Fixed installation
Type 6010 SWA serves horizontal HV roadways; Type 6020 DWA supports vertical shaft drops and steep incline drifts.
Product
MGM 118 Type 6010 / 6020 Unscreened Armoured MV Feeder Cable is manufactured to British Coal Specification MGM 118 and BS 6708 for 3.8/6.6 kV underground mine roadway and shaft high-voltage distribution, featuring three Class 2 tinned copper conductors (25
Typical values for this cable type, based on British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type 6020 DWA 3.8/6.6 kV) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for 6.6 kV underground mine trunk roadways, pit-bottom HV substations,vertical shafts (Type 6020 DWA), and bolted 6.6 kV flameproof coupler distribution systems.
Type 6010 SWA serves horizontal HV roadways; Type 6020 DWA supports vertical shaft drops and steep incline drifts.
Unscreened 6.6 kV EPR cores fit directly into traditional compound-filled or elastomeric BS 6708 6.6 kV mining couplers.
Extruded PVC bedding and mining-grade outer PVC sheath protect the 6.6 kV core assembly in wet shafts.
Construction
Three circular stranded tinned annealed copper conductors (BS EN 60228 Class 2, 25 to 185 mm²), conductor semi-conductive stress control
| # | Layer | Material & reference |
|---|---|---|
| 1 | Stranded tinned copper conductor | BS EN 60228 Class 2 circular compacted tinned annealed copper (25 to 185 mm²)MGM 118 / BS EN 60228 |
| 2 | 6.6 kV EPR rubber insulation (90 °C) | Conductor stress-control layer + cross-linked 90 °C EPR insulation per BS 7655-1.2MGM 118 / BS 7655-1.2 |
| 3 | Extruded PVC inner bedding | Flame-retardant extruded PVC inner beddingMGM 118 |
| 4 | SWA (Type 6010) or DWA (Type 6020) ≥ | Single or double layer of galvanized steel round wires interspersed with tinned copperMGM 118 / BS 6708 |
| 5 | Mining flame-retardant PVC outer sheath | Heavy-duty abrasion- and flame-retardant PVC outer sheath, Black or HV RedMGM 118 / BS 7655 |
3.8/6.6 kV unscreened SWA feeder for horizontal underground roadways and pit-bottom switchrooms.
3.8/6.6 kV unscreened DWA feeder for vertical shafts, steep drifts, and high-crush longwall gates.
Technical data
Sizes
Nominal dimensions, copper weights, DC resistance and current ratings for MGM 118 Type 6010 / 6020 per British Coal MGM 118 / BS 6708 (Type 6010 SWA & Type
| Order designation | Cores × Size | Main cross-section | Outer Ø ≈ mm | Copper kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|
| Standard MGM 118 Type 6010 / 6020 configurations | |||||||
| MGM 118 Type 6010 3C × 35 mm² SWA | 3 × 35 mm² (Type 6010 SWA) | 35.0 mm² | 40.2 | 1,120 | 3,180 | 482 | |
| MGM 118 Type 6010 3C × 70 mm² SWA (Cu/GSW) | 3 × 70 mm² (Type 6010 SWA) | 70.0 mm² | 47.4 | 2,280 | 4,650 | 569 | |
| MGM 118 Type 6010 3C × 120 mm² SWA (Cu/GSW) | 3 × 120 mm² (Type 6010 SWA) | 120.0 mm² | 55.8 | 3,920 | 6,840 | 670 | |
| MGM 118 Type 6020 3C × 50 mm² DWA (Cu/GSW) | 3 × 50 mm² (Type 6020 DWA) | 50.0 mm² | 47.8 | 1,580 | 4,920 | 574 | |
| MGM 118 Type 6020 3C × 95 mm² DWA (Cu/GSW) | 3 × 95 mm² (Type 6020 DWA) | 95.0 mm² | 56.6 | 3,040 | 7,280 | 679 | |
| MGM 118 Type 6020 3C × 185 mm² DWA (Cu/GSW) | 3 × 185 mm² (Type 6020 DWA) | 185.0 mm² | 69.2 | 5,920 | 11,650 | 830 | |
| Configuration | Max. DC R @ 20 °C Ω/km | Iz free air A | Iz tray / duct A | Isc (1 s) kA | Voltage drop mV/A/m | Dielectric test V |
|---|---|---|---|---|---|---|
| 3 × 35 mm² (Type 6010 SWA) | 0.53 | 158 | 142 | 5.01 | 1.12 | 11,000 |
| 3 × 70 mm² (Type 6010 SWA) | 0.27 | 242 | 218 | 10.01 | 0.58 | 11,000 |
| 3 × 120 mm² (Type 6010 SWA) | 0.15 | 338 | 304 | 17.16 | 0.35 | 11,000 |
| 3 × 50 mm² (Type 6020 DWA) | 0.39 | 192 | 173 | 7.15 | 0.82 | 11,000 |
| 3 × 95 mm² (Type 6020 DWA) | 0.20 | 288 | 259 | 13.59 | 0.43 | 11,000 |
| 3 × 185 mm² (Type 6020 DWA) | 0.10 | 432 | 389 | 26.46 | 0.24 | 11,000 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 11 kV AC dielectric & insulation resistance | 11,000 V AC for 5 min per MGM 118 / BS 6708 | 100 % of drums |
| Phase & SWA/DWA armour DC resistance ratio | Armour conductance ≥ 75 % of one phase conductor | 100 % of drums |
| Sample tests | ||
| EPR hot-set & galvanizing coat weight | BS 7655-1.2 & BS EN 10257-1 wire checks | Per production batch |
| Underground mining flame & impact test | Pass MGM 118 / BS 6708 mechanical and flame qualification | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.