown, Black, Grey
Outer sheath colour
Black (or Red HV) embossed 'MGM 118 TYPE

Sizes

6 standard configurations (MGM 118 Type 6010 / 6020)

Nominal dimensions, copper weights, DC resistance and current ratings for MGM 118 Type 6010 / 6020 per British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type

Dimensions & weights
Order designationCores × SizeMain cross-sectionOuter Ø ≈
mm
Copper
kg/km
Weight ≈
kg/km
Min. bend R
fixed mm
Enquiry
Standard MGM 118 Type 6010 / 6020 configurations
MGM 118 Type 6010 3C × 35 mm² SWA3 × 35 mm² (Type 6010 SWA)35.0 mm²40.21,1203,180482
MGM 118 Type 6010 3C × 70 mm² SWA (Cu/GSW)3 × 70 mm² (Type 6010 SWA)70.0 mm²47.42,2804,650569
MGM 118 Type 6010 3C × 120 mm² SWA (Cu/GSW)3 × 120 mm² (Type 6010 SWA)120.0 mm²55.83,9206,840670
MGM 118 Type 6020 3C × 50 mm² DWA (Cu/GSW)3 × 50 mm² (Type 6020 DWA)50.0 mm²47.81,5804,920574
MGM 118 Type 6020 3C × 95 mm² DWA (Cu/GSW)3 × 95 mm² (Type 6020 DWA)95.0 mm²56.63,0407,280679
MGM 118 Type 6020 3C × 185 mm² DWA (Cu/GSW)3 × 185 mm² (Type 6020 DWA)185.0 mm²69.25,92011,650830
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Outer diameters and weights are nominal factory values subject to ±5 % manufacturing tolerance per British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type 6020 DWA 3.8/6.6 kV).

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
11 kV AC dielectric & insulation resistance11,000 V AC for 5 min per MGM 118 / BS 6708100 % of drums
Phase & SWA/DWA armour DC resistance ratioArmour conductance ≥ 75 % of one phase conductor100 % of drums
Sample tests
EPR hot-set & galvanizing coat weightBS 7655-1.2 & BS EN 10257-1 wire checksPer production batch
Underground mining flame & impact testPass MGM 118 / BS 6708 mechanical and flame qualificationType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

British Coal MGM 118BS 6708CE / UKCA

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX MGM 118 TYPE 6010 / 6020
Delivery form
Non-returnable timber drums or heavy export
Standard drum lengths
250 m · 500 m · 1000 m · custom cut lengths
MOQ
100 m (stock variants) · 500 m (custom)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-20
Updated
2026-10-20

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

How do MGM 118 Type 6010 and Type 6020 decode?
Under British Coal Specification MGM 118 for 3.8/6.6 kV ('6') 3-core cables: the second digit '0' indicates unscreened phase cores; the third digit indicates armour ('1' = Single Wire Armour in Type 6010, '2' = Double Wire Armour in Type 6020); and the fourth digit '0' is the MGM 118 3-core 6.6 kV series identifier.
What is the difference between British Coal MGM 109 and MGM 118?
MGM 109 covers 640/1100 V (10xx series) and 1.9/3.3 kV (3xxx series) armoured mining roadway cables, whereas MGM 118 covers 3.8/6.6 kV (6xxx series) medium-voltage armoured mining trunk cables. Each production drum undergoes 100 % conductor DC resistance verification, insulation thickness gauging, and high-voltage
When is unscreened Type 6010/6020 specified instead of individually copper-screened Type 6110?
Type 6010 and Type 6020 are specified where existing underground 6.6 kV bolted cable couplers and transwitch terminal chambers are designed for unscreened coordinated-wall EPR cores with collective metallic armour earthing. Each production drum undergoes 100 % conductor DC resistance verification, insulation thickness gauging,
How does Type 6010/6020 achieve ≥ 75 % earth conductance at 6.6 kV?
High-conductivity tinned copper wires are stranded alongside the galvanized steel armour wires in calculated proportions so the metallic armour conductance is always ≥ 75 % of one phase conductor. Each production drum undergoes 100 % conductor DC resistance verification, insulation thickness gauging, and high-voltage

Request a quote

Get an engineering quote for MGM 118 Type 6010 / 6020

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

MGM 118 Type 6010 / 6020 Unscreened Armoured MV Feeder Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 