Fixed installation
Mica glass-fibre fire barrier or ceramifying silicone insulation maintains circuit integrity during 750–1,100 °C fire exposure.
Product
MHXCH FE120 & MHXH FE120 0.6/1 kV & FMHXCH FE120 250 V S95 Ceramized-Elastomer Insulated Copper-Braided SHF1 Fire-Resistant Shipboard Cable (IEC 60331 / IEC 60092-353, 0.6/1 kV, -40 to +90 °C, min. bend radius 6 × OD).
Typical values for this cable type, based on IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer — confirmed in the datasheet and quotation for your order.
Application fit
MHXCH FE120 & MHXH FE120 0.6/1 kV & FMHXCH FE120 250 V S95 Ceramized-Elastomer Insulated Copper-Braided SHF1 Fire-Resistant Shipboard Cable (IEC 60331 / IEC 60092-353, 0.6/1 kV, -40 to +90 °C, min. bend radius 6 × OD).
Mica glass-fibre fire barrier or ceramifying silicone insulation maintains circuit integrity during 750–1,100 °C fire exposure.
Low-smoke zero-halogen SHF1/SHF2/SW4 sheath minimizes toxic gas and smoke opacity during marine evacuation.
Metallic wire braid armour resists mechanical shock, water spray (+WSR) and water jet (+WJR) firefighting impact.
Terminates directly into emergency switchboards, fire-alarm panels, PA/GA systems and watertight glands.
Mica-taped fire-resistant shipboard cable is designed for fixed installation, not continuous reeling drums.
Use HVSC Shore Power Reeling CableConstruction
Shown: MHXCH FE120 & FMHXCH FE120 (IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer) featuring tinned copper conductors (7×1.5 mm²), s95 ceramifying silicone insulation (hx) and shf1 halogen-free outer sheath (5-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Tinned Copper Conductors (7×1.5 mm²) | Stranded tinned annealed copper conductors |
| 2 | S95 Ceramifying Silicone Insulation (HX) | Cross-linked silicone elastomer forming protective ceramic shell in fire (FE120) |
| 3 | Halogen-Free Inner Covering | Flame-retardant halogen-free bedding compound and glass tape |
| 4 | Copper Wire Braid Screen (C) | High-coverage copper wire braid for EMC and mechanical protection |
| 5 | SHF1 Halogen-Free Outer Sheath | Low-smoke zero-halogen polyolefin jacket |
Built to IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer with tinned copper conductors (7×1.5 mm²) and shf1 halogen-free outer sheath
Available in custom continuous shipboard/offshore drum lengths or with marine EMC cable glands
Supplied with EN 10204 3.1 routine dielectric, conductor resistance & flame/fire test report
Technical data
Sizes
Manufactured to IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer for shipboard, offshore platform, drilling rig and marine applications.
| Order designation | Configuration | Core / stranding | Outer Ø ≈ mm | Net weight ≈ kg/km | Tensile rating kN ≈ | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| MHXCH FE120 & FMHXCH FE120 Construction Schedule (−40…+90 °C) | |||||||
| MHXCH FE120 4G2.5 mm² | 4 × 2.5 mm² (or 4C × 14 AWG) | IEC 60228 Class 2/5 Cu/SnCu | 13.2 | 275 | 1.5 | 80 | |
| MHXCH FE120 7G2.5 mm² | 7 × 2.5 mm² (or 7C × 14 AWG) | IEC 60228 Class 2/5 Cu/SnCu | 15.8 | 415 | 2.6 | 95 | |
| MHXCH FE120 12G1.5 mm² | 12 × 1.5 mm² (or 12C × 16 AWG) | IEC 60228 Class 2/5 Cu/SnCu | 17.4 | 495 | 2.7 | 105 | |
| Configuration | Max. DC R₂₀ / Atten. Ω/km or dB/km | Rating / Impedance | Operating temp. |
|---|---|---|---|
| 4 × 2.5 mm² (or 4C × 14 AWG) | 7.98 | 0.6/1 kV (26 A) | −40…+90 °C |
| 7 × 2.5 mm² (or 7C × 14 AWG) | 7.98 | 0.6/1 kV (21 A) | −40…+90 °C |
| 12 × 1.5 mm² (or 12C × 16 AWG) | 13.30 | 0.6/1 kV (14 A) | −40…+90 °C |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance, continuity & dimensional verification (IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer) | DC resistance at 20 °C / optical attenuation and outer diameter within IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer tolerances | Every manufactured drum length |
| High-voltage dielectric & insulation resistance test (IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer) | Zero dielectric breakdown and verified insulation resistance for 0.6/1 kV rating | Every manufactured drum length |
| Sample tests | ||
| Flame, fire integrity, oil/mud & mechanical qualification (IEC 60331 (FE120) / IEC 60092-353 & 60092-376 S95 Ceramifying Elastomer) | Verified flame/fire performance, fluid resistance and thermal stability across −40…+90 °C | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.